Control Specification
SiBE041012_B
52
Function and Control
3.8
Outdoor Fan Control
1. Fan ON control to cool down the electrical box
The outdoor fan is turned ON when the electrical box temperature is high while the compressor
is OFF.
2. Fan OFF control during defrosting
The outdoor fan is turned OFF during defrosting.
3. Fan OFF delay when stopped
The outdoor fan is turned OFF 60 seconds after the compressor stops.
4. Fan speed control for pressure difference upkeep
The rotation speed of the outdoor fan is controlled for keeping the pressure difference during
cooling operation with low outdoor temperature.
When the pressure difference is low, the rotation speed of the outdoor fan is reduced.
When the pressure difference is high, the rotation speed of the outdoor fan is controlled as
well as normal operation.
5. Fan speed control during forced cooling operation
The outdoor fan is controlled as well as normal operation during forced cooling operation.
6. Fan speed control during POWERFUL operation
The rotation speed of the outdoor fan is increased during POWERFUL operation.
7. Fan speed control during indoor / outdoor unit quiet operation
The rotation speed of the outdoor fan is reduced by the command of the indoor / outdoor unit
quiet operation.
8. Fan ON/OFF control when operation starts / stops
The outdoor fan is turned ON when the operation starts. The outdoor fan is turned OFF when
the operation stops.
3.9
Liquid Compression Protection Function
Outline
In order to obtain the dependability of the compressor, the compressor is stopped according to
the outdoor temperature and the outdoor heat exchanger temperature.
Detail
Operation stops depending on the outdoor temperature.
Compressor turns off under the conditions that the system is in cooling operation and outdoor
temperature is below –12°C.
Содержание FTXG-J
Страница 11: ...SiBE041012_B List of Functions 1 Part 1 List of Functions 1 Functions 2 ...
Страница 15: ...SiBE041012_B Specifications 5 Part 2 Specifications 1 Specifications 6 ...
Страница 68: ...SiBE041012_B 58 Remote Controller Part 5 Remote Controller 1 FTXG25 35 50JV1BW S A 59 ...
Страница 131: ...SiBE041012_B Check Service Diagnosis 121 RXG50K2V1B RXG50K3V1B R16073 Power module Power module R16692 ...