background image

SAFETY PRECAUTIONS 

• The precautions described herein are classified as WARNING  and CAUTION. They both contain important 

information regarding safety.  Be sure to observe all precautions without fail. 

•  Meaning of WARNING  and CAUTION notices 

� WARNING 

Failure to follow these instructions properly may result in personal injury or loss of life. 

� CAUTION 

Failure to observe these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances. 

• The safety  marks shown in this manual have the following meanings: 

I  Be sure to follow the instnuctions. 

Be sure to establish an earth connection. 

(S) 

Never attempt. 

• After completing installation,  conduct a trial operation to check for faults and explain to the customer how to 

operate the air conditioner and take care of it with the aid of the operation manual. 

�  WARNING 

• Ask your dealer or qualified  personnel to carry out installation work. 

Do not  attempt  to  install the air conditioner yourself.  Improper installation may  result in water  leakage,  electric  shocks  or fire. 

•  Install the air conditioner in accordance with the instructions in this installation manual.  Improper instanation may result in water leakage, electric shocks or fire. 
•  Be sure to use only the specified accessories and parts for installation work. Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to withstand the weight of the unit. A foundation of •sufficient streng� may result in �e equipment falling and causing •��-
• Electrical work must be perfonmed in accordance with relevant local and national regulations and with instructions in this installation manual. 

Be sure  to  use  a dedicated  power supply circuit only.  Insufficiency of power circuit capacity and improper workmanship may result in electric shocks or fire. 

•  Use  a  cable  of suitable  length.  Do not use  tapped  wires or an extension  lead, as this may cause overheating,  electric  shocks  or fire. 

• Make sure that all wiring is secured,  the specified wires are used, and that there is no strain on the terminal 

connections  or wires.  Improper connections or securing of wires may result in abnormal heat build-up or fire. 

• When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the 

control box lid can  be securely fas tened.  Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals. 

• If refrigerant gas leaks  during  installation,  ventilate the area immediately. 

0

Toxic gas may be produced  if the refrigerant comes into contact with fire. 

• After completing installation, check for refrigerant gas leakage. Toxic gas may be produced if the refrigerant gas 

0

leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker. 

• When installing or relocating the air conditioner, be sure to bleed the refrigerant circuit to ensure it is free of air, and use only the specified 

refrigerant (R32). The presence of air or other foreign matter in the refrigerant circutt causes abnormal pressure rise, which may result in equipment damage and even injury. 

•  During installation, attach the refrigerant piping securely before running the compressor. If the refrigerant pipes are not attached and the stop 

valve is open when the compressor is run, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

•  During pump-down, stop the compressor before removing the refrigerant piping. If the compressor is stil running and the stop valve is open during pump-down, 

air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury. 

• Be sure to earth the air conditioner. 

0

Do not earth the unit to a utility pipe,  lightning conductor or telephone earth lead.  Imperfect earthing may result in electric  shocks. 

•  Be sure  to  install  an earth leakage  circuit b reaker.  Failure to install an earth leakage circuit breaker may result in electric shocks or fire. 

• Do not pump down when the refrigerant has leaked, otherwise the compressor may be damaged. 

�  CAUTION 

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

(S) 

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out. 

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate 

piping  to  prevent condensation.  Improper drain piping may result in indoor water leakage and property damage. 

• Tighten the flare nut according to the specified method such as with a torque wrench. If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage. 
• Take adequate steps to  prevent the outdoor unit being used as a shelter by small animals. 

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean. 

• The temperature of refrigerant circuit will be high, please keep the inter-unit wires away from copper pipes that are not thenmally insulated. 

Содержание FTL28UV16W1

Страница 1: ...OPERATION MANUAL l D 1j r a 7c I MODELS F GTL28UV16W1 F GTL35UV16W1 F GTL35UV16W3 F GTL50UV16U3 F GTL50UV16V3 F GTL50UV16V7 F GTL50UV16V5 F GTE60UV16U2 F GTQ60UV16U5 F GTL50UV16U2 F GTL50UV16V2 F GTQ...

Страница 2: ...e performance quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that prod...

Страница 3: ...1 Signal receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop...

Страница 4: ...ration mode DRY COOUFAN 9 ECONO button 10 TIMER CANCEL button It cancels the timer setting 11 ON TIMER button 12 OFF TIMER button 13 COANDA button COANDA operation 14 GOOD SLEEP button NOTE Notes on r...

Страница 5: ...t get it wet The maximum transmission distance is about 7m To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor unit When attaching the accessory...

Страница 6: ...remote the default set temperature will be set as mentioned in below table Mode Set temperature before remote switched OFF Set temperature after remote switched ON Cool If set temperature 24 C Defaul...

Страница 7: ...1 minute after the operation is started However if the POWER CHILL operation is started air starts circulating immediately NOTE Note on airflow rate setting At smaller airflow rates the cooling effec...

Страница 8: ...flaps reach the desired position The flaps will stop moving disappears from the LCD Right and left airflow direction To adjust the louvres at desired position Hold the knobs and move the louvres vert...

Страница 9: ...again disappears from the LCD Notes on ECONO operation ECONO operation can only be set when the unit is running Pressing t1 causes the settings to be cancelled and disappears from the LCD ECONO operat...

Страница 10: ...C O C OFF and the stop time default 2HR are displayed on the LCD ON OFF c J The TIMER lamp lights orange 0 1 TEMP ISP ay 2 Press v while C is blinking Each pressing of the button changes tempera ture...

Страница 11: ...it toward you to disengage one of the front panel shafts Disengage the front panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward your...

Страница 12: ...nt panel Insert the filters into slots of the front grille Close the front panel slowly and push the panel at the 3 points g c A c i I Accessory filter I Filter type Ag ion filter Micro filter PM2 5 1...

Страница 13: ...filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Mirco filter PM1 0 1 set Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Prior to a long period of...

Страница 14: ...arge voltage fluctuations It automatically resumes operation in about 3 minutes A sound is heard A sound like flowing water This sound is generated because the refrigerant in the air conditioner is fl...

Страница 15: ...ool down Is the airflow rate setting appropriate If the airflow rate setting is too low increase it Is the set temperature appropriate Is the adjustment of the airflow direction appropriate Are the ai...

Страница 16: ...er and call your service centre The air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood s...

Страница 17: ...R MAIN CIRCUIT OVERVOLTAGE U4 FAILURE OF TRANSMISSION BETWEEN INDOOR UNIT AND OUTDOOR UNIT A1 INDOOR PCB DEFECTIVENESS A5 FREEZE UP PROTECTOR INDOOR A6 FAN MOTOR FAULT UNIT C4 FAULTY HEAT EXCHANGER TE...

Страница 18: ......

Страница 19: ......

Страница 20: ......

Страница 21: ...ALLATION MANUAL l J ffi 1 i i J MODELS F GTL28UV16W1 F GTL35UV16W1 F GTL35UV16W3 F GTL50UV16U3 F GTL50UV16V3 F GTL50UV16V7 F GTL50UV16V5 F GTE60UV16U2 F GTQ60UV16U5 F GTL50UV16U2 F GTL50UV16V2 F GTQ50...

Страница 22: ...nt gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leak...

Страница 23: ...the unit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby fflGi l li11 114 The outdoor unit should be posi...

Страница 24: ...o 1100 610 Liquid pipeend Gaspipeend Drainhose position Applicable Unit Size Type H X W X D A B C i 298 X 800 X 229 800 116 5 116 5 298 X 821 X 229 821 128 126 5 298 X 885 X 229 885 116 5 116 5 298 X...

Страница 25: ...oor unit to the A mounting plate with the E indoor unit fixing screws M4 x 12L 10 Caulk thegap between the pipe and the front grillewith putty 11 After completing refrigerant piping wiring and drain p...

Страница 26: ...the unit it WARNING ____________________________________1_a1J_1 _N_ _ 4 Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as...

Страница 27: ...ed too much it may cause condensation or water dripping f Heat insulationpipe cover Slit 1111q11111J Slit Vinyl tape This illustration shows the case of the left rear piping Sectional view wire Insula...

Страница 28: ...s 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of O...

Страница 29: ...When there is no work space because the unit is close to ceiling CAUTION 1 Push up Be sure to wear protection gloves Place both hands under the centre of the front grille and while pushing up pull it...

Страница 30: ...6 27 4N m 0 D 9 5mm 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 48 1 59 7N m 505 615 kgf cmJ 490 61O kgf cm I 10 8 14 7N m 0 D 15 9mm 61 8 75 4N m 110 150 kgf cm 630 770 kgf cm 14 2...

Страница 31: ...asstop valve sservice port then fully openliquidand gasstop valves Do not attempt to turn valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas stop valves with a...

Страница 32: ...tion noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Draining line is properly install...

Страница 33: ...020 Meaning of E waste under E Waste Management Rules 2022 E waste Rules Waste electrical and electronic equipment whole or in part of reject from their manufacturing and repair process which are inte...

Отзывы: