Installation manual

9

FFQ25~60C2VEB

Split System air conditioners

4P341094-1B – 2013.04

Setting indoor unit number of simultaneous operation 
system

When using in simultaneous operation system mode, change the
Second code No. as shown in the table. (Second code No. is factory
set to "01" for 1 connected unit.)

When using in simultaneous operation system mode, refer to

"Simultaneous operation system individual setting" on page 9

 to set

master and slave units separately.

When using wireless remote controllers

When using wireless remote controllers, wireless remote controller
address setting is necessary. Refer to the installation manual
attached to the wireless remote controller for setting instructions.

Simultaneous operation system individual setting

It is easier if the optional remote controller is used when setting the
slave unit.

Perform the following procedures when setting the master and slave
unit separately.

Procedure 

(See figure 16)

1

Change the Second code No. to "02", individual setting, so that
the slave unit can be individually set. (Second code No. is
factory set to "01", unified setting.)

2

Perform field setting for the master unit.

3

Turn off the main power supply switch after (2).

4

Detach remote controller from the master unit and connect it to
the slave unit.

5

Turn on the main power supply switch again, and as in (1),
change the Second code No. to "02", individual setting.

6

Perform field setting for the slave unit.

7

Turn off the main power supply switch after (6).
In case there are 2 or more slave units, repeat steps (4) to (7) for
all slave units.

8

Detach the remote controller from the slave unit after the setting,
and reattach to the master unit. This is the end of the setting
procedure.

You do not need to rewire the remote controller from the master unit if
the optional remote controller for slave unit is used. (However,
remove the wires attached to the remote controller terminal board of
the master unit.)

Test operation

Refer to 

"For the following items, take special care during

construction and check after installation is finished" on page 2

.

After finishing the construction of refrigerant piping, drain piping, and
electric wiring, conduct test operation accordingly to protect the unit.

Test operation after installing decoration panel

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours.

4

Set to cooling operation with the remote controller and start
operation by pushing ON/OFF button.

5

Press Inspection/Test Operation button 

 4 times

(2 times for wireless remote controller) and operate at Test
Operation mode for 3 minutes.

6

Push air flow direction adjust button 

 to make sure

the unit is in operation.

7

Press Inspection/Test Operation button 

 and operate

normally.

8

Confirm function of unit according to the operation manual.

Test operation before installing decoration panel 

1

Open the gas side stop valve.

2

Open the liquid side stop valve.

3

Electrify crank case heater for 6 hours.

4

Set to cooling operation with the wired remote controller and
start operation by pushing ON/OFF button.

5

Press Inspection/Test Operation button 

 4 times and

operate at Test Operation mode for 3 minutes.

6

Press Inspection/Test Operation button 

 and operate

normally.

7

Confirm function of unit according to the operation manual.

8

Turn off the main power supply after operation.

Precautions

1

In case something is wrong with the unit and it does not operate,
refer to the installation manual attached to the outdoor unit or
contact your dealer.

2

Refer to the installation manual attached to the outdoor unit in
case of Individual Operation System type.

3

Conduct test operation after installing decoration panel if the
wireless remote controller is used.

Setting

Mode No.

First code 

No.

Second 

code No.

Pair system (1 unit)

11 (21)

0

01

Simultaneous operation 

system (2 unit)

02

Simultaneous operation 

system (3 unit)

03

Simultaneous operation 

system (4 unit)

04

1

Main power supply

2

Main switch

3

Fuse

4

Remote controller (optional accessories)

5

Indoor unit (Master)

6

Indoor unit (Slave)

Setting

Mode No.

First code No.

Second code 

No.

Unified setting

11 (21)

1

01

Individual setting

02

NOTE

Do not touch the drain pump, this may cause electrical
shock.

Содержание FFQ25C2VEB

Страница 1: ...INSTALLATION MANUAL FFQ25C2VEB FFQ35C2VEB FFQ50C2VEB FFQ60C2VEB Split System air conditioners...

Страница 2: ...4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 BYFQ60C BYFQ60B PP H2 PP PP PP BYFQ60C BYFQ60B PP H1 H2 PP 2 1 5 4 3 8 8 2 4 7 1 9 10 5 5 2 7 4 3 a 2 3 4 2 5 6 575 a 700 700 a 575 8 7 3 2 1 4 1 5 6 575 a 62...

Страница 3: ...y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pa...

Страница 4: ...t Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting th...

Страница 5: ...er it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher tha...

Страница 6: ...ing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult t...

Страница 7: ...ng exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Fina...

Страница 8: ...et on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the d...

Страница 9: ...the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit...

Страница 10: ...hen attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insulation material field supply thus...

Страница 11: ...de No First code No and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according t...

Страница 12: ...uction and check after installation is finished on page 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit...

Страница 13: ...uit board A5P Printed circuit board Wired remote controller R4T Thermistor air Connector for optional parts X24A Connector wiring remote controller X33A Connector adaptor for wiring X35A Connector pow...

Страница 14: ......

Страница 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Страница 16: ...4P341094 1B 2013 04 Copyright 2013 Daikin...

Отзывы: