SiBE041213E
Troubleshooting
Service Diagnosis
86
Troubleshooting
In case of “
H9
” “
J3
” “
J6
”
H9
: Outdoor temperature thermistor
J3
: Discharge pipe thermistor
J6
: Outdoor heat exchanger thermistor
Check No.01
Refer to P.92
(R16059)
Caution
NO
YES
YES
NO
NO
YES
Turn on the power again.
Normal?
Reconnect the connectors
or thermistors.
J3
error: the discharge
pipe temperature is
lower than the heat
exchanger temperature.
Replace the defective
thermistor(s) of the following
thermistors.
∗
Outdoor temperature
thermistor
∗
Discharge pipe thermistor
∗
Outdoor heat exchanger
thermistor
Cooling: Outdoor heat
exchanger
temperature
Heating: Indoor heat
exchanger
temperature
Replace the indoor heat
exchanger thermistor.
Replace the outdoor unit
PCB.
Error displayed
again on remote
controller?
Indoor heat
exchanger thermistor
functioning?
Check No. 01
Check the thermistor resistance
value.
Check No. 01
Check the indoor heat exchanger
thermistor resistance value in the
heating operation.
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание FTXS35K2V1B
Страница 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49...
Страница 111: ...SiBE041213E Check Service Diagnosis 100 42 class 50 class R12266 Tester 1 2 3 4 Tester 1 2 3 4 R14700...
Страница 113: ...SiBE041213E Check Service Diagnosis 102 42 class 50 class R18241 Power module Power module R16692...
Страница 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition...