20
English
10-1 AIRFLOW SETTINGS WHEN THERMOSTAT IS OFF
•
Set the flow rate according to the requirement of the environment after consultation with the customer.
(As the factory setting, airflow for when cooler thermostat is off is set to SECOND CODE NO. “02”, while
other settings are set to “01”.)
(Refer to Table 6)
Table 6
are the settings when shipped from the factory.
10-2 SETTING AIR FILTER SIGN
•
Remote controllers are equipped with liquid crystal display air filer signs to display the time to clean air fil-
ters.
•
Change the SECOND CODE NO. according to Table 7 depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for air filter contamination-light.)
Explain to the customer that filters need to be cleaned periodically to prevent clogging, and the time that is
set.
•
The periodical cleaning time for the filter can be shortened depending on the usage environment.
Table 7
10-3 SETTING AIR FLOW RATE INCREASE MODE
•
The set airflow rate (HH, H, and L) can be increased depending on the installation condition or customer’s
request. In such a case, switch the SECOND CODE NO. as shown in Table 8.
(SECOND CODE NO. is factory set to “01” for standard.)
Table 8
Setting
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Fan operation when thermo-
stat is OFF (Cooling/Heating)
Normal
11 (21)
2
01
Stop
02
Airflow rate when cooler ther-
mostat is OFF
LL airflow rate
12 (22)
6
01
Setting airflow rate
02
Airflow rate when heater
thermostat is OFF
LL airflow rate
12 (22)
3
01
Setting airflow rate
02
Setting
Spacing time of display air
filter sigh
Mode No.
FIRST
CODE NO.
SECOND
CODE NO.
Air filter
contamination-light
Approx. 200 hrs.
10 (20)
0
01
Air filter
contamination-heavy
Approx. 100 hrs.
02
Setting
Mode No.
FIRST CODE NO.
SECOND CODE NO.
Standard
13(23)
0
01
Slightly increase
02
Increase
03