EWWP045~06 ECB1~3MUW

Packaged water-cooled water chillers

4PW30041-1A

Operation manual

18

Tasks of the history menu

Checking the safety info and the unit status after a reset

The information available in the safeties menu is also stored in the
history menu, where it is stored after resetting the unit or the module.
In this way, the history menu provides a means of checking the unit
status at the moment of the latest 10 shutdowns.

To check the safety info and the unit status, proceed as follows:

1

Enter the 

HISTORY MENU 

through the main menu. (Refer to the

chapter 

"Main menu" on page 14

.)

The controller enters the 

UNIT HISTORY

 screen which contains the

following information: the number of shutdowns, the unit safety
which caused the most recent shutdown and the basic
information at the moment of this shutdown.

2

Press the 

and

  h

  keys to consult the 

M1

,

  M2 

or 

M3 HISTORY

screens.

3

Press the 

q

 key to see the detailed information.

Tasks of the info menu

Consulting additional unit information

1

Enter the 

INFO MENU 

through the main menu. (Refer to the

chapter 

"Main menu" on page 14

).

The controller enters the 

UNIT INFORMATION

 screen which contains

the following information: the unit name, the refrigerant used and
the manufacturing (serial) number.

2

Press 

h

 to consult the next 

UNIT INFORMATION

 screen.

This screen contains information about the controller's software
version.

Tasks of the input/output menu

Checking the status of the inputs and outputs

The input/output menu provides a means of checking the status of
the digital inputs and the status of the relay outputs.

The locked digital inputs are:

M1

,

  M2 

or 

M3 SAFETY

:  indicates the status of the general module

safeties.

FLOWSWITCH

:  indicates the status of the flowswitch, activated or

deactivated.

REVERSE PHASE PROTECTOR

: indicates the status of this safety.

The changeable digital inputs are:

REM. C/H

:  indicates the status of the remote cooling/heating

switch.

DUAL SETPOINT

:  indicates the status of the remote dual setpoint

switch, setpoint 1 or setpoint 2.

REM. ON/OFF

: indicates the status of the remote on/off switch.

CAP LIM1/2/3

: indicates the status of the enable/disable capacity

limitation switch(es).

The locked relay outputs are:

LPBYPASS 1/2/3

:  indicates whether the low pressure of the

module is in bypass mode or not.

C11, C12, C21, C22, C31, C32

:  indicates whether the compressor is

running or not.

PUMP/GEN OPER

: indicates the status of this voltage free contact.

It is activated if the pump should be ON, which also indicates
general operation.

The changeable relay outputs are:

REV. VALVE (C/H)

: indicates whether the unit is running in cooling

or in heating.

2ND EVAP PUMP

:  indicates the status of the second evaporator

pump.

CONDENSER PUMP

: indicates the status of the condenser pump.

100% CAPACITY

: indicates when the unit is working at 100%.

To check the inputs and outputs, proceed as follows:

1

Enter the 

I/O STATUS MENU 

through the main menu.

 

(Refer to the

chapter 

"Main menu" on page 14

.)

The controller enters the first 

DIGITAL INPUTS

 screen.

2

Consult the other screens of the input/ouput menu using the 

g

and

 h

 keys.

Tasks of the user password menu

Changing the user password

Access to the user settings menu and the setpoints menu is
protected by the user password (a 4-digit number between 

0000

 and

9999

).

To change the user password, proceed as follows:

1

Enter the 

USERPASSWORD MENU

 through the main menu

.

 (Refer to

the chapter 

"Main menu" on page 14

).

The controller will request the password.

2

Enter the correct password using the 

and

 h

 keys.

3

Press 

q

  to confirm the password and to enter the password

menu.

The controller requests the new password.

4

Press 

q

 to start the modification.

The cursor is positioned behind 

NEW PASSWORD

.

5

Enter the new password using the 

and

 h

 keys.

6

Press 

q

 to confirm the new password.

When the new password has been confirmed, the controller will
ask to enter the new password a second time (for safety
reasons). The cursor is positioned behind 

CONFIRM

.

7

Enter the new password again using the 

and

 h

 keys.

8

Press 

q

 to confirm the new password.

NOTE

The actual password will only be changed when the
new password and the confirmed password have the
same value.

Содержание EWWP045KAW1M

Страница 1: ...OPERATION MANUAL EWWP045KAW1M EWWP055KAW1M EWWP065KAW1M ECB1MUW ECB2MUW ECB3MUW Packaged water cooled water chillers...

Страница 2: ...arting up the unit for the first time make sure that it has been properly installed It is therefore necessary to carefully read the installation manual supplied with the unit and the recommendations l...

Страница 3: ...nning current A 10 4 13 1 15 0 10 4 10 4 13 1 13 1 13 1 15 15 10 4 13 1 10 4 13 1 13 1 13 1 15 13 1 15 15 27 11 23 26 500 500 500 2 3 1 4 20 17 12 13 24 21 18 25 16 22 19 28 28 28 8 5 6 9 7 10 15 14 1...

Страница 4: ...denser removes small particles from the refrigerant to prevent blockage of the tubes Expansion valve The liquid refrigerant coming from the condenser enters the evaporator via an expansion valve The e...

Страница 5: ...rough the water heat exchanger an interlock contact S11L of e g a flow switch must be installed in the start up circuit of the unit Internal wiring Parts table Refer to the internal wiring diagram sup...

Страница 6: ...ommendations Before switching on the unit read following recommendations 1 When the complete installation and all necessary settings have been carried out close all front panels of the unit 2 The serv...

Страница 7: ...ter a few minutes consult the actual operational information available in the list of direct parameters Also refer to the chapter Troubleshooting on page 19 Switching the unit off To switch the unit o...

Страница 8: ...he parameter codes 5 To consult other actual operational information repeat from instruction 2 onwards 6 To return to normal operation press the E key or wait approximately 40 seconds In the first cas...

Страница 9: ...s of the user password When scrolling through the list of parameters using the A and or Z key you see the direct parameters and user parameters The user parameters appear in the following order d to d...

Страница 10: ...g on the setting of user parameter d all temperature values are displayed in C or in F The conversion formulas from C to F and vice versa are T C T F 32 1 8 T F T C x 1 8 32 If user parameter d is set...

Страница 11: ...ars on the display Enabling or disabling the buzzer When an alarm is detected the buzzer is activated for the period defined by user parameter p4 The default limit and step values for the activation p...

Страница 12: ...arameter code h9 using the A and or Z key 3 Press the R key to switch to the parameter value 4 Select the appropriate setting using the A and or Z key 5 Press the R key to return to the list of parame...

Страница 13: ...and an initialization cycle is started Once all the timers have reached zero the unit starts up When a remote ON OFF switch is configured the following table applies 2 When the unit is started up for...

Страница 14: ...ture of condenser setpoint 2 In double thermostat operation two setpoints are reserved for inlet control of the evaporator and two others are reserved for inlet control of the condenser INLSETP 1 E in...

Страница 15: ...information i e the number of times a unit safety or a circuit safety occurred and the unit status at the moment of shutdown can be checked by means of the history menu To consult actual operational...

Страница 16: ...SOR TIMERS COMPR STARTED 00s BC COMPRESSOR TIMERS C11 GRD 000s AR 000s C12 GRD 000s AR 000s C21 GRD 000s AR 000s BW COMPRESSOR TIMERS C22 GRD 000s AR 000s C31 GRD 000s AR 000s C32 GRD 000s AR 000s BX...

Страница 17: ...SETTINGS screen of the user settings menu The default limit and step values for the thermostat parameters are Defining the lead lag mode The lead lag mode determines which module starts up first in ca...

Страница 18: ...ow through the evaporator stops after the flowstart timer has reached zero If the water flow has not restarted during the countdown the unit will shut down PUMPLEAD PUMPLEAD refer to the pump control...

Страница 19: ...l setpoint switch setpoint 1 or setpoint 2 REM ON OFF indicates the status of the remote on off switch CAP LIM1 2 3 indicates the status of the enable disable capacity limitation switch es The locked...

Страница 20: ...ivated The ON LED is broken Contact your local dealer The unit is in bypass mode Check the bypass remote contact POSSIBLE CAUSES CORRECTIVE ACTION One of the following safety devices is activated Comp...

Страница 21: ...ter filters Check if the mesh width is 1 mm maximum Disposal requirements Dismantling of the unit treatment of the refrigerant oil and any other parts should be done in accordance with the relevant lo...

Страница 22: ...t control default 32 48Hp 4 step thermostat control default 32 48Hp 6 step thermostat control default 52 72Hp 6 step thermostat control default 52 72Hp 0 1 2 a b Stepnumber Setpoint Temperature 0 1 2...

Страница 23: ...group settings of groups G1 G2 G3 G4 and H work similar as following example settings for group 1 MARCH MON TUE WED THU FRI SAT SUN 1 G1 2 G1 3 G2 4 G1 5 G1 6 G3 7 G3 8 G1 9 G1 10 G2 11 G1 12 G1 13 G...

Страница 24: ...HAS STOPPED OUTE1 07 0 C OUTE3 OUTE2 07 0 C 07 0 C e UNIT HISTORY 003 0AE FLOW HAS STOPPED C11 OFF SAF C21 C12 OFF SAF OFF SAF e UNIT HISTORY 003 0AE FLOW HAS STOPPED C22 OFF SAF C32 C31 OFF OFF e UN...

Страница 25: ...NOTES NOTES...

Страница 26: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PW30041 1A...

Отзывы: