Operation manual

23

EWWP045~06 ECB1~3MUW

Packaged water-cooled water chillers

4PW30041-1A

32~72H

P

 A

NNEX

 III - S

OFTWARE

 

STRUCTURE

Actual screens can be different than the shown example (52~72Hp).

$

>INLSETP1  E : 12.0°C

      INLSETP2 E : 12.0°C

      INLSETP1  C : 30.0°C

      INLSETP2 C : 30.0°C

      ENTER  PASSWORD

      PASSWORD :  0000

BX

          GENERAL  TIMERS

LOADUP:000s-DWN:000s

PUMPLEAD  : 000s

FLOWSTOP   : 00s

BX

                   UNIT SAFETY

0C9 : INL  E  SENSOR  ERR

>READOUT MENU

  SETPOINTS MENU

  USERSETTINGS MENU

  TIMERS MENU

  HISTORY MENU

  INFO MENU

  I/O STATUS MENU

  USERPASSWORD MENU

  COOL/HEAT MENU

BX

 MANUAL MODE

INL WATER   E:  12.0°C

INL WATER   C: 30.0 °C

THERMOSTAT STEP :2/6

$e

                 EVAPORATOR

M1 : OUTLWATER:  07.0 °C

M2: OUTLWATER:  07.0 °C

M3: OUTLWATER:-03.0 °C

$e

     HD PERIOD: 01 TO 03

01  : 01/09    TO  04/09

02 : 00/00  TO  00/00

03 : 00/00  TO  00/00

$e

          SCHEDULE  TIMER

MON : G1  THU : G2  SAT : -

TUE  : G1  FRI  : G2  SUN : -

WED : -

      ENTER  PASSWORD

      PASSWORD :  0000

$e

 SETPOINT  PASSWORD

PASSWORD  NEEDED  TO

CHANGE  SETPOINTS : Y

$e

  COMPRESSOR  TIMERS

COMPR.  STARTED : 00s

$e

      DISPLAY  SETTINGS

LANGUAGE : ENGLISH

TIME  : 00h00

DATE : 00/01/2001

$e

        GROUP1 : 01  TO  03

1  : 00h00  -   -       -

2 : 00h00  -   -       -

3 : 00h00  -   -       -

$e

  COMPRESSOR  TIMERS

C11   GRD : 000s  AR : 000s

C12  GRD : 000s  AR : 000s

C21  GRD : 000s  AR : 000s

$e

        HOLIDAY : 01 TO 03

1 : 00h00    -

2: 00h00    -

3: 00h00    -

$e

       DUAL  EVAP.  PUMP

MODE : AUTOM.  ROTATION

OFFSET  ON  RH :  0048h

$e

       GROUP2 : 01  TO  03

1  : 00h00  -   -       -

2 : 00h00  -   -       -

3 : 00h00  -   -       -

$e

    THERMOST.SETTINGS

STEPS : 6    STPL.:  1.5°C

STEPDIFFERENCE: 0.5°C

LOADUP: 180s-DWN: 30s

$e

       GROUP3 : 01  TO  03

1  : 00h00  -   -       -

2 : 00h00  -   -       -

3 : 00h00  -   -       -

$e

 COMPRESSOR STATUS

C11 : OFF-CAN STARTUP

C12: OFF-CAN STARTUP

C21: OFF-CAN STARTUP

g

$e

 COMPRESSOR STATUS

C22: OFF- CAN STARTUP

C31 : OFF- SAFETY ACT.

C32: OFF- LIMIT

$a

          RUNNING HOURS

C11  : 00010h   12 ; 00010h

C21 : 00010h  22 ; 00010h

C31 : 00010h  32 ; 00010h

$e

       GROUP4 : 01  TO  03

1  : 00h00  -   -       -

2 : 00h00  -   -       -

3 : 00h00  -   -       -

$a

  COMPRESSOR  TIMERS

C22 GRD : 000s  AR : 000s

C31  GRD : 000s  AR : 000s

C32 GRD : 000s  AR : 000s

q

$z

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

 00h00 - 12/01/2001

         MANUAL MODE

$e

 CONTROL SETTINGS

MODE :MANUAL CONTROL

C11  : OFF  12 ; OFF  31  ; OFF

C21 : OFF 22; OFF  32 ; OFF

$e

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

INL.E :  12.0°C    STEP :

INL.C : 30.0°C    0

$e

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

OUTE1 :  07.0°C       OUTE3 :

OUTE2:  07.0°C       07.0°C

$e

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

C11 :  ON              C21: 

C12:  ON              ON

$e

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

C22 :  ON             C32 :

C31 :    OFF           OFF

$e

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

RH11  : 00000h RH21:

RH12 : 00000h 00000h

$a

      UNIT HISTORY : 004

0C9 : INL  E  SENSOR  ERR

RH22: 00000h      RH32:

RH31:  00000h      00000h

$z

      UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

 00h00 - 01/01/2001

       INLSETP2 E : 30.0°C

$e

       UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

INL.E :  12.0°C    STEP :

INL.C : 30.0°C    2

$e

 UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

OUTE1 :  07.0°C    OUTE3:

OUTE2:  07.0°C    07.0°C

$e

       UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

C11 :  OFF - SAF  C21: 

C12:  OFF - SAF  OFF - SAF

$e

       UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

C22:  OFF - SAF  C32: 

C31  :  OFF              OFF

$e

       UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

RH11  : 00000h RH21:

RH12 : 00000h 00000h

$a

       UNIT HISTORY : 003

0AE : FLOW HAS STOPPED

RH22: 00000h     RH32:

RH31 : 00000h     00000h

$z

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

 00h00 - 01/01/2001

        INLSETP1 E : 30.0°C

$e

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

INL.E :  12.0°C    STEP :

INL.C : 30.0°C    2

$e

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

OUTE1 :  07.0°C    OUTE3:

OUTE2:  07.0°C    07.0°C

$e

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

C11 :  OFF              C21: 

C12:  OFF              OFF

$e

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

C22:  OFF              C32: 

C31  :  ON                ON

$e

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

RH11  : 00000h RH21:

RH12 : 00000h 00000h

$a

    MOD 1 HISTORY : 002

1EO : GENERAL SAFETY

RH22: 00000h     RH32:

RH31 : 00000h     0000h

$z

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

 00h00 - 12/01/2001

        INLSETP1 C : 07.0°C

$e

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

INL.E :  12.0°C    STEP :

INL.C : 30.0°C    2

$e

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

OUTE1 :  07.0°C    OUTE3:

OUTE2:  07.0°C    07.0°C

$e

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

C11 :  OFF - F D    C21: 

C12:  OFF - F D    OFF - F D

$e

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

C22:  OFF - F D    C32: 

C31  : OFF - SAF   OFF - SAF

$e

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

RH11  : 00000h RH21:

RH12 : 00000h 00000h

$a

    MOD 3 HISTORY : 001

3EO : GENERAL SAFETY

RH22: 00000h    RH32:

RH31 : 00000h    00000h

$z

       TIME  INFORMATION

TIME   : 00h00

DATE : 00/01/2001

$e

        UNIT INFORMATION

UNITTYPE : WW-HP-32

MANUFACT. NR.: 0000000

REFRIGERANT  : R134a

$e

        UNIT INFORMATION

SW : V1.0M6  (01/11/01)

SW   CODE :  FLDKNMCH0A

$z

            DIGITAL  INPUTS

M1   SAFETY OK

M2  SAFETY OK

M3  SAFETY NOK

$e

          RELAY  OUTPUTS

LPBYPASS1  : CLOSED

LPBYPASS2 : CLOSED

LPBYPASS3 : OPEN

$a

 CHANG.  REL  OUTPUTS

DO1  REV.VALVE(C/H)  : O

$e

   CHANG.  DIG.  INPUTS

DI1   DUAL  SETP : SETP.1

DI2  REM.  ON/OFF : OFF

DI3  REM.  C/H : COOL

$e

          RELAY  OUTPUTS

C11  : ON          C12  : ON

C21 : ON          C22 : ON

C31 : OFF        C32 : OFF

$e

           RELAY  OUTPUTS

GEN. ALARM: CLOSED

PUMP/GEN OPER: CLOSED

$e

            DIGITAL  INPUTS

FLOWSWITCH : FLOW OK

REV.PHASE  PR. : OK

$

       CHANGE PASSWORD

NEW PASSWORD : 0000

              CONFIRM : 0000

       

ENTER  PASSWORD

       PASSWORD :  0000

$

           COOLING/HEATING

MODE :  COOLING (EVAP)

h

q

q

g

h

g

h

g

h

g

h

q

g

h

g

h

h

g

h

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

h

q

g

h

g

h

g

h

g

h

g

h

g

h

g

h

g

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

q

p

h

h

g

g

$a

        PCB INFORMATION

BOOT : V2.02-02/08/00

BIOS  : V2.32-31/07/01

g

h

$e

 ENTER  SERVICE

         PASSWORD :  0000

g

f

$e

    LEAD-LAG SETTINGS

LEAD-LAG MODE   : AUTO

LEAD-LAG HOURS: 1000h

$e

     CAP.  LIM.  SETTINGS

MODE : REMOTE  DIG  INP.

L1M1  : OFF   2: OFF  3: OFF

L2M1 : OFF  2: OFF  3: OFF

$e

     CAP.  LIM.  SETTINGS

L3M1  : OFF   2: OFF  3: OFF

L4M1  : OFF   2: OFF  3: OFF

$e

               PUMPCONTROL

PUMPLEADTIME :  020s

PUMPLAGTIME   :  000s

DAILY ON : Y    AT : 00h00

$e

           SCHEDULE TIMER

ENABLE TIMER : N

ENABLE HOLIDAY PER : N

only for 

52~72Hp

Содержание EWWP045KAW1M

Страница 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Страница 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Страница 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Страница 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Страница 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Страница 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Страница 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Страница 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Страница 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Страница 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Страница 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Страница 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Страница 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Страница 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Страница 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Страница 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Страница 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Страница 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Страница 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Страница 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Страница 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Страница 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Страница 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Страница 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Страница 25: ...NOTES NOTES...

Страница 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30041 1A...

Отзывы: