Si04-402A
Troubleshooting
Service Diagnosis
103
4.24
Over-voltage Detection
Remote
Controller
Display
U2
Method of
Malfunction
Detection
An abnormal voltage rise is detected by checking the specified over-voltage detection circuit.
Malfunction
Decision
Conditions
An over-voltage signal is fed from the over-voltage detection circuit to the microcomputer
(The voltage is over 400V).
The system will be shut down if the error occurs 255 times.
Clearing condition: Continuous run for about 10 minutes (normal)
Supposed
Causes
Supply voltage not as specified
Over-voltage detection circuit defective
PAM control part(s) defective
Troubleshooting
Note:
If the model doesn’t have SPM, replace the outdoor unit PCB.
Check the supply voltage.
Correct the power supply.
Check for such factors for a
long term.
Replace the SPM.
(Replace the outdoor unit
PCB.)
(R2957)
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Supply voltage as
specified?
NO
YES
Turn on the
power again.
Error displayed again?
YES
Repeat a
couple of times.
NO
Disturbance factors
∗
Noise
∗
Power supply distortion
Содержание FTXG25CVMAW
Страница 1: ...Inverter Pair Wall Mounted Type C Series Applied Models z z z zInverter Pair Heat Pump Si04 402A...
Страница 23: ...Printed Circuit Board Connector Wiring Diagram Si04 402A 14 Printed Circuit Board Connector Wiring Diagram...
Страница 167: ...Outdoor Unit Si04 402A 158 Removal Procedure When reassembling make sure to fit the hook Step Procedure Points...
Страница 181: ...Outdoor Unit Si04 402A 172 Removal Procedure...
Страница 185: ...Others Si04 402A 176 Others...
Страница 189: ...Wiring Diagrams Si04 402A 180 Appendix...