Trouble shooting
Si04-115
70
Service Diagnosis
5.5
Faulty Indoor Unit PCB
Remote
Controller
Display
∗
Indoor unit LED
Display
Method of
Malfunction
Detection
The proper program operation of the microcomputer is checked by the program.
Malfunction
Decision
Conditions
When the microcomputer program does not function properly.
Supposed
Causes
"
Microcomputer program is in abnormal condition due to an external factor.
∗
Noise.
∗
Momentary voltage drop.
∗
Momentary power failure, etc.
"
Faulty indoor unit PCB.
Troubleshooting
Turn on the power again.
Check the grounding. (earth)
NO
Replace the indoor unit PCB.
Provide proper grounding.
The malfunction may be
caused by an external factor,
rather than defective parts.
Locate the cause of the noise,
etc., and correct the situation.
Dose it reappear?
Is the grounding proper?
(R1948)
YES
YES
NO
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
Содержание FTK25JVE9
Страница 10: ...Si04 115 List of Function 1 Part 1 List of Function 1 Functions 2 1 1 Indoor Unit and Outdoor Unit 2...
Страница 50: ...Si04 115 System Configuration 41 Part 5 System Configuration 1 Instruction 42 1 1 FTK25 35J FTX25 35J 42...
Страница 69: ...Instruction Si04 115 60 System Configuration...
Страница 134: ...Si04 115 For RK25J RK35J RX25J RX35J Removal Procedure 125 2 Slide the MID upward and release Step Procedure Points...
Страница 136: ...Si04 115 For RK25J RK35J RX25J RX35J Removal Procedure 127 4 Remove the fan motor Step Procedure Points...
Страница 145: ...For RK25J RK35J RX25J RX35J Si04 115 136 Removal Procedure...
Страница 146: ...Si04 115 Others 137 Part 8 Others 1 Others 138 1 1 Explanation 138...