SiUS071735EA
Control Specification
Functions and Control
34
2.4
Discharge Pipe Temperature Control
Outline
The discharge pipe temperature is used as the internal temperature of the compressor. If the
discharge pipe temperature rises above a certain level, the upper limit of frequency is set to keep
the discharge pipe temperature from rising further.
Details
09/12 class
15/18/24 class
(°C)
(°F)
(°C)
(°F)
A
110
230.0 110
230.0
B
103
217.4 103
217.4
C
98
208.4 101.5
214.7
D
93
199.4 100
212.0
E
88
190.4 95
203.0
Zone
Control
Stop zone
When the temperature reaches the stop zone, the compressor stops.
Dropping zone
The upper limit of frequency decreases.
Keep zone
The upper limit of frequency is kept.
Up zone
The upper limit of frequency increases.
Reset zone
The upper limit of frequency is canceled.
(R25005)
Discharge pipe
temperature
Stop zone
Dropping zone
Keep zone
Up zone
Reset zone
E
A
B
C
D
Содержание FDMQ09RVJU
Страница 12: ...SiUS071735EA 1 List of Functions Part 1 List of Functions 1 Functions 2 ...
Страница 14: ...SiUS071735EA 3 Specifications Part 2 Specifications 1 Specifications 4 ...
Страница 120: ...Check SiUS071735EA 109 Service Diagnosis 15 18 24 class R25105 1 2 3 4 Multimeter ...
Страница 122: ...Check SiUS071735EA 111 Service Diagnosis 15 18 24 class R20704 W V U DC_P1 DC_N1 ...
Страница 138: ...Piping Diagrams SiUS071735EA 127 Appendix 1 Piping Diagrams 1 1 Indoor Unit FDMQ09 12 15 18 24RVJU C 4D112974A ...
Страница 140: ...Piping Diagrams SiUS071735EA 129 Appendix RX24RMVJU A 3D092249A ...