41
Troubleshooting
Error Codes
Error Codes
Error Description
Action
0
Normal No
action.
U0
Insuf
fi
cient gas
1. Check sensor connection.
2. Check stop valve.
3. Check for gas leak.
4. Check the EXV.
5. Check H8.
U2
DC voltage out of range
1. Check the supply voltage.
2. Check the outdoor fan by rotating with hand.
3. Restart the system.
4. Check power supply waveform.
U4
Communication error
1. Check the indoor unit - outdoor unit connection wires.
2. Check the voltage of the signal terminal.
3. Check the indoor fan by rotating with hand.
4. Check the power supply waveform.
U7
Signal transmission error
(on outdoor unit PCB)
1. Restart the system.
2. Replace outdoor PCB.
3. Long term monitor on external factor.
UA
Installation error
1. Check the indoor and outdoor unit model name.
2. Check the part code on the indoor and outdoor PCB.
UF
Communication Error (indoor and
outdoor) piping and wiring
1. Check the wiring and piping between indoor and outdoor units.
2. Check refrigerant level.
3. Check refrigerant line on blockage.
UH
Anti-freeze function in other room
1. Check which indoor having error A5.
2. Check the supply voltage.
3. Check the indoor and outdoor model name.
A1
Indoor PCB error
1. Check connector connection.
2. Replace indoor PCB.
A3
Water pump error
1. Check for short circuit.
2. Check connection on drain pump.
3. Restart the system.
4. Check the drain water level.
5. Check
fl
oat switch connection.
A5
Antifreeze
1. Check the air passage.
2. Check the intake air
fi
lter.
3. Check dust accumulation on indoor coil.
4. Check wiring and piping.
5. Check the EXV.
6. Check indoor coil sensor resistance value.
7. Check refrigerant level.
8. Check room sensor resistance value.
A6
Indoor fan motor abnormal
1. Check the indoor fan by rotating with hand.
2. Replace indoor fan motor if not rotating smoothly.
3. Check fan motor voltage.
4. Replace indoor PCB if not at the rated voltage.
5. Check fan capacitor’s conductivity (AC Motor).
6. Replace fan capacitor if there’s conductivity.
C4
Indoor heat exchanger thermistor short/
open
1. Check the connector connection.
2. Check the sensor resistance value.
C9
Indoor room thermistor short/open
Содержание FTXN25MV1B
Страница 2: ......
Страница 4: ...ii...
Страница 11: ...7 Application Information Refrigerant Circuit Diagrams Model 2MX45BGXV1 2MX50BGXV1 Model 3MX60BGXV1 4MX80BGXV1...
Страница 33: ...29 Outline Dimension Indoor Unit Model FLQ35 50 1080 0 928 0 218 0 65 0 630 0 400 0 230 0 Note Dimension in mm...
Страница 36: ...32 Wiring Diagram Indoor Unit Model FTXN25 35MV1 Indoor Unit Model FTXN50MV1...
Страница 37: ...33 Wiring Diagram Indoor Unit Model FFQ25 35 50CXV1 Indoor Unit Model FDMQ25 35C2XV1...
Страница 38: ...34 Wiring Diagram Indoor Unit Model FDMQ50CXV1 Indoor Unit Model FLQ35EXV1...
Страница 39: ...35 Wiring Diagram Indoor Unit Model FLQ50EXV1...
Страница 50: ......