8 Maintenance and service
Operation manual
22
EZESHP20 EZLSHP20AUAW1B
Exigo E1500 Trailer Refrigeration Unit
4P726855-1 – 2023.03
DANGER: RISK OF EXPLOSION
Always disconnect the negative battery terminal first when
removing battery cables. When reconnecting the battery
terminals, connect the positive terminal (+) first.
The order in which to remove the battery terminals is important.
The frame is connected to the negative battery terminal (grounded).
This means that with the negative terminal connected, a complete
circuit exists from the positive terminal of the battery to the frame.
Contacting the positive side and the frame simultaneously with a
metal object will cause sparks or arcing, creating a fire hazard. Also,
by this short-circuiting of the battery, hydrogen gases can be
emitted, and an explosion might occur.
2
Disconnect the negative (–) battery terminal.
3
Disconnect the positive (+) battery terminal.
8.4
After a long stop period
If the battery is still connected
1
If applicable, disconnect the automatic battery charger.
2
Turn the ON/OFF switch (a) ON.
a
If the battery is NOT connected
DANGER: RISK OF EXPLOSION
Always disconnect the negative battery terminal first when
removing battery cables. When reconnecting the battery
terminals, connect the positive terminal (+) first.
1
Connect the positive (+) battery terminal.
2
Connect the negative (–) battery terminal.
3
Turn the ON/OFF switch ON.
8.5
To jump-start the unit
WARNING
Acid fumes and explosive hydrogen may be released
during battery charging. No open flame or smoking near
the battery.
When the battery is dead or does not provide sufficient voltage it is
possible to jumpstart the diesel engine.
Have the battery changed as soon as possible by a qualified service
person.
b
a
a
Positive (+) battery terminal of the unit
b
Negative (–) terminal of the unit
1
Remove the positive (+) pole protection cap.
2
Connect the clamp of the red jumper cable to the positive (+)
battery terminal of the unit (a).
3
Connect the other clamp of the red jumper cable to the positive
(+) battery terminal of the back-up battery (e.g. the battery of a
truck).
4
Connect the clamp of the black jumper cable to the negative (–)
battery terminal of the back-up battery.
5
Connect the other clamp of the black jumper cable to the
negative (–) terminal of the unit (b).
6
Start the unit.
7
Disconnect the clamp of the black jumper cable from the
negative (–) terminal of the unit (b).
8
Disconnect the clamp of the red jumper cable from the positive
(+) battery terminal of the unit (a).
9
Disconnect the clamp of the red jumper cable from the positive
(+) battery terminal of the back-up battery.
10
Disconnect the clamp of the black jumper cable from the
negative (–) battery terminal of the back-up battery.
11
Reinstall the positive (+) pole protection cap.
8.6
Scheduled maintenance
NOTICE
To ensure correct operation of the unit, keep the diesel
tank clean, use quality diesel fuel and respect the
maintenance schedule.
An alarm is triggered when the maintenance hour meter timer has
expired to warn the user that scheduled maintenance is required.