The Digital Controller
ESIE07-05
2–34
Part 2 – Functional Description
3
1
2
4
5
Compressor configuration
■
N. OF COMPRESSOR: 1/2/3/4
■
N. OF EVAPORATORS (if compressor number >2)
■
Max number of pulses to load
compressor
■
Max number of pulses to unload
compressor
15
15
Min. Time between same
compressor start
600 s
Min. Time between different
compressor start
120 s
Min. Time compressor On
120 s
Min. Time compressor Off
180 s
■
Interstage Timer
■
Double load/unload pulse for
compressor load under
210 sec
35%
Compressor unloading pulse time
■
PULSE TIME = 0.3 s
■
MIN. PULSE PERIOD = 1 s
■
MAX. PULSE PERIOD = 10 s
Compressors config.
1
N. of compressors
Number of pulses
to load comp.
Number of pulses
to unload comp.
015
015
Min T between same
comp. starts
comp. starts
Min T between diff.
600
120
s
s
Min Time compressor
ON
OFF
Min Time compressor
120
180
s
s
Interstage time
Double pulse under
210
035
s
%
Compressor Unloading
Min pulse period
Max pulse period
Pulse time
00.3
01
010
s
s
s
ESIE07-05.book Page 34 Friday, December 21, 2007 3:21 PM
Содержание EWWQ-AJYNN
Страница 3: ...ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 13: ...ESIE07 05 2 2 Part 2 Functional Description 3 1 2 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 88: ...ESIE07 05 3 2 Part 3 Troubleshooting 3 1 3 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 112: ...ESIE07 05 4 2 Part 4 Commissioning and Test Run 3 1 4 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...
Страница 114: ...ESIE07 05 5 2 Part 5 Maintenance 3 1 5 ESIE07 05 book Page 2 Friday December 21 2007 3 21 PM...