Modulating Gas Burner without End Switch Cycling
Similar to the sequence of operation described previously
except at any time the burner is operating, the modulating
controllers will determine the firing rate. The modulating
controls position an operator which will change both gas and
airflow proportionally. The modulating control will always go to
the low fire position for light OFF.
Figure 10: Typical Electrical Schematic with no MicroTech III Control System
IM 684-6 • ROOFTOP SYSTEMS 14 www .DaikinApplied .com
Start-Up and Operating Procedures