1. Others
1.1
Explanation
1.1.1
Test Run from the Remote Controller
(For Heat Pump Model Only)
Trial Operation and Testing
1. Measure the supply voltage and make sure that it falls in the specified range.
2. Trial operation should be carried out in either cooling or heating mode.
For Heat pump
In cooling mode, select the lowest programmable temperature; in heating mode, select the
highest programmable temperature.
"
Trial operation may be disabled in either mode depending on the room temperature.
"
After trial operation is complete, set the temperature to a normal level
(26°C to 28°C in cooling mode, 20°C to 24°C in heating mode).
"
For protection, the system disables restart operation for 3 minutes after it is turned off.
For Cooling
operation in case
of low ambient
temperature
Select the lowest programmable temperature.
"
Trial operation in cooling mode may be disabled depending on the room temperature.
Use the remote control for trial operation as described below.
Trial operation from Remote Controller
(1) Press ON/OFF button to turn on the system.
(2) Simultaneously press center of TEMP button and MODE buttons.
(3) Press MODE button twice.
(“
T
” will appear on the display to indicate that Trial Operation mode is selected.)
(4) Trial run mode terminates in approx. 15 minutes and switches into normal mode. To quit a
trial operation, press ON/OFF button.
"
After trial operation is complete, set the temperature to a normal level (26°C to 28°C).
"
For protection, the machine disables restart operation for 3 minutes after it is turned off.
3. Carry out the test operation in accordance with the Operation Manual to ensure that all
functions and parts, such as louver movement, are working properly.
"
The air conditioner requires a small amount of power in its standby mode. If the system is
not to be used for some time after installation, shut off the circuit breaker to eliminate
unnecessary power consumption.
"
If the circuit breaker trips to shut off the power to the air conditioner, the system will restore
the original operation mode when the circuit breaker is opened again.
G -SLEEP SENSOR
POWERFULL
TEMP
TIMER
ON
MODE
FAN
CANCEL
OFF
ON/OFF
SWING
(3)
(2)
(1) (4)
(3)
(RL033)
Содержание FTK25JVE9
Страница 10: ...Si04 115 List of Function 1 Part 1 List of Function 1 Functions 2 1 1 Indoor Unit and Outdoor Unit 2...
Страница 50: ...Si04 115 System Configuration 41 Part 5 System Configuration 1 Instruction 42 1 1 FTK25 35J FTX25 35J 42...
Страница 69: ...Instruction Si04 115 60 System Configuration...
Страница 134: ...Si04 115 For RK25J RK35J RX25J RX35J Removal Procedure 125 2 Slide the MID upward and release Step Procedure Points...
Страница 136: ...Si04 115 For RK25J RK35J RX25J RX35J Removal Procedure 127 4 Remove the fan motor Step Procedure Points...
Страница 145: ...For RK25J RK35J RX25J RX35J Si04 115 136 Removal Procedure...
Страница 146: ...Si04 115 Others 137 Part 8 Others 1 Others 138 1 1 Explanation 138...