SiUS071735EA
Field Settings
Trial Operation and Field Settings
120
Wireless Remote
Controller
(BRC082A43)
To set the field settings, you have to change:
Mode No.
First code No.
Second code No.
1. When in normal mode, hold down
/TEST button for at least 4 seconds to enter the Field Set
mode.
2. Select the desired Mode No. with
MODE
button.
3. Press
button and select the First code No.
4. Press
button and select the Second code No.
5. Press
RESERVE
button to confirm the settings.
6. Press
/TEST button to quit the Field Set mode and to return to normal display again.
RESERVE
button
Mode No.
Field setting mode
UP
button
DOWN
button
First code No.
Second code No.
MODE
button
(R25096)
INSPECTION/TEST
button