1.11 Presence and Floor Sensors (Option)
Outline
With the human presence signal and the floor temperature signal from the optional sensor kit, the
system provides the energy saving control, or the comfortable temperature control and airflow
direction control preventing the direct draft to the human.
To use sensor related functions, a wired remote controller (BRC1E73) and optional sensor kit
(BRYQ60A2W(S)) are necessary to be installed.
Details
1. Draft prevention (with presence sensor)
When the sensor detects human presence during auto-swing operation, the system sets the airflow
direction parallel to the floor (position 0) to reduce unpleasant draft.
The operation returns to the normal auto-swing as the sensor detects no human in the room.
Draft prevention is enabled only when decoration panel BYFQ60C2W1W(S), sensor kit
BRYQ60A2W(S) and wired remote controller BRC1E73 are connected to the main unit and
draft prevention is set to “enabled” on the wired remote controller.
Factory setting is “disabled”.
Draft prevention cannot be activated when individual flap control is set, even if draft prevention
is enabled on the wired remote controller.
Setting on the wired remote controller
1
Setting
Main Menu
Configuration
Current Settings
Clock & Calendar
2/3
2
Draft Prevention
Configuration
Setting
3
Enable
Draft Prevention
Enable/Disable
Setting
4
No
Yes
Draft Prevention
Save the settings?
Setting
Press
Menu/OK
button to display the
main menu screen.
Press buttons to select
Yes
.
The confirmation screen will appear
when
Menu/OK
button is pressed.
Press
Menu/OK
button to confirm the
settings and to return to the basic
screen.
Language
Contrast Adjustment
Display
Press buttons to select
Configuration
and press
Menu/OK
button.
Press buttons to select
Draft Prevention
and press
Menu/OK
button.
Press buttons to select
Enable
.
Содержание FFQ09Q2VJUFFQ12Q2VJUFFQ15Q2VJUFFQ18Q2VJURX09QMVJURX12QMVJURX15QMVJURX18QMVJU
Страница 12: ...SiUS091628EA 1 List of Functions Part 1 List of Functions 1 Functions 2...
Страница 14: ...SiUS091628EA 3 Specifications Part 2 Specifications 1 Specifications 4...
Страница 120: ...Check SiUS091628EA 109 Service Diagnosis 15 18 class R20701 1 2 3 4 Multimeter...
Страница 122: ...Check SiUS091628EA 111 Service Diagnosis 15 18 class R20704 W V U DC_P1 DC_N1...