21
|
Configuration
Installer and user reference guide
77
FAA71+100BUV1B
Split system air conditioner
4P654517-1 – 2021.03
If you want…
Then
(1)
M
SW
—
During thermostat
OFF at cooling
operation
LL
(2)
12 (22)
6
01
Setup volume
(2)
02
OFF
03
Monitoring 1
(2)
04
Monitoring 3
(2)
05
During thermostat
OFF at heating
operation
LL
(2)
12 (22)
3
01
Setup volume
(2)
02
OFF
03
Monitoring 1
(2)
04
Monitoring 2
(2)
05
Setting: Time to clean air filter
This setting must correspond with the air contamination in the room. It determines
the interval at which
"Time to clean filter"
notification is displayed on the user
interface.
If you want an interval of…
(air contamination)
Then
(1)
M
SW
—
±200 h (light)
10 (20)
0
01
±100 h (heavy)
02
Setting: Indoor unit number of simultaneous operation system
For simultaneous operation system mode made following field setting:
If the system mode is…
Then
(1)
M
SW
—
Pair (1 unit)
11 (21)
0
01
Simultaneous (2 units)
02
Simultaneous (3 units)
03
When using in
simultaneous operation
system mode, refer to “simultaneous
operation system individual setting” section to set master and slave units
separately.
When using
wireless remote controllers,
wireless remote controller address
setting is necessary. Refer to the installation manual attached to the wireless
remote controller for setting instructions.
(1)
Field settings are defined as follows:
•
M
: Mode number –
First number
: for group of units –
Number between brackets
: for individual unit
•
SW
: Setting number
•
—: Value number
•
: Default
(2)
Fan speed:
•
LL
: Low fan speed (set during thermostat OFF)
•
L
: Low fan speed (set by the user interface)
•
Setup volume
: The fan speed corresponds to the speed the user has set using the fan speed button on the user interface.
•
Monitoring 1, 2, 3
: The fan is OFF, but runs for a short time every 6 minutes to detect the room temperature by
LL
(Monitoring 1),
L
(Monitoring 2) or
Setup volume
(Monitoring 3).