FFQ25~60C2VEB
Split System air conditioners
4P341094-1B – 2013.04

Installation manual

8

Wiring example

For the wiring of outdoor units, refer to the installation manual
attached to the outdoor units.

Confirm the system type:

Pair type or multi system: 1 remote controller controls 1 indoor
unit (standard system).

Simultaneous operation system: 1 remote controller controls
2 indoor units (2 indoor units operate equally)

Group control: 1 remote controller controls up to 16 indoor units
(All indoor units operate according to the remote controller).

2 remote controller control: 2 remote controllers control 1 indoor
unit.

Pair type or multi system 

(See figure 12)

Simultaneous operation system 

(See figure 13)

Group control 

(See figure 14)

2 remote controller control 

(See figure 15)

Precautions

1

All transmission wiring except for the remote controller wiring is
polarized and must match the terminal symbol.

2

In case of group control, perform the remote controller wiring to
the master unit when connecting to the simultaneous operation
system (wiring to the slave unit is unnecessary).

3

For group control remote controller, choose the remote controller
that suits the indoor unit which has the most functions (as
attached swing flap).

4

When controlling the simultaneous operation system with
2 remote controllers, connect it to the master unit (wiring to the
slave unit is unnecessary).

5

Be sure to connect the wiring to the master unit when combining
with a simultaneous operating multi-type in group control.

6

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper ground-
ing could result in electric shock.

Installation of the decoration panel

Refer to the installation manual delivered with the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dew drop.

Field setting

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode No.", "First code
No." and "Second code No.".

For setting and operation, refer to "Field setting" in the
installation manual of the remote controller.

Setting ceiling height

Adjust the Second code No. according to the table below so that it
corresponds to the ceiling height of your installation. (Second code
No. is factory set to "01")

The figure of ceiling height is for air discharge in all directions.

Setting air discharge direction

For changing air discharge direction (3 or 4 directions), refer to the
option handbook of the optional blocking pad kit. (Second code No. is
factory set to "01" for all-round air discharge)

Setting air volume when thermostat control is OFF

Before setting thermostat control, consult with the customer
regarding whether that is responding to their environment.
(Second code No. is "02" at cooling thermostat OFF and others are
"01" as factory setting.)

Setting air filter sign

Remote controllers are equipped with liquid crystal air filter signs to
display the time to clean the air filter.

Change the Second code No. Depending on the amount of dirt or
dust in the room. (Second code No. is factory set to "01" for air filter
contamination-light)

Air filter contamination

When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.

1

Main power supply

2

Main switch

3

Fuse

4

Remote controller (optional accessories)

5

Indoor unit (Master)

6

Indoor unit (Slave)

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is auto-
matically set when the power is activated.

Ceiling height (m)

Mode No.

First code No.

Second code No.

2.7

N

13 (23)

0

01

>2.7 or 

3.0

H

13 (23)

0

02

>3.0 or 

3.5

S

13 (23)

0

03

Setting

Mode

(1)

 

No.

(1) Mode No. setting is done in a batch for the group. To make or confirm settings for 

an individual unit, set the Mode No. shown in parentheses

First 

code 

No.

Second 

code 

No.

Fan stops at thermostat 

OFF (cooling/heating)

Normal

11(21)

2

01

Stop

02

Air volume at cooling 

thermostat OFF

LL

12(22)

6

01

Setup volume

02

Air volume at heating 

thermostat OFF

LL

12(22)

3

01

Setup volume

02

Setting

Display 
interval

Mode No.

First code 

No.

Second 

code No.

Light

±2500 hrs

10 (20)

0

01

Heavy

±1250 hrs

10 (20)

0

02

No display

10 (20)

3

02

Содержание FFQ25C2VEB

Страница 1: ...INSTALLATION MANUAL FFQ25C2VEB FFQ35C2VEB FFQ50C2VEB FFQ60C2VEB Split System air conditioners...

Страница 2: ...4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 BYFQ60C BYFQ60B PP H2 PP PP PP BYFQ60C BYFQ60B PP H1 H2 PP 2 1 5 4 3 8 8 2 4 7 1 9 10 5 5 2 7 4 3 a 2 3 4 2 5 6 575 a 700 700 a 575 8 7 3 2 1 4 1 5 6 575 a 62...

Страница 3: ...y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pa...

Страница 4: ...t Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels When selecting th...

Страница 5: ...er it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher tha...

Страница 6: ...ing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult t...

Страница 7: ...ng exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Fina...

Страница 8: ...et on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the d...

Страница 9: ...the main power supply is turned off and then turned back on again Refer to the installation manual attached to the outdoor unit for the size of power supply electric wire connected to the outdoor unit...

Страница 10: ...hen attaching the control box lid make sure not to pinch any wires After all wiring connections are done fill in any gaps in the casing wiring holes with putty or insulation material field supply thus...

Страница 11: ...de No First code No and Second code No For setting and operation refer to Field setting in the installation manual of the remote controller Setting ceiling height Adjust the Second code No according t...

Страница 12: ...uction and check after installation is finished on page 2 After finishing the construction of refrigerant piping drain piping and electric wiring conduct test operation accordingly to protect the unit...

Страница 13: ...uit board A5P Printed circuit board Wired remote controller R4T Thermistor air Connector for optional parts X24A Connector wiring remote controller X33A Connector adaptor for wiring X35A Connector pow...

Страница 14: ......

Страница 15: ...3 4 P1 P2 1 2 3 1 2 3 1 2 3 4 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 1 2 3 4 4 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 1 2 3 1 2 3 1 2 3 5 6 1 2 3 1 2 1 2 3 1 2 3 1 2 3 5...

Страница 16: ...4P341094 1B 2013 04 Copyright 2013 Daikin...

Отзывы: