background image

EWYQ080~250DAYN
Packaged air-cooled water chillers
4PW35559-1D – 03.2011

Installation manual

13

Example 2: Single ring system with separate pumps

Figure 2

 shows the system configuration, field wiring and terminals

for field wiring of this example.

Purpose

Purpose of this system is to deliver a constant water flow at a
constant temperature to a particular load. One unit, slave 3 (S3), is
kept as a standby unit.

Setup

The system is controlled on entering water temperature.

Pump 1, pump 2 and pump 3 keep running as long as the
master unit, slave 1 or slave 2 are ON. Pump 4 only starts
running if slave 3 is switched ON. After switching OFF the units,
the pumps run for a time indicated by the 

PUMPLAG

 setting.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S1S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S1S (M) which is
connected to the master unit.

The setpoint can be switched from 

INLETSETP1

 to

INLETSETP2

 using the dual setpoint selection switch S2S

which is connected to the master unit.

Parameter settings of the units

Usersettings menu, submenu 

DICN

Changeable inputs/outputs must be defined as follows:

Service setting menu, submenu 

INPUT OUTPUT

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

STANDBY

. In

this case, S1S (S3) has no function.

Example 3: Double ring system with several pumps

Figure 3

 shows the system configuration, field wiring and terminals

for field wiring of this example.

Purpose

Purpose of this system is to keep a buffer at a constant temperature
and to feed a load from this buffer. One unit, slave 3 (S3), is kept as a
standby unit.

Setup

The system is controlled on entering water temperature.

The pumps of the slave units only run when their compressor is
running (energy saving). After stopping the compressor, the
pump runs for a time indicated by the 

PUMPLAG

 setting.

The pump of the master unit must run continuously so as to
sense the correct temperature.

Slave 3 (S3) is configured to operate when its remote start/stop
switch S1S (S3) is pushed by the operator.

Slave 1 (S1), slave 2 (S2) and the master unit (M) are switched
ON or OFF using the remote start/stop switch S1S (M) which is
connected to the master unit.

The setpoint can be switched from 

INLETSETP1

 to

INLETSETP2

 using the dual setpoint selection switch S2S

which is connected to the master unit.

Parameter settings of the units

Usersettings menu, submenu 

DICN

:

Changeable inputs/outputs must be defined as follows:

Service setting menu, submenu 

INPUT OUTPUT

Remark

Slave 3 can be configured to start up automatically if:

1 of the other units is in alarm or;

all other units are running on full capacity and the setpoint is not
reached yet.

To have your slave 3 unit act this way, set its mode to 

STANDBY

. In

this case, S1S (S3) has no function.

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

Slave 3

Slave 2

Slave 1

Master

MODE

:

DISCONNECT

ON/OFF

NORMAL

NORMAL

NORMAL

PUMP ON IF:

UNIT ON

UNIT ON

UNIT ON

UNIT ON

Slave 3

Slave 2

Slave 1

Master

Terminal 46-47 

S2S 

DI1

NONE

NONE

NONE

DUAL 

SETPOINT

Terminal 48-49 

S1S 

DI2

REMOTE

ON/OFF

NONE

NONE

REMOTE

ON/OFF

Terminal 50-51 

DI3

NONE

NONE

NONE

NONE

Terminal 52-53 

DI4

NONE

NONE

NONE

NONE

NOTE

K*P can also be a 24 V DC or 230 V AC contactor.

Slave 3

Slave 2

Slave 1

Master

MODE

:

DISCONNECT

ON/OFF

NORMAL

NORMAL

NORMAL

PUMP ON IF:

COMPR ON

COMPR ON COMPR ON COMPR ON

Slave 3

Slave 2

Slave 1

Master

Terminal 46-47 

S2S 

DI1

NONE

NONE

NONE

DUAL 

SETPOINT

Terminal 48-49 

S1S 

DI2

REMOTE 

ON/OFF

NONE

NONE

REMOTE

ON/OFF

Terminal 50-51 

DI3

NONE

NONE

NONE

NONE

Terminal 52-53 

DI4

NONE

NONE

NONE

NONE

Содержание EWYQ080DAYN

Страница 1: ...INSTALLATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Страница 2: ...4P F13 230V 24V K4P M4P L2 L3 SLAVE 3 SLAVE 3 F14 F2 F3 N L1 F4 F15 230V 24V K3P M3P L2 L3 SLAVE 2 F16 F5 F6 N L1 F7 F17 230V 24V K2P M2P L2 L3 SLAVE 1 F18 F8 F9 N L1 F10 F19 230V 24V K1P M1P L2 L3 MA...

Страница 3: ...ate cu Certificatul C conform celor stabilite n Dosarul tehnic de construc ie D i apreciate pozitiv de E Modul aplicat F n conformitate cu Certificatul G Categorie de risc H Consulta i de asemenea pag...

Страница 4: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin M...

Страница 5: ...OP03 Condenser protection grills OPCG Inverter fans OPIF Low noise operation OPLN OPIF compressor housing Single pump OPSP High static pump OPHP Twin pump OPTP Heater tape s OP10 Glycol application f...

Страница 6: ...either the discharged air nor the sound generated by the unit disturb anyone 7 Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction Frontal wind will...

Страница 7: ...indicated The concrete foundation should approximately be 100 mm higher than the oor level for ease of plumbing work and better drain Make sure that the foundation surface is even and at 4 Remove the...

Страница 8: ...ystem and the water ow through the evaporator must be within the operation range as speci ed in the table Cooling mode Heating mode Only for models with option OPSP OPTP or OPHP Maximum allowed instal...

Страница 9: ...detectable corrosion Ammonium ion mg NH4 l 1 0 0 1 corrosion Remaining chloride mg Cl l 0 3 0 3 corrosion Free carbide mg CO2 l 4 0 4 0 corrosion Stability index corrosion scale The chillers are only...

Страница 10: ...PTC K1S Overcurrent relay pump not for options OPSC OPTC OPSP OPTP and OPHP K2P Pump contactor only for options OPTP and OPTC M1P Pump motor 1 only for options OPSC OPTC OPSP OPTP and OPHP M2P Pump mo...

Страница 11: ...ting of the eld wiring must be as indicated in the gures below In the cover plate some free space is provided to install the appropriate nipples drilling through the cover plate is required for single...

Страница 12: ...of the cable 0 75 mm2 4 wire and maximum 500 m long Setting the addresses on the remote digital controller When a remote digital controller is used the address has to be set by means of DIP switches...

Страница 13: ...ng The electrical main power supply must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipment in general Refer to the wirin...

Страница 14: ...it safety is active WARNING indicates that a warning is active C1 C2 OPERATION indicates that a compressor of that circuit is switched on 0 CAPACITY indicates that no compressors are switched on COOLI...

Страница 15: ...cannot modify them De ning the thermostat settings For a stand alone unit Enter the rst screen of the THERMOSTAT submenu through the service menu De ning the thermostat settings for inlet or outlet wa...

Страница 16: ...S1S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master unit M are switched ON or OFF using the remote start stop switch S1S M which is connected to the master unit The setpoint can be...

Страница 17: ...t slave 3 S3 is kept as a standby unit Setup The system is controlled on entering water temperature The pumps of the slave units only run when their compressor is running energy saving After stopping...

Страница 18: ...Installation manual 14 EWYQ080 250DAYN Packaged air cooled water chillers 4PW35559 1D 03 2011 NOTES...

Страница 19: ...r circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerge...

Страница 20: ...4PW35559 1D 03 2011 Copyright 2007 Daikin...

Отзывы: