13
Installation Guideline
2.
Drilling A Wall Hole And Installing Wall Embedded Pipe
3.
Installing Indoor Unit
• For walls containing metal frame or metal board, be
sure to use a wall embedded pipe and wall cover in the
feed-through hole to prevent possible heat, electrical
shock, or fire.
• Be sure to caulk the gaps around the pipes with
caulking material to prevent water leakage.
1) Drill a feed-through hole of 65mm in the wall so it has a
down slope toward the outside.
2) Insert a wall pipe into the hole.
3) Insert a wall cover into wall pipe.
4) After completing refrigerant piping, wiring, and drain
piping, caulk pipe hole gap with putty.
Inside
Outside
Caulking (Putty)
(Field supply)
Wall embedded pipe
(Field supply)
Wall hole cover
(Field supply)
Wall embedded pipe
(Field supply)
Ø 65
Right-side, right-back, or right-bottom piping.
Right-back piping
Right-bottom
piping
Right-side piping
Remove pipe port cover
here for right-side piping
Remove pipe port cover
here for right-bottom piping
Bind refrigerant pipe
and drain hose together
with insulation tape.
Inter-unit wire
Wire guide
Hang indoor unit’s hook here.
Mounting plate
When stripping the
ends of inter-unit wire
in advance, bundle
the wire lead ends
with insulation tape.
Mounting plate
Left-side, left-back, or left-bottom piping.
How to replace the drain plug and drain hose
• Removal method
1) Rotate to detach wire clip from hook on the right and
remove the drain hose.
2) Remove the drain plug on the left side and attach it
to the right side.
3) Insert the drain hose and tighten by rotating the
wire clip to hook.
Forgetting to tighten this may cause water leakages.
Drain hose attachment position
The drain hose is on the back of the unit.
1) Attach the drain hose to the underside of the refrigerant
pipes with adhesive vinyl tape.
2) Wrap the refrigerant pipes and drain hose together with
insulation tape.
3) Pass the drain hose and refrigerant pipes through the wall
hole, then set the indoor unit on the mounting plate hooks by
using the markings at the top of the indoor unit as a guide.
4) Open the front panel, then open the service lid.
(Refer to installation tips.)
5) Pass the inter-unit wire from the outdoor unit through the
feed-through wall hole and then through the back of the
indoor unit. Pull them through the front side. Bend the ends
of cable tie wires upward for easier work in advance. (If the
inter-unit wire ends are to be stripped first, bundle the wire
lead ends with adhesive tape.)
6) Press the bottom frame of the indoor unit with both hands to
set it on the mounting plate hooks. Make sure the wire leads
do not catch on the edge of the indoor unit.
Left side
Right side
Front side of unit
Attachment on the left side
Wire clip
Attachment on the right side
(factory default)
Drain hose
Drain hose
Wire clip
Содержание FTV-A Series
Страница 1: ...TM FTV 1020 F Split Unit Air Conditioner Wall Mounted FTV A P PS Series Cooling Only 50Hz...
Страница 2: ......
Страница 30: ...28 Dimensions Model FTV85PS Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Страница 33: ...31 Dimensions Model RC85A Note Dimension in mm FOR ILLUSTRATIVE PURPOSES ONLY...
Страница 35: ...33 Wiring Diagram Model RV35A Model RV50 60A R08024149386 3P548018 1...
Страница 37: ...35 Wiring Diagram Model FTV50 60P Outdoor Unit Model RV50 60C R08024149860A R08024145839...
Страница 44: ...42 Piping Diagram Model RV50 60C Note Dimension in mm Model RC85A Note Dimension in mm 3D121531...
Страница 56: ...54 Capacity Tables FTV28P RV28F FTV35P RV35F...
Страница 68: ...66 Sound Level FTV85PS...