D-EIMHP01601-22_01EN 20/26     
 

1. 

the current absorbed by the compressor must be compared to the rated value. Normally the value of the absorbed current 
is lower  than  the  rated value  that corresponds  to the  absorption of  the full  load compressor  at the maximum operating 
conditions. 

2. 

at least once every three months all the security checks must be made to verify their functionality. Each appliance, with 
aging, can change its point of operation and this must be monitored to adjust it or replace it. The pump interlocks and flow 
switches must be checked to make sure that they interrupt the control circuit if they intervene. 

13.3 

Service and limited warranty 

All units are factory tested and guaranteed for 12 months as of the first start-up or 18 months as of delivery. 

These units have been developed and constructed according to high quality standards ensuring years of failure free operation. 

However,  the  unit requires  maintenance  even  during  the warranty  period,  from  the  time  of  installation  and  not  just 
from  the  commissioning  date. 

We  strongly  advise  stipulating  a  maintenance  contract  with  a  service  authorized  by  the 

manufacturer to ensure efficient and problem free service, thanks to the expertise and experience of our personnel. 
It must be borne in mind that operating the unit in an inappropriate manner, beyond its operating limits or not performing proper 
maintenance according to this manual can void the warranty. Observe the following points, to conform to warranty limits: 
 

1. 

The unit cannot function beyond the specified limits. 

2. 

The electrical power supply must be within the voltage limits and without voltage harmonics or sudden  changes. 

3. 

The  three-phase  power  supply  must  not  have  an  unbalance  between  phases  exceeding  3%.  The  unit  must  stay 
turned off until the electrical problem has been solved. 

4. 

No safety device, either mechanical, electrical or electronic must be disabled or overridden. 

5. 

The water used for filling the water circuit must be clean and suitably treated. A mechanical filter must be installed at 
the point closest to the 

BPHE

 inlet. 

6. 

The value of the 

BPHE

 water flow must be included in the declared range for the unit considered, refer to the 

CSS

 

selection

 software. 

Table 9

– Standard Routine Maintenance Plan

 

Monthly  Yearly/Seasonal 

List of Activities 

Weekly 

(Note 1) 

(Note 2) 

General: 

Reading of operating data (Note 3) 

 

 

Visual inspection of unit for any damage and/or loosening 

 

 

Verification of thermal insulation integrity 

 

 

Cleaning 

 

 

Paint where necessary 

 

 

Analysis of water (4) 

 

 

Check of flow switch operation 

 

 

Electrical Installation: 

Verification of control sequence 

 

 

Verify contactor wear 

– Replace if necessary 

 

 

Verify that all electrical terminals are tight 

– Tighten if necessary 

 

(Quarterly)   

Clean inside the electrical panel 

 

 

Visual inspection of components for any signs of overheating 

 

 

Verify operation of compressor and electrical resistance 

 

 

Refrigeration circuit: 

Check for any refrigerant leakage (leak test) 

 

 

Analyse compressor vibrations 

 

 

Hydraulic circuit: 

Check for any water leakage 

 

 

Check hydraulic connections 

 

 

Check the pressure at the exchangers water inlet 

 

 

Clean the water filter 

 

 

Check the glycol concentration 

 

 

Check the water flow rate 

 

 

BPHE

Check the cleaning of the 

BPHE

 

 

 

Notes: 

1.  Monthly activities include all the weekly ones. 
2.  The annual (or early season) activities include all weekly and monthly activities. 
3.  Daily reading of the operating values of the unit allows maintaining high observational standards. 
4.  Check for any dissolved metals. 
5.  Clean condenser banks with clean water and water heat exchangers with appropriate chemicals. Particles and fibres could clog up the exchangers, 

especially  for  water  exchangers  pay  attention  if  water  rich  in  calcium  carbonate  is  used.  An  increase  in  pressure  drops  or  a  decrease  in  thermal 

Содержание EWLQ025KCW1N

Страница 1: ...N EWLQ025KCW1N EWLQ033KCW1N EWLQ049KCW1N EWLQ064KCW1N REV 01 Date 07 2022 Supersedes D EIMHP01601 22_00EN Installation Operation and Maintenance Manual D EIMHP01601 22_01EN CONDENSERLESS WATER COOLED...

Страница 2: ...ance 19 13 2 Electrical Installation 19 13 3 Service and limited warranty 20 14 BEFORE STARTING 23 List of tables Table 1 Technical specifications 1 4 Table 2 Electrical specifications 1 4 Table 3 Fla...

Страница 3: ...lt in electric shock short circuit leaks fire or other damage to the equipment Be sure only to use accessories optional equipment and spare parts made by Daikin which are specifically designed for use...

Страница 4: ...shops in light industry and on farms or for commercial use by lay persons Sound pressure level is less than 70 dB A Table 1 Technical specifications 1 Model EWLQ 014 025 033 Dimensions HxWxD mm 600x6...

Страница 5: ...ater temperature kit Master slave water temperature kit Modem for Daikin On Site 1 2 Features Glycol application for chilled water temperature down to 10 C Voltage free contacts general operation alar...

Страница 6: ...26 2 OPERATION RANGE Figure 1 Operation range EWLQ014 033KC Figure 2 EWLQ049 064KC ELWT Evaporator leaving water temperature Tc Saturated condensing temperature 1 Operation with water 2 Operation with...

Страница 7: ...10 Evaporator leaving water temperature sensor 11 Freeze up sensor 12 Digital Controller and display 13 Power supply intake 14 Ball valve field installed 15 Water filter field installed 16 Air purge v...

Страница 8: ...D EIMHP01601 22_01EN 8 26 Please fill in with indelible ink the total refrigerant charge 1 GWP global warming potential...

Страница 9: ...ical specifications the pipe thickness of the refrigerant piping must comply with relevant local and national regulations For R410A the design pressure is 4 17 MPa 3 In case the required pipe sizes in...

Страница 10: ...ondenser less unit is installed below the condensing unit the following can occur when the unit stops oil will return to the discharge side of the compressor When starting the unit this can cause liqu...

Страница 11: ...15 8 19 1 97 110 N m 22 9 23 3 When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly Figure 5 Conne...

Страница 12: ...he sealed area 4 of the body Tighten the cap firmly Figure 7 Charging the unit NOTES Use a charging hose with push rod when using the service port 5 Make sure to keep stop valve open during operation...

Страница 13: ...rge until the additional 10 refrigerant charge weight The unit must have time to stabilize which means that this charging must be done in a smooth way Take care for contamination of the remote condens...

Страница 14: ...ger 2 Drain traps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance or in case of shut down 3 Anti vibration systems in all water piping co...

Страница 15: ...moving dirt from the water to prevent damage to the unit or malfunctioning of the evaporator 5 The water filter must be cleaned on a regular base Table 5 Water quality specification DAE Water quality...

Страница 16: ...max 135 C discharge pipe it must be insulated thoroughly A minimum of insulation to protect the liquid pipe from damage is advisable 10 5 Antifreeze protection for BPHE and recovery exchangers If the...

Страница 17: ...h phase and an earth leak detector Recommended fuses are mentioned on the wiring diagram supplied with the unit Switch off the main isolator switch before making any connections switch off the circuit...

Страница 18: ...to keep this equipment in good working order However during operation and maintenance it is essential to observe the following instructions Do not allow unauthorized and or unqualified personnel to a...

Страница 19: ...ocess cooling data centres etc Highly Aggressive Environments can be defined as the follows Industrial environment with possible concentration of fumes result of combustion and chemical process Coasta...

Страница 20: ...en solved 4 No safety device either mechanical electrical or electronic must be disabled or overridden 5 The water used for filling the water circuit must be clean and suitably treated A mechanical fi...

Страница 21: ...h concentration of airborne particles it might be necessary to clean the condenser bank more often 12 Units placed or stored in a Highly Aggressive Environment for long time without operation are stil...

Страница 22: ...porator Compressor 5 Evaporator BPHE S1 1 Evaporator Accumulator 6 Ball valve optional S1 2 Accumulator Compressor 7 Air purge valve optional W1 W3 Water inlet assembly Included kit but optional mount...

Страница 23: ...the table under Water charge flow and quality 5 The piping must be completely purged See also chapter Checking the water circuit 6 Connect the flow switch and pump contacts so that the unit can only...

Страница 24: ...D EIMHP01601 22_01EN 24 26 NOTES...

Страница 25: ...D EIMHP01601 22_01EN 25 26...

Страница 26: ...efer to the data communicated at the time of the order All the data and specifications contained herein are liable to change without notice Refer to the data communicated at the time of the order Daik...

Отзывы: