8.15 Power Cable Connection:

Air-conditioning unit with single-phase power supply

1. 

Remove the front panel of the outdoor unit.

(1) 

Attach rubber ring to the cable-cross hole of the outdoor unit.

(2) 

Pass the cable though rubber ring.

(3) 

Connect the power supply cable to the “L, N” terminals and the grounding screw on the metal electric 

(4) 

box.
Use cable fastener to bundle and fi x the cable.

(5) 

2.  Air-conditioning unit with 3-phase power supply

Remove the front panel of the outdoor unit.

(1) 

Attach rubber ring to the cable-cross hole of the 

(2) 

outdoor unit.
Pass the cable though rubber ring.

(3) 

Connect the power cable to the terminal and 

(4) 

earthing screws marked “L1, L2, L3 & N”. Connect 
the earth wire to the earthed terminal screw on the 
electric box.
Use cable fastener to bundle and fi x the cable.

(5) 

8.16 Cable Connecting Diagram

The section area of cables selected by users must not be smaller than the specifi cations shown in the 

1. 

diagram. The signal wire between indoor and outdoor unit shall be installed in the shielded bushing, and 
the unshielded twisted pair cable (UTP) shall be used, the cross sectional area of the cables must be 
0.75mm².

Schematic Diagram of Unit Line Connection:

FDMR24PEV1K
FDYMRY24PEV1K
FDM R30PEV1K
FDYMRY30PEV1K

Outdoor Unit

Power: 220-240V~50Hz

Power: 220-240V~50Hz

L

(1)

(2)

(3)

N

L N 1

1
2

1
2

2 3

L N

breaker

breaker

PE

L N PE

Indoor Unit

(1) Power cord 3×4mm² (H07RN-F)

(2) Power cord 3×1.0 mm² (H05VV-F)

(3) Communication cords 2×0.75mm² (H05RN-F)

 CAUTION

Take great care when carrying out the following 
connections, so as to avoid malfunction of the 
air-conditioning unit because of electromagnetic 
interference. 

The signal line of the wired controller must 

(1) 

be separated from the power line and the 
connecting line between the indoor unit and 
the outdoor unit.
In case the unit is installed in a place 

(2) 

vulnerable by electromagnetic interference, 
it is better to use shielded cable or double-
twisted cable as the signal line of the wired 
controller.

01_EN_EM09A058A.indd   36

01_EN_EM09A058A.indd   36

5/13/2010   11:43:39 AM

5/13/2010   11:43:39 AM

Содержание FDYM-PV1

Страница 1: ...nit FDM24PEV1K FDM30PEV1K FDM36PEV1K FDM42PEV1K FDM48PEV1K FDYM24PEV1K FDYM30PEV1K FDYM36PEV1K FDYM42PEV1K FDYM48PEV1K Outdoor unit R24PEV1K R30PEV1K R36PEY1K R42PEY1K R48PEY1K RY24PEV1K RY30PEV1K RY3...

Страница 2: ...cation of wired controller once the unit is installed in the place where there is electromagnetic interference Make sure communication line is connected into correct port to avoid communication malfun...

Страница 3: ...of delivery of the condensate drainage pump 24 VIII INSTALLATION INSTRUCTIONS 25 8 1 Dimensions of Indoor Unit 25 8 2 Dimensions of Outdoor Unit 27 8 3 Precautions on Installation of Outdoor Unit 27 8...

Страница 4: ...local dealer about installation work Doing the work yourself may result in water leakage electric shocks or fire hazards Consult our local dealer regarding modification repair and maintenance of the a...

Страница 5: ...oner in accordance with the instructions in this installation manual Improper installation may result in water leakage electric shocks or fire Be sure to use only the specified accessories and parts f...

Страница 6: ...is a danger of flammable gas leakage In the event of a gas leakage build up of gas near the air conditioner may result in fire hazards Do not put flammable containers such as spray cans within 1m from...

Страница 7: ...pected in rooms with electronic fluorescent lamps inverter or rapid start types Install the indoor unit as far away from fluorescent lamps as possible Do not install the air conditioner in the followi...

Страница 8: ...lish DISPLAYING PART II 2 1 Outline of wired controller Fig 2 1 LCD Display of Wired Controller 2 2 LCD display Fig 01_EN_EM09A058A indd 6 01_EN_EM09A058A indd 6 5 13 2010 11 43 12 AM 5 13 2010 11 43...

Страница 9: ...monitoring 13 Turbo Turbo function state 14 Memory Memory state Indoor unit resumes original setting state after power failure and then power recovery 15 Twinkle Flicking when unit is on without oper...

Страница 10: ...turbo save E heater blow quiet 7 Timer Timer setting 8 On off Turn on off indoor unit 4 Mode and 2 Memory function Press Mode and for 5s under off state of the unit to enter cancel key memory functio...

Страница 11: ...hole with screws M4X25 3 Insert the 4 core twisted pair into controller s slot through rectangle hole and buckle the front panel and 4 soleplate of controller together At last fix the controller s fr...

Страница 12: ...energization The state shown in Fig 5 2 Note indicates on state of the unit after energization 5 1 Off state of the unit Fig 5 2 On state of the unit Fig 5 2 Mode Setting Under on state of the unit p...

Страница 13: ...sed by 1 C every 0 5s In Cooling Dry Fan and Heating mode temperature setting range is 16 30 C In Auto mode the setting temperature is un adjustable As shown in Fig 5 3 5 3 Fig 5 4 Fan Speed Setting P...

Страница 14: ...timer on and then press Timer to confirm If Mode button is pressed before pressing Timer button to confirm timer mode will be switched to timer off setting mode In this case LCD displays xx Hour OFF b...

Страница 15: ...utton will make setting time increased or decreased by 0 5hr If press either of them continuously setting time will automatically increase decrease by 0 5hr every 0 5s Note If both timer on and timer...

Страница 16: ...nit continuously runs for 60min and fresh air valve opens for 42 min 8 The unit continuously runs for 60min and fresh air valve opens for 48 min 9 The unit continuously runs for 60min and fresh air va...

Страница 17: ...button into sleep function Turn on the unit without turning on sleep function 5 8 Sleep setting Fig Sleep setting is cleared after power failure and then power recovery There is no sleep function in f...

Страница 18: ...displayed Turbo function will be automatically canceled after setting of quiet function 2 5 10 Save Function Setting Energy Saving Function Energy saving result that the air conditioner runs in smalle...

Страница 19: ...ning mode with save function on the unit will forcibly quit auto running mode and change to 1 current operation mode After setting of SAVE sleep function will be canceled In save mode if 2 Function bu...

Страница 20: ...to confirm or press Enter Cancel button to cancel In this case E HEATER won t be displayed which means E heater is prohibited to be turned on The setting of this function is shown as Fig 5 11 below P...

Страница 21: ...g is shown in Fig 5 12 Press Function button into blow function Press Enter Cancel button to turn on blow function Press Enter Cancel button to turn off blow function Press Function button into blow f...

Страница 22: ...an speed is un adjustable 1 When turning on auto quiet function the unit will enter quiet running state according to temperature 2 difference between room temperature and setting temperature In this c...

Страница 23: ...buttons at the same time for 5s till the wired controller enters lock state In this case LCD displays After that repress these two buttons at the same time for 5s to quit lock state Under lock state...

Страница 24: ...er unit on Error code meaning Error code Malfunction E1 High pressure protection of compressor E2 Indoor anti freezing protection E3 Low pressure protection of compressor E4 High discharge temperature...

Страница 25: ...room sensors on the basis of the engineering requirement Refer to the section of wired controller instructions for detailed operation Indoor Room Sensor A Indoor Room Sensor B 7 1 Fig 7 2 Checking of...

Страница 26: ...wired controller instructions for detailed operation Outdoor Fresh Air Indoor Side Air Damper Fresh Air Air Intake Pipe Air Supply Pipe Before starting up the unit please remove all the sealing film o...

Страница 27: ...6PEV1K FDM42PEV1K FDYM42PEV1K FDM48PEV1K FDYM48PEV1K Unit mm Item Model A B C D E F G H I J Connecting Pipe Liquid Pipe Connecting Pipe Gas Pipe Drainage Pipe Outer Diameter Wall Thickness FDM24PEV1K...

Страница 28: ...asher 250 250 8 2 Fig For FDM24PEV1K FDYM24PEV1K FDM30PEV1K FDYM30PEV1K FDM36PEV1K FDYM36PEV1K FDM42PEV1K FDYM42PEV1K FDM48PEV1K FDYM48PEV1K WARNING The height of installation for the indoor unit shou...

Страница 29: ...nit will not return and that sufficient 1 space for repair shall be provided around the machine The installation site must have good ventilation so that the outdoor unit can take in and exhaust enough...

Страница 30: ...r smoke 5 The indoor unit is of ceiling mount indoor unit is hidden inside the ceiling 6 The indoor and outdoor units the power cable and the connecting electrical lines must be at least 1 meter 7 fro...

Страница 31: ...s required to check the level of the whole unit The unit must be placed horizontally but the condensate pipe shall be installed obliquely so as to facilitate the drainage of condensate Air Supply B Ai...

Страница 32: ...t both the left and right sides of the indoor unit After selecting one drainage 2 outlet the other outlet shall be blocked by rubber plug Bundle the blocked outlet with string to avoid leakage and als...

Страница 33: ...than 5m it is required to add refriger ant In the above table the amounts of refrigerant to be added for the models are listed for each addi tional meter of pipe length The pipe thickness shall be 0 5...

Страница 34: ...is discharged for 15 seconds Then close the one way valve 7 immediately and tighten the bonnet Fully open the spools of the liquid valve and the gas valve refer to Fig 8 12 8 Tighten the valve cover T...

Страница 35: ...rial to block the hole in 2 the wall so as to prevent rain and wind from entering the room 8 12 Position and Method of Installing Wired Controller One end of the controlling wire of the wired controll...

Страница 36: ...te of Wired Controller Screw M4X10 Front panel of Wired Controller 8 13 Connection of Signal Line of Wired Controller Open the cover of the electric box of the indoor unit 1 Pull the signal cable of t...

Страница 37: ...ers to connect a terminal matching the size of the screw at the end of the multiple 3 twisted wires Put the screw through the terminal of the multiple twisted wires and fix the terminal at the termina...

Страница 38: ...e signal wire between indoor and outdoor unit shall be installed in the shielded bushing and the unshielded twisted pair cable UTP shall be used the cross sectional area of the cables must be 0 75mm S...

Страница 39: ...t Power 380 415V 3N 50Hz Power 220 240V 50Hz L1 1 2 3 L2 L3 N L N 1 1 2 1 2 2 3 L1 L2 breaker breaker L3 N PE L N PE Indoor Unit 1 Power cord 5 4mm H07RN F 2 Power cord 3 1 5mm H05VV F 3 Communication...

Страница 40: ...Y1K 380 415 3 50 25 4 0 4 0 RY48PEY1K R48PEY1K 380 415 3 50 25 4 0 4 0 Indoor Unit Duct Type Model Power Supply V Ph Hz Capability of Air Switch Minimum Sectional Area of Earth Wire Minimum Sectional...

Страница 41: ...ntrol line is abnormal 6 The indoor fan does not start under the heating mode The installation site of the tube sensor is not proper 1 Tube sensor is not correctly plugged 2 The connecting line of the...

Страница 42: ...upport the weight of air conditioner unit If not the air condi tioner unit might fall down and cause human injury or death To ensure proper drainage the drainage pipe shall be correctly installed acco...

Страница 43: ...static pressure The parameters are subject to change with the improvement of products in which case the values on nameplate shall prevail WARNING This appliance is not intended for use by persons incl...

Страница 44: ...DYM36PEV1K FDYM42PEV1K FDYM48PEV1K OUTDOOR UNIT RY24PEV1K RY30PEV1K RY36PEY1K RY42PEY1K RY48PEY1K RATED VOLTAGE V 220 240 220 240 380 415 380 415 380 415 RATED FREQUENCY Hz 50 50 50 50 50 COOLING T1 R...

Страница 45: ...66129904511 EM09A058A 1002 HT 00_CV_EM09A058A indd 4 00_CV_EM09A058A indd 4 5 15 2010 9 14 49 AM 5 15 2010 9 14 49 AM...

Отзывы: