11
Application Information
Unit Installation
15.0
538.0
18.0
38.0
505.0
32.0
580.0 ~ 610mm (CEILING OPENING MEASUREMENT)
580.0 ~ 610mm (CEILING OPENING MEASUREMENT)
529.0
88.0
448.0
19.0
FFQ-CXV1
• The indoor unit must be away from heat and steam sources (avoid installing it near an entrance).
• Measure and mark the position for the hanging rod. Drill the hole for the angle nut on the ceiling and
fi
x the
hanging rod.
• The installation template is extended according to temperature and humidity. Check on dimensions in
using.
• The dimensions of the installation template are same as those of the ceiling opening dimensions.
• Before ceiling laminating work is completed, be sure to
fi
t the installation template to the indoor unit.
Note: Be sure to discuss the ceiling drilling work with the installers concerned.
Unit Hanging
Indoor Unit
Ceiling
Board
30.0mm
FFQ-CXV1
• Con
fi
rm the pitch of the hanging rod is 770mm x 622mm sharp.
• Hold the unit and hand it on the hanging rod with the nut and washer.
• Adjust the unit height to 35.0mm between the indoor unit bottom surface and the ceiling surface.
• Con
fi
rm with a level gauge that the unit is installed horizontally and tighten the nut and bolt to prevent unit
falling and vibration.
• Open the ceiling board along the outer edge of the paper installation template.
Содержание FTXN25MV1B
Страница 2: ......
Страница 4: ...ii...
Страница 11: ...7 Application Information Refrigerant Circuit Diagrams Model 2MX45BGXV1 2MX50BGXV1 Model 3MX60BGXV1 4MX80BGXV1...
Страница 33: ...29 Outline Dimension Indoor Unit Model FLQ35 50 1080 0 928 0 218 0 65 0 630 0 400 0 230 0 Note Dimension in mm...
Страница 36: ...32 Wiring Diagram Indoor Unit Model FTXN25 35MV1 Indoor Unit Model FTXN50MV1...
Страница 37: ...33 Wiring Diagram Indoor Unit Model FFQ25 35 50CXV1 Indoor Unit Model FDMQ25 35C2XV1...
Страница 38: ...34 Wiring Diagram Indoor Unit Model FDMQ50CXV1 Indoor Unit Model FLQ35EXV1...
Страница 39: ...35 Wiring Diagram Indoor Unit Model FLQ50EXV1...
Страница 50: ......