3.5
Input Current Control
Outline
The microcomputer calculates the input current while the compressor is running, and sets the
frequency upper limit based on the input current.
In case of heat pump models, this control is the upper limit control of frequency and takes priority
over the lower limit control of four way valve operation compensation.
Detail
Frequency control in each zone
Stop zone
After the input current remains in the stop zone for 2.5 seconds, the compressor is stopped.
Dropping zone
The upper limit of the compressor frequency is defined as operation frequency – 2 Hz.
After this, the output frequency is lowered by 2 Hz every second until it reaches the keep zone.
Keep zone
The present maximum frequency goes on.
Reset zone
Limit of the frequency is canceled.
Limitation of current dropping and stop value according to the outdoor temperature
The current drops when outdoor temperature becomes higher than a certain level (depending
on the model).
09 class
12 class
15 class
Cooling
Heating
Cooling
Heating
Cooling
Heating
A
(A)
12
13
18
B
(A)
7.5
8.5
11.5
12
12
12
C
(A)
6.5
7.5
10.75
11.25
11
11
Compressor Stop
Input current
Dropping zone
Stop zone
Keep zone
Reset zone
(R23249)
A
(A)
B
C
Содержание FTX09NMVJU
Страница 12: ...SiUS091601E 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 15: ...SiUS091601E Specifications 4 Part 2 Specifications 1 Specifications 5...
Страница 65: ...SiUS091601E Remote Controller 54 Part 5 Remote Controller 1 FTX Series 55 2 FVXS Series 57...
Страница 121: ...SiUS091601E Check Service Diagnosis 110 12 class 15 class Multimeter R23024 R20701 1 2 3 4 Multimeter...
Страница 144: ...Revision History Month Year Version Revised contents 02 2016 SiUS091601E First edition...