SiMT041509E
Control Specification
Function and Control
38
3.6
Freeze-up Protection Control
During cooling operation, the signal sent from the indoor unit determines the frequency upper
limit and prevents freezing of the indoor heat exchanger. (The signal from the indoor unit is
divided into zones.)
The operating frequency limitation is judged with the indoor heat exchanger temperature.
3.7
Heating Peak-cut Control
During heating operation, the indoor heat exchanger temperature determines the frequency
upper limit to prevent abnormal high pressure.
The operating frequency limitation is judged with the indoor heat exchanger temperature.
A
(°C)
B
(°C)
C
(°C)
7
5
3
(R22433)
Reset zone
Indoor heat exchanger
thermistor temperature
Up zone
Keep zone
Dropping zone
Stop zone
0˚C
C
˚C
B
˚C
A
˚C
13˚C
A
(°C)
B
(°C)
C
(°C)
D
(°C)
E
(°C)
60
54
51
49
44
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
Indoor heat exchanger
thermistor temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
(R22434)
D
˚C
C
˚C
B
˚C
A
˚C
E
˚C
Содержание FTKM18PVMK
Страница 16: ...SiMT041509E 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 18: ...SiMT041509E 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 59: ...SiMT041509E Remote Controller 44 Part 5 Remote Controller 1 Remote Controller 45 ...
Страница 118: ...Revision History Month Year Version Revised contents 07 2015 SiMT041509E First edition ...