2.22
Oil Management Safeties
2.22.1
Pressure ratio alarm
Introduction
Because the capacity control is done by oil pressure it is very important to have a minimum pressure
difference between LP and HP to be able to move the sliding vane.
Function
description
When the pressure ratio is too small for a specified time, the controller will give an alarm.
■
When the unit is at 25% capacity, the unit will go into alarm when the pressure ratio is below 1.4
for a specified time.
■
When the unit is at 100% capacity, the unit will go into alarm when the pressure ratio is below 1.8
for a specified time.
■
When the unit is between 25% and 100% capacity the unit will go into alarm when the pressure
ratio is below the calculated value for a specified time.
pressure ratio =
discharge pressure (Abs)
____________________
suction pressure (Abs)
1.4
Pressure ratio
1.8
25 % cap.
100 % cap.
Pressure Ratio Alarm
Min Load Setp
Max Load Setp
1.4
1.8
ESIE07-05.book Page 78 Friday, December 21, 2007 3:21 PM
Содержание EWWQ-AJYNN
Страница 3: ...ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 13: ...ESIE07 05 2 2 Part 2 Functional Description 3 1 2 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 88: ...ESIE07 05 3 2 Part 3 Troubleshooting 3 1 3 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 112: ...ESIE07 05 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 114: ...ESIE07 05 5 2 Part 5 Maintenance 3 1 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...