Burner Operates; However . . . (continued)
4 .5 At the instant spark comes on, the
flame safeguard drops out and
restarts the pre-purge cycle .
a . Check
. The LED code may diagnose the problem .
b . Ignition interference . Flame rod or its wire is sensing voltage from ignition . Also
determine that ignition electrode spark gap is within specifications.
4.6 When the flame safeguard is
powered it locks out and the
ALARM LED comes ON .
a . Check
. The LED code may diagnose the problem .
b . Purge card missing or bad, terminals are energized that should not be at that
stage, or there is an internal system fault . Replace purge card or RM7897A as
indicated .
Troubleshooting
www .DaikinApplied .com 29
IM 684-6 • ROOFTOP SYSTEMS