D-EIMWC003H02-18_02EN - 19/34 

 

 

Figure 6-Condensation control scheme with well water

 

 

From the main condenser pump 

Service valve 

Direct acting water regulating valve 

Configuration required when the regulating valve is not used 

At Drain 

2.12  Chilled water control sensor 

The  water  cooled  EWWH  VZ  unit  is  equipped  with  a  microprocessor.  Be  careful  when  working  around  the  unit  to  avoid 
damaging  cables  and  sensors.  Check  cables  before  starting  the  unit.  Prevent  rubbing  of  the  cables  on  the  frame  or  other 
components.  Make  sure  the  cables  are  securely  locked.  If  the  temperature  sensor  is  removed  for  maintenance,  do  not 
eliminate the conductive paste in the well and replace the sensor correctly. After replacing the sensor, tighten the lock nut to 
prevent accidental slipping. 

2.13  Safety Valve 

Each  exchanger  (evaporator  and  condenser)  is  provided  with  a  safety  valve  installed  on  a  changeover  valve  that  allows 
maintenance  and  periodic  checks,  without  losing  a  significant  amount  of  refrigerant.  Do  not  leave  the  safety  valve  in  the 
intermediate position. 

 

To  prevent  damages  due  to  inhalation  and  direct  contact  with  refrigerant  gas,  the  safety  valve 
outlets  must  be  connected with  a conveyor  pipe  before  operations.  These pipes  must  be  installed 
so that, in case the valve opens, the discharged refrigerant flow not invest people and/or things, or 
can  enter  the  building  through  windows  and/or  other  openings.  The  installer  is  responsible  for 
connecting  the  safety  valve  to  the  purge  pipe  and  pipe  dimensioning.  In  this  regard,  refer  to  the 
harmonized standard EN13136 to dimension the drain pipes to be connected to the safety valves 

2.14  Open the isolation and/or shut off valves 

Before powering the machine and thus starting the compressors, open all valves that were closed at the factory for shipping. 
 The valves to be opened are: 

1.  Valve (optional) installed on the compressor line 
2.  Oil return pipe shutoff valves (jet pump). These valves are positioned below the evaporator sleeve in the vicinity of 

the jet pump. 

3.  Liquid line valve installed under the condenser. 
4.  Oil valves installed on the line that feeds the compressor lubrication system. This line comes from the bottom of the 

oil separator located inside the condenser. 

5.  Valve (optional) installed on the compressor pump line. 

 

2.15  Electrical connections 

The  unit  must  be  connected  with  in  the  proper  section  copper  cables  relative  to  the  plate  absorption  values  and  in 
accordance with applicable electrical regulations. 
Daikin Applied Europe SpA cannot be held liable for improper electrical connections. 
 

 

The connections to the terminals must be made with copper terminals and cables. 
The electrical connection must be made by qualified personnel. 
There is a risk of electric shock 

 
The electrical panel must be connected keeping the correct phase sequence.  

2.16  Phase imbalance  

In  a  three-phase  system,  excessive  imbalance  between  the  phases  is  the  cause  of  motor  overheating.  The  maximum 
allowed voltage imbalance is 2%, calculated as follows: 

𝐼𝑚𝑏𝑎𝑙𝑎𝑛𝑐𝑒 % =

(𝑉𝑥 − 𝑉𝑚) ∗ 100

𝑉𝑚

 

Vx = phase with greatest imbalance 
Vm = average of the voltages 

Содержание EWWD VZ

Страница 1: ...ion in English REV 02 Date December 2018 Supersedes D EIMWC003H02 18_01EN WATER COOLED WATER CHILLERS WITH VARIABLE SPEED COMPRESSOR EWWD VZ EWWH VZ Installation maintenance and operating manual D EIM...

Страница 2: ...or shut off valves 19 2 15 Electrical connections 19 2 16 Phase imbalance 19 2 17 Control circuit 20 3 OPERATION 20 3 1 Operator s responsibilities 20 3 2 Unit description 21 3 3 Cooling cycle descrip...

Страница 3: ...applied to the unit 4 Figure 2 Description of the labels applied to the electric panel 6 Figure 3 Lifting instructions 11 Figure 4 Unit positioning 12 Figure 5 Condenser control scheme with cooling to...

Страница 4: ...D EIMWC003H02 18_02EN 4 34 Figure 1 Description of the labels applied to the unit Single circuit unit...

Страница 5: ...R solenoid valve circ 1 1 8 VR 5 Evaporator entering water temperature sensor 17 High pressure switch 6 Air purge 18 Discharge temperature sensor 7 Water drain 19 Oil Pressure Transducer 8 Liquid line...

Страница 6: ...unit Identification of labels 1 Manufacturer s logo 8 Lifting instructions 2 Electricity warning 9 Refrigerant 3 Shutoff valve position 10 W012 Symbol 4 Wire tightness check 11 Attention Closed Valve...

Страница 7: ...e refrigerant leaks 13 disable the unit from the mains using the main switch before opening the control panel 14 check that the unit has been grounded correctly before starting it 15 install the machi...

Страница 8: ...e screw compressor and adjustment inverters are designed and constructed to cool and or heat buildings or industrial processes Daikin technicians specifically trained for this purpose must start the f...

Страница 9: ...azing or similar activity and then only provided the refrigerant concentration is monitored and adequate ventilation is ensured Such open flames shall not be left unattended A remote switching emergen...

Страница 10: ...0 303 kg m3 0 07575 kg m3 16500 ppm All electrical equipment not only the refrigerating system shall be selected to be suitable for use in the zones identified in the risk assessment Electrical equipm...

Страница 11: ...n pads optional are shipped separately Make sure these items if required are delivered with the unit Use extreme caution when handling the unit to prevent damage to the control panel and the refrigera...

Страница 12: ...prevent refrigerant accumulation inside that can deprive air of the right oxygen content that can cause asphyxiation In this regard we recommend the application of harmonized standard EN378 3 Safety a...

Страница 13: ...freezing The flow switch must not be used as a machine control system The absence of the flow switch on the evaporator water connection voids the warranty for frost damage The evaporator and condenser...

Страница 14: ...f untreated water can result in corrosion erosion mud fouling and formation of algae Daikin Applied Europe is not liable for equipment damage or malfunction due to a lack of a water treatment or water...

Страница 15: ...and high condenser inlet water temperature may be inhibited Glycol must be used for all applications with the evaporator outlet fluid below 4 C The maximum permissible water temperature in the evapor...

Страница 16: ...C Ref 2c standard unit opt 174 Low Brine Limit for Propylene Glycol ELWT 8 C Ref 3 standard unit opt 111 High temperatures kit Ref 4a standard unit opt 08 Brine opt 111 high temperature kit Limit for...

Страница 17: ...5 lt kW Process 6 6 lt kW 5 0 lt kW Variable capacity 6 6 lt kW 5 0 lt kW Calculation example Cooling capacity at 100 670 kW Minimum system volume for conditioning 670 x 3 3 2211 lt Minimum system vol...

Страница 18: ...re should not be less than 20 C at full water tower flow rate If the water temperature must be lower even the water flow must be reduced proportionately To modulate the water flow to the condenser ins...

Страница 19: ...onsible for connecting the safety valve to the purge pipe and pipe dimensioning In this regard refer to the harmonized standard EN13136 to dimension the drain pipes to be connected to the safety valve...

Страница 20: ...tor becomes familiar with the equipment before operating the machine In addition to reading this manual the operator should study the operation manual and the wiring diagram supplied with the unit to...

Страница 21: ...ased to the condensation water which heats accordingly The condensed fluid at saturation temperature passes through the sub cooling section where it yields heat to further increase cycle efficiency Th...

Страница 22: ...control protects the compressor from any operating faults The oil filter must be replaced within the first 500 hours of compressor operations The electronic controller generates an alarm for high oil...

Страница 23: ...te that all units are also provided with the Control Manual Figure 7 Unit interface 3 3 8 Safeties for each refrigerant circuit High pressure pressure switch Motor cooling High compressor delivery tem...

Страница 24: ...thermistors the controller is able to constantly monitor winding temperature and stop the corresponding compressor in the event that the temperature exceeds the safety value Repeated interventions of...

Страница 25: ...tem the heat transfer fluid should be checked for the possible presence of refrigerant After any repair work the safety devices for example refrigerant detectors and mechanical ventilation systems sho...

Страница 26: ...f compressors installed on the machine The valves are managed and controlled by the main electronic controller that optimizes the flow of refrigerant gas to the evaporator according to machine operati...

Страница 27: ...Typical single circuit cooling circuit Fig 7 Typical dual circuit cooling circuit Legend 1 Compressor 15 Oil injection valve 2 Delivery valve optional 16 Oil injection solenoid valve 3 Oil Condenser S...

Страница 28: ...0 5 and 4 C d The difference between condensing temperature and condenser outlet water temperature is between 1 and 3 C 5 Make sure the indicator on the liquid tube is full If one of these parameters...

Страница 29: ...ed Europe Spa cannot be held liable for damage caused by untreated or improperly treated water 4 5 2 Seasonal start up Annual start up is a good time to assess motor winding ground resistance A semi a...

Страница 30: ...ntative technical staff a Oil Analysis have to be performed each year or every 5000 hours of operation whichever shall first occur b Change the oil filter if p 2 bar c Check water temperature entering...

Страница 31: ...operable Water system operated and flow balanced to meet unit design requirements Electrical Power leads connected to unit main terminal block Power leads have been checked for proper electrical phasi...

Страница 32: ...g instructions Any refrigerant charge for each circuit 1 2 3 added during commissioning the total refrigerant charge 1 2 3 calculate the greenhouse gas emission with the following formula 1000 Use the...

Страница 33: ...rdance with local laws regarding disposal and if in scope with the national laws implementing the Directive 2012 19 EU RAEE Batteries and electrical components must be sent to specific waste collectio...

Страница 34: ...contained herein are liable to change without notice Refer to the data communicated at the time of the order Daikin Applied Europe S p A cannot be held liable for direct or indirect damage in the bro...

Отзывы: