2 About the box
Installation and operation manual
4
FCAHG71~140FVEB
Split system air conditioners
4P429472-1 – 2015.12
▪
Wiring instruction sheet
▪ Instructions on how to connect the optional sensor kit and
decoration panels
▪ Format: Paper (in the box of the indoor unit)
Latest revisions of the supplied documentation may be available on
the regional Daikin website or via your dealer.
The original documentation is written in English. All other languages
are translations.
For the installer
2
About the box
2.1
Indoor unit
2.1.1
To remove the accessories from the
indoor unit
8×
4×
1×
1×
1×
a
4×
1×
1×
1×
1×
7×
1×
e
f
d
c
b
h
j
i
g
1×
k
1×
l
m
o
n
a
Paper pattern for installation (upper part of packing)
b
General safety precautions
c
Indoor unit installation and operation manual
d
Installation guide
e
Washers for hanger brackets
f
Screws (to temporarily attach the paper pattern for
installation to the indoor unit)
g
Cable ties
h
Metal clamp
i
Insulation piece (drain pipe)
j
Sealing pads: Large (drain pipe), medium 1 (gas pipe),
medium 2 (liquid pipe), small (electrical wiring)
k
Drain hose
l
Insulation piece: Small (liquid pipe)
m
Insulation piece: Large (gas pipe)
n
Wiring instruction sheet (for the connection of the optional
sensor kit and decoration panels)
o
Wire harness for the self‑cleaning decoration panel
3
About the units and options
3.1
About the indoor unit
Use the system in the following temperature and humidity ranges for
safe and effective operation.
Cooling
Heating
Outdoor
temperature
–15~50°C DB
–19~21°C DB
–20~15.5°C WB
Indoor
temperature
18~35°C DB
12~28°C WB
10~27°C DB
Indoor humidity
≤80%
(a)
(a)
To avoid condensation and water dripping out of the unit. If
the temperature or the humidity is beyond these conditions,
safety devices may be put in action and the air conditioner
may not operate.
3.2
System layout
NOTICE
Design of the system must not be done at temperatures
below –15°C.
f g
b
h
i
a
d
e
c
a
Indoor unit
b
Outdoor unit
c
User interface
d
Suction air
e
Discharge air
f
Refrigerant interconnection cable
g
Drain pipe
h
Earth wiring
i
Suction grille and air filter
4
Preparation
4.1
Preparing installation site
4.1.1
Installation site requirements of the
indoor unit
INFORMATION
The sound pressure level is less than 70 dBA.
CAUTION
Appliance not accessible to the general public, install it in a
secured area, protected from easy access.
This unit, both indoor and outdoor, is suitable for
installation
in
a
commercial
and
light
industrial
environment.
▪
Spacing
. Mind the following requirements:
Содержание FCAHG71FVEB