D-EIMHP01601-22_01EN 16/26     
 

pressures and temperatures of the system, it must also be resistant to the used glycol in the water. 

The external surface of the water pipes must be adequately protected against corrosion.

 

10.2 

Water charge, flow and quality 

To assure proper operation of the unit a minimum water volume is required in the system and the water flow through the 
evaporator must be within the operation range as specified in the table below.  

Table 6-Water flow operation range 

 

Minimum 

water volume (l) 

Minimum 

water flow 

Maximum 

water flow 

EWWQ014 

62 

31 l/min     75 l/min 

EWWQ025 

134 

53 l/min 

123 l/min 

EWWQ033 

155 

76 l/min     186 l/min 

EWWQ049 

205 

101 l/min 

247 l/min 

EWWQ064 

311 

152 l/min 

373 l/min 

10.3 

 Water piping insulation 

 

The complete water circuit, inclusive all piping, must be insulated to prevent condensation and  reduction of the cooling 
capacity. 

10.4 

 Refrigerant piping insulation 

 
To prevent burning injuries by accidental touching the hot (max 

135°C

) discharge pipe, it must be insulated thoroughly. 

A minimum of insulation to protect the liquid pipe from damage is advisable. 

10.5 

Antifreeze protection for BPHE and recovery exchangers 

 

If the exchangers are completely empty and cleaned with antifreeze solution, additional methods can be used against 
freezing. 
The following protection methods must be considered when designing the system as a whole: 
 

1.  continuous water flow circulation inside piping and exchangers. 

 

2.  addition of an appropriate amount of glycol inside the water circuit or, as alternative, an additional heat 

insulation and heating of exposed piping (internal and external to the unit).  

 

3.  if the unit does not work during the winter season, emptying and cleaning of the heat exchanger.  

It is the responsibility of the installer and/or of local maintenance personnel to ensure that described antifreeze meth ods 
are used. 
Make sure that appropriate antifreeze protection is always maintained. Failing to follow the instructions above could 
result in unit damage. 

 

 

Damage caused by freezing is excluded from the warranty, therefore Daikin Applied Europe S.p.A. 
declines all responsibility.

 

 

 

 

 

 

 

 

 

 

 

 

Содержание EWLQ025KCW1N

Страница 1: ...N EWLQ025KCW1N EWLQ033KCW1N EWLQ049KCW1N EWLQ064KCW1N REV 01 Date 07 2022 Supersedes D EIMHP01601 22_00EN Installation Operation and Maintenance Manual D EIMHP01601 22_01EN CONDENSERLESS WATER COOLED...

Страница 2: ...ance 19 13 2 Electrical Installation 19 13 3 Service and limited warranty 20 14 BEFORE STARTING 23 List of tables Table 1 Technical specifications 1 4 Table 2 Electrical specifications 1 4 Table 3 Fla...

Страница 3: ...lt in electric shock short circuit leaks fire or other damage to the equipment Be sure only to use accessories optional equipment and spare parts made by Daikin which are specifically designed for use...

Страница 4: ...shops in light industry and on farms or for commercial use by lay persons Sound pressure level is less than 70 dB A Table 1 Technical specifications 1 Model EWLQ 014 025 033 Dimensions HxWxD mm 600x6...

Страница 5: ...ater temperature kit Master slave water temperature kit Modem for Daikin On Site 1 2 Features Glycol application for chilled water temperature down to 10 C Voltage free contacts general operation alar...

Страница 6: ...26 2 OPERATION RANGE Figure 1 Operation range EWLQ014 033KC Figure 2 EWLQ049 064KC ELWT Evaporator leaving water temperature Tc Saturated condensing temperature 1 Operation with water 2 Operation with...

Страница 7: ...10 Evaporator leaving water temperature sensor 11 Freeze up sensor 12 Digital Controller and display 13 Power supply intake 14 Ball valve field installed 15 Water filter field installed 16 Air purge v...

Страница 8: ...D EIMHP01601 22_01EN 8 26 Please fill in with indelible ink the total refrigerant charge 1 GWP global warming potential...

Страница 9: ...ical specifications the pipe thickness of the refrigerant piping must comply with relevant local and national regulations For R410A the design pressure is 4 17 MPa 3 In case the required pipe sizes in...

Страница 10: ...ondenser less unit is installed below the condensing unit the following can occur when the unit stops oil will return to the discharge side of the compressor When starting the unit this can cause liqu...

Страница 11: ...15 8 19 1 97 110 N m 22 9 23 3 When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly Figure 5 Conne...

Страница 12: ...he sealed area 4 of the body Tighten the cap firmly Figure 7 Charging the unit NOTES Use a charging hose with push rod when using the service port 5 Make sure to keep stop valve open during operation...

Страница 13: ...rge until the additional 10 refrigerant charge weight The unit must have time to stabilize which means that this charging must be done in a smooth way Take care for contamination of the remote condens...

Страница 14: ...ger 2 Drain traps must be provided at all low points of the system to permit complete drainage of the circuit during maintenance or in case of shut down 3 Anti vibration systems in all water piping co...

Страница 15: ...moving dirt from the water to prevent damage to the unit or malfunctioning of the evaporator 5 The water filter must be cleaned on a regular base Table 5 Water quality specification DAE Water quality...

Страница 16: ...max 135 C discharge pipe it must be insulated thoroughly A minimum of insulation to protect the liquid pipe from damage is advisable 10 5 Antifreeze protection for BPHE and recovery exchangers If the...

Страница 17: ...h phase and an earth leak detector Recommended fuses are mentioned on the wiring diagram supplied with the unit Switch off the main isolator switch before making any connections switch off the circuit...

Страница 18: ...to keep this equipment in good working order However during operation and maintenance it is essential to observe the following instructions Do not allow unauthorized and or unqualified personnel to a...

Страница 19: ...ocess cooling data centres etc Highly Aggressive Environments can be defined as the follows Industrial environment with possible concentration of fumes result of combustion and chemical process Coasta...

Страница 20: ...en solved 4 No safety device either mechanical electrical or electronic must be disabled or overridden 5 The water used for filling the water circuit must be clean and suitably treated A mechanical fi...

Страница 21: ...h concentration of airborne particles it might be necessary to clean the condenser bank more often 12 Units placed or stored in a Highly Aggressive Environment for long time without operation are stil...

Страница 22: ...porator Compressor 5 Evaporator BPHE S1 1 Evaporator Accumulator 6 Ball valve optional S1 2 Accumulator Compressor 7 Air purge valve optional W1 W3 Water inlet assembly Included kit but optional mount...

Страница 23: ...the table under Water charge flow and quality 5 The piping must be completely purged See also chapter Checking the water circuit 6 Connect the flow switch and pump contacts so that the unit can only...

Страница 24: ...D EIMHP01601 22_01EN 24 26 NOTES...

Страница 25: ...D EIMHP01601 22_01EN 25 26...

Страница 26: ...efer to the data communicated at the time of the order All the data and specifications contained herein are liable to change without notice Refer to the data communicated at the time of the order Daik...

Отзывы: