Combination Fan and Limit Control
The fan limit control is a hydraulic action type with a remote
sensing element and connecting capillary tube . The sensing
element is locked into a bracket located on one of the heat
exchanger tubes about halfway toward the back of the furnace,
on the side away from the blower . One corner of the bracket is
bent aside to remove the element .
Normal setting of the FAN control: Fan ON=125°F, Fan
OFF=100°F .
The LIMIT control must never be set higher than the
temperature listed below. If the burner is shutting off on high
limit at these settings, it indicates that there is a problem with
the furnace not getting enough air or it is being overfired.
Table 5:
Limit Control Set Points
BURNER
MODEL
LIMIT
CONTROL
SET POINT
BURNER
MODEL
LIMIT
CONTROL
SET POINT
020
215
079
181
025
160
080
229
032
196
100
170
040
154
110
222
050
229
140
168
064
185
150
194
065
232
200
151
Replacing “White Rogers” Fan
Limit Controller with “Antunes”
Wire 24 VAC input power to terminals T2 and T3 . Wire
temperature sensor from the secondary tubes at the heat
exchanger to terminals T7 and T8 . Connect N .C and COM
wires for internal fan and high limit relays
Figure 19: Antunes
®
Fan Limit Controller
IM 684-6 • ROOFTOP SYSTEMS 22 www .DaikinApplied .com