![Daikin EWWD170~600G-SS Скачать руководство пользователя страница 38](http://html1.mh-extra.com/html/daikin/ewwd170-600g-ss/ewwd170-600g-ss_installation-operation-and-maintenance-manual_4025782038.webp)
D-EIMWC00208-16EN - 38/48
Standard Checks
Temperature and pressure sensors
The unit comes factoryequipped with all the sensors listed below. Periodically check that their measurements are correct
by means of reference instruments (manometers, thermometers); correct the wrong readings as necessary using the
microprocessor keypad. W ellcalibrated sensors ensure better efficiency for the machine and a longer lifetime.
Note: Refer to the microprocessor use and maintenance manual for a complete description of applications, settings and
adjustments.
All sensors are preassembled and connected to the microprocessor. The descriptions of e ach sensor are listed below:
Outlet water temperature sensor
– This sensor is located on the evaporator outlet water connection and is used by the
microprocessor to control the machine load depending on the system’s thermal load. It also helps control the
evaporator’s antifreeze protection.
Inlet water temperature sensor
– This sensor is located on the evaporator inlet water connection and is used for
monitoring the return water temperature.
Compressor discharge pressure transducer
– This is installed on every compressor and allows to monitor the
discharge pressure and to control the fans. Should the condensation pressure increase, the microprocessor will control
the compressor load in order to allow it to function even if the compressor flow gas must be reduced. It also contributes
to the oil control logic.
Oil pressure transducer
– This is installed on every compressor and allows to monitor the oil pressure. The
microprocessor uses this sensor to inform the operator on the conditions of the oil filter a nd on how the lubrication
system is functioning. By working together with the high and lowpressure transducers, it protects the compressor from
problems deriving from poor lubrication.
Lowpressure transducer
– This is installed on every compressor and allows to monitor the compressor suction
pressure along with low pressure alarms. It contributes to complementing the oil control logic.
Suction sensor
– This is installed optionally (if the electronic expansion valve has been requested) on every
compressor, and allows to monitor the suction temperature. The microprocessor uses the signal from this sensor to
control the electronic expansion valve.
Compressor discharge temperature sensor
– This is installed on every compressor and allows to monitor compressor
discharge pressure and oil temperature. The microprocessor uses the signal from this sensor to control the liquid
injection and to shut down the compressor in case that the discharge temperature reaches 110°C. It also protects the
compressor from pumping liquid refrigerant at startup.
Содержание EWWD170~600G-SS
Страница 14: ...D EIMWC00208 16EN 14 48 Fig 7 Condenser Located above Chiller Unit Fig 8 Condenser Located below Chiller Unit...
Страница 21: ...D EIMWC00208 16EN 21 48 Fig 10 Refrigeration cycle EWWD G SS EWWD G XS 23 5 bar...
Страница 22: ...D EIMWC00208 16EN 22 48 Fig 11 Refrigeration cycle EWWD G SS EWWD G XS Partial Heat recovery 23 5 bar...
Страница 23: ...D EIMWC00208 16EN 23 48 Fig 12 Refrigeration cycle EWLD G SS OPTIONAL 23 5 bar...
Страница 45: ...D EIMWC00208 16EN 45 48...
Страница 46: ...D EIMWC00208 16EN 46 48...
Страница 47: ...D EIMWC00208 16EN 47 48...