Indoor Unit Installation

6.

Drain piping.

1) Connect the drain hose, as described right.

2) Remove the air filters and pour some water into the drain pan to check the water 

flows smoothly.

3) When drain hose requires extension, obtain an extension hose commercially avail-

able. 
Be sure to thermally insulate the indoor section of the extension hose.

4) When connecting a rigid polyvinyl chloride pipe 

(nominal diameter 13mm) directly to the drain 
hose attached to the indoor unit as with embed-
ded piping work, use any commercially available 
drain socket (nominal diameter 13mm) as a 
joint.

Refrigerant piping work

, install as described in the installation manual supplied with the Multi outdoor unit.

1.

Flaring the pipe end.

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing downward 

so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.

The drain hose should 
be inclined downward.

No trap is permitted.

Do not put the end 
of the hose in water.

Indoor unit 
drain hose

φ

18

Extension drain hose

Heat insulation tube
(Field supply)

Drain hose supplied with 
the indoor unit

Commercially available drain 
socket 
(nominal diameter 13mm)

Commercially available rigid 
polyvinyl chloride pipe
(nominal diameter 13mm)

φ

18

With a Multi indoor unit

Set exactly at the position shown below.

A

Flaring

Die

A

0 ~ 0.5mm

Clutch-type

Flare tool for R410A

1.0 ~ 1.5mm

Clutch-type (Rigid-type)

1.5 ~ 2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

(Cut exactly at 

right angles.)

 Remove burrs

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

01_EN_3P170836-1.fm  Page 9  Thursday, October 20, 2005  3:18 PM

Содержание FTXS50EV1B

Страница 1: ...tion manual R410A Split series Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A Split systeem Manual de instalaci n Serie Split R410A Manual...

Страница 2: ...MC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF 015 74736 KRQ EMC97 4957 Daikin TCF...

Страница 3: ...due force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire If any refrigerant has leaked out durin...

Страница 4: ...er 1 Turn on all the fluorescent lamps in the room if any and find the site where remote control signals are properly received by the indoor unit within 7 metres Installation Tips 1 Removing and insta...

Страница 5: ...nd firmly engage the upper hooks 3 locations 2 Install 3screws of the front grill 3 Install the air filter and then mount the front panel 3 How to set the different addresses When two indoor units are...

Страница 6: ...propriate length and wrap it with tape making sure that no gap is left in the insulation pipe s cut line Caulk pipe hole gap with putty Screws Field supply The mounting plate should be installed on a...

Страница 7: ...ews Recommended mounting plate retention spots and Dimensions 125 60 83 503 5 44 5 290 52 1050 99 5 52 90 55 100 100 Through the wall hole 80mm Drain hose position 80 80 Recommended mounting plate ret...

Страница 8: ...op of the indoor unit as a guide 4 Open the front panel then open the service lid Refer to Installation tips 5 Pass the interconnecting wires from the outdoor unit through the feed through wall hole a...

Страница 9: ...ate hooks Secure indoor unit to the mounting plate with screws M4 12L 3 3 Wall Embedded Piping Follow the instructions given under 1 Insert the drain hose to this depth so it wont be pulled out of the...

Страница 10: ...the electrical wiring box 1 screw 3 Remove the metal plate electrical wiring cover 4 tabs 4 Attach the connection cord to the S21 connector and pull the harness out through the notched part in the fi...

Страница 11: ...from getting into the system as this would reduce the lifetime of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with the unit 4 Do nev...

Страница 12: ...2 Be sure to insulate both the gas and liquid piping and to provide insulation dimen sions as below 3 Use separate thermal insulation pipes for gas and liquid refrigerant pipes Gas side Liquid side G...

Страница 13: ...ner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the...

Страница 14: ...0511 HT 3P170836 1 M05B096 00_CV_3P170836 1 fm Page 2 Thursday October 20 2005 9 43 AM...

Отзывы: