SiMT041509E
Troubleshooting
Service Diagnosis
60
Troubleshooting
Correct the power supply.
Replace the outdoor
unit PCB (main PCB).
Check for such factors for a
long term.
(R20413)
Caution
Be sure to turn off the power switch before connecting or disconnecting
connectors, or parts may be damaged.
NO
NO
YES
YES
NO
YES
YES
Reconnect the harness.
Check the power supply voltage.
Check the connection of the
compressor harness.
Disturbance factors
∗
Noise
∗
Power supply distortion
(Precaution before turning on the power again)
Make sure the power has been off for at
least 30 seconds.
Replace the indoor
unit PCB (control PCB).
Turn on
the power. System
restarted? (Repeat a few
times.)
Error
again
within
3 minutes
after turning on the
power?
Loose or
disconnected?
NO
YES
NO
Replace the outdoor fan motor
and the outdoor unit PCB
(main PCB).
Does the
outdoor fan rotate
smoothly?
Is the
voltage fluctuation
within ±10% from the
rated value?
Содержание FTKM18PVMK
Страница 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45 ...
Страница 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition ...