background image

Installation manual

10

EWYQ080~250DAYN

Packaged air-cooled water chillers

4PW35559-1D – 03.2011

Setting the password for safety reset

Enter the 

SAFETY

 submenu through the service menu.

To avoid resetting of safeties by unqualified persons, the user
password is asked by default when resetting a safety.

This password however can be changed to 

SERVICE PASSWORD

or to 

NONE

.

Setting of compressor running hours

Enter the 

COMPRESSOR

 submenu through the service menu.

When the displayed running hours do not comply with the actual
running hours of the compressor it is possible to change the running
hours to comply.

Defining of the changeable digital/analogue inputs and 
outputs

Enter the 

INPUT OUTPUT

 submenu through the service menu.

Besides locked inputs and outputs there are a number of changeable
inputs and outputs of which the function can be chosen from several
possibilities.

Possible functions for changeable digital inputs are:

NONE

: no function is appointed to the changeable digital input.

STATUS

: no function is appointed to the changeable digital

input, but the input status can be read in the "INPUT OUTPUT"
menu.

DUAL SETPOINT

: to switch between setpoints.

REMOTE ON/OFF

: to remotely switch the unit on or off.

REMOTE COOL/HEAT

: to remotely put the unit in cooling

mode or in heating mode.

CAP. LIM 25%

/

50%

/

75%

/

SET

: to limit the capacity of the

unit to the entered values.

FREE COOLING REQ

: to remotely put the unit into free

cooling state.

FAN FORCED ON

: to activate the fans if the unit is off

Possible functions for the changeable digital output are:

NONE (OPEN)

: no function is appointed to the changeable

digital output.

CLOSED

: no function is appointed to the changeable digital

output, but the output is closed.

2ND PUMP

: can be used to steer a second evaporator pump.

100% CAPACITY

: indicates when the unit is working at

100%.

FULL CAPACITY

: indicates when the unit is working at

maximum capacity, example reached 100% capacity or reached
maximum capacity because of safety limitation.

FREE COOLING

: to control a 3-way water valve when the unit

is working in free cooling state.

GEN.OPERATION

: indicates when the unit is switched on.

W.(NO)

: indicates that a safety or warning is active

using a normal open contact.

W.(NC)

: indicates that a safety or warning is active

using a normal closed contact.

SAFETY (NO)

: indicates that a safety is active using a

normal open contact.

SAFETY (NC)

: indicates that a safety is active using a

normal closed contact.

C1

/

C2 SAFETY

: indicates that a circuit safety is active.

WARNING

: indicates that a warning is active.

C1

/

C2 OPERATION

: indicates that a compressor of that

circuit is switched on.

0% CAPACITY

: indicates that no compressors are switched on.

COOLING

: indicates that the cooling mode is active.

HEATING

: indicates that the heating mode is active.

DEFROST

: indicates that the defrost mode is active.

Possible configurations for the changeable analogue input are:

For each configuration of 

CHANG.AI

 the type must also be

selected:

0-20mA

4-20mA

0-1V

0-5V

0-10V

NTC TYPE 1

NTC TYPE 2

NTC TYPE 3

NTC

TYPE 4 

(Refer to the service manual to know what the

different types of NTC sensors stand for.)

DI

 (Digital input) 

(for how to connect, refer to the wiring diagram)

NONE

: no function is appointed to the changeable analogue

input.

STATUS

: only displays the status by means of test

FLOATING SETP

: floating setpoint based on ambient or

analogue input (only available for 

mA

V

 or 

NTC

 types)

TEMPERATURE

: only displays the (by example) condenser

outlet temperature (only available for 

NTC

 types)

DI

***: refer to the possible functions for changeable digital

inputs. (*** can be any of the following: 

STATUS

DUAL

SETPOINT

REMOTE ON/OFF

REM. COOL/HEAT,

FREE COOLING REQ

LOW NOISE

 or 

FAN FORCED

ON

.) (only available for 

DI

 (digital input) types)

Setting of the probe offset

Enter the 

INPUT OUTPUT

 submenu through the service menu.

It is possible to enter a correction value for certain measured
temperatures (inlet water evaporator temperature and mixed outlet
water evaporator temperature). This in order to correct a possible
measurement fault. The default value of the probe offset, is equal to 0.

Steering the pump manually

Enter the 

PUMP

 submenu through the service menu

There is the possibility to turn the pump on or off manually. This
means that when the unit is off the pump can also be turned on at
any time to check the pump.

In case a heater tape is installed

Enter the 

PUMP

 submenu through the service menu

In case no heater tape is installed, a pump can be activated in low
ambient conditions when the unit is switched off.

NOTE

Since inadequate resetting of safeties can damage the
machine, it is advised to keep the default protection
level setting of the 

SAFETY

 menu and certainly not to

change it to 

NONE

.

NOTE

NO

: normal open contact

Possible all changeable digital outputs
-

Safety active = contact closed

-

No power = contact open

-

No safety active = contact open

NC

: normal closed contact

Only possible on changeable digital output 1
-

Safety active = contact closed

-

No power = contact closed

-

No safety active = contact open

The default setting is 

OFF

. Modify

this setting to 

ON

 in case the pump

function is required

.

_        PUMPCONTROL

IF UNIT OFF AND LOW

WATER TEMP THEN PUMP

: OFF

Содержание EWYQ080DAYN

Страница 1: ...INSTALLATION MANUAL EWYQ080DAYN EWYQ100DAYN EWYQ130DAYN EWYQ150DAYN EWYQ180DAYN EWYQ210DAYN EWYQ230DAYN EWYQ250DAYN Packaged air cooled water chillers...

Страница 2: ...4P F13 230V 24V K4P M4P L2 L3 SLAVE 3 SLAVE 3 F14 F2 F3 N L1 F4 F15 230V 24V K3P M3P L2 L3 SLAVE 2 F16 F5 F6 N L1 F7 F17 230V 24V K2P M2P L2 L3 SLAVE 1 F18 F8 F9 N L1 F10 F19 230V 24V K1P M1P L2 L3 MA...

Страница 3: ...ate cu Certificatul C conform celor stabilite n Dosarul tehnic de construc ie D i apreciate pozitiv de E Modul aplicat F n conformitate cu Certificatul G Categorie de risc H Consulta i de asemenea pag...

Страница 4: ...stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi 14 Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota TS TSmin M...

Страница 5: ...OP03 Condenser protection grills OPCG Inverter fans OPIF Low noise operation OPLN OPIF compressor housing Single pump OPSP High static pump OPHP Twin pump OPTP Heater tape s OP10 Glycol application f...

Страница 6: ...either the discharged air nor the sound generated by the unit disturb anyone 7 Make sure that the air inlet and outlet of the unit are not positioned towards the main wind direction Frontal wind will...

Страница 7: ...indicated The concrete foundation should approximately be 100 mm higher than the oor level for ease of plumbing work and better drain Make sure that the foundation surface is even and at 4 Remove the...

Страница 8: ...ystem and the water ow through the evaporator must be within the operation range as speci ed in the table Cooling mode Heating mode Only for models with option OPSP OPTP or OPHP Maximum allowed instal...

Страница 9: ...detectable corrosion Ammonium ion mg NH4 l 1 0 0 1 corrosion Remaining chloride mg Cl l 0 3 0 3 corrosion Free carbide mg CO2 l 4 0 4 0 corrosion Stability index corrosion scale The chillers are only...

Страница 10: ...PTC K1S Overcurrent relay pump not for options OPSC OPTC OPSP OPTP and OPHP K2P Pump contactor only for options OPTP and OPTC M1P Pump motor 1 only for options OPSC OPTC OPSP OPTP and OPHP M2P Pump mo...

Страница 11: ...ting of the eld wiring must be as indicated in the gures below In the cover plate some free space is provided to install the appropriate nipples drilling through the cover plate is required for single...

Страница 12: ...of the cable 0 75 mm2 4 wire and maximum 500 m long Setting the addresses on the remote digital controller When a remote digital controller is used the address has to be set by means of DIP switches...

Страница 13: ...ng The electrical main power supply must be arranged so that it can be switched on or off independently of the electrical supply to other items of the plant and equipment in general Refer to the wirin...

Страница 14: ...it safety is active WARNING indicates that a warning is active C1 C2 OPERATION indicates that a compressor of that circuit is switched on 0 CAPACITY indicates that no compressors are switched on COOLI...

Страница 15: ...cannot modify them De ning the thermostat settings For a stand alone unit Enter the rst screen of the THERMOSTAT submenu through the service menu De ning the thermostat settings for inlet or outlet wa...

Страница 16: ...S1S S3 is pushed by the operator Slave 1 S1 slave 2 S2 and the master unit M are switched ON or OFF using the remote start stop switch S1S M which is connected to the master unit The setpoint can be...

Страница 17: ...t slave 3 S3 is kept as a standby unit Setup The system is controlled on entering water temperature The pumps of the slave units only run when their compressor is running energy saving After stopping...

Страница 18: ...Installation manual 14 EWYQ080 250DAYN Packaged air cooled water chillers 4PW35559 1D 03 2011 NOTES...

Страница 19: ...r circuit The operation of the water chiller is then controlled by the Digital Display Controller Shut down by switching off the controller and the circuit breaker of the power circuit WARNINGS Emerge...

Страница 20: ...4PW35559 1D 03 2011 Copyright 2007 Daikin...

Отзывы: