Troubleshooting
SiBE041213E
85
Service Diagnosis
4.21 Thermistor or Related Abnormality (Outdoor Unit)
Error Code
H9
,
J3
,
J6
,
P4
Method of Error
Detection
This fault is identified based on the thermistor input voltage to the microcomputer.
A thermistor fault is identified based on the temperature sensed by each thermistor.
Error Decision
Conditions
The thermistor input voltage is above 4.96 V or below 0.04 V with the power on.
J3
error is judged if the discharge pipe temperature is lower than the heat exchanger
temperature.
Supposed
Causes
Disconnection of the connector for the thermistor
Thermistor corresponding to the error code is defective
Defective heat exchanger thermistor in the case of
J3
error (outdoor heat exchanger
thermistor in cooling operation, or indoor heat exchanger thermistor in heating operation)
Defective outdoor unit PCB
Troubleshooting
In case of “
P4
”
Replace the outdoor unit PCB.
P4
: Radiation fin thermistor
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
Содержание FTXS35K2V1B
Страница 12: ...SiBE041213E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiBE041213E 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 59: ...SiBE041213E Remote Controller 48 Part 5 Remote Controller 1 Remote Controller 49...
Страница 111: ...SiBE041213E Check Service Diagnosis 100 42 class 50 class R12266 Tester 1 2 3 4 Tester 1 2 3 4 R14700...
Страница 113: ...SiBE041213E Check Service Diagnosis 102 42 class 50 class R18241 Power module Power module R16692...
Страница 129: ...Revision History Month Year Version Revised contents 05 2013 SiBE041213E First edition...