5 Operation

Operation manual

13

ETVH/X16S(U)18+9W + ETBH/9W
Daikin Altherma 3 H HT F+W
4P644732-1 – 2021.02

1

Go to [2]: 

Main zone

 or [3]: 

Additional zone

.

Main zone

2

Additional zone

3

2

Adjust the desired leaving water temperature.

+

35

°C

2

a

b

Main zone

+

45

°C

3

a

b

Additional zone

a

 Actual leaving water temperature

b

 Desired leaving water temperature

5.7

Domestic hot water control

5.7.1

Reheat mode

In  reheat  mode  the  DHW  tank  continuously  heats  up  to  the
temperature  shown  on  the  home  screen  (example:  50°C)  when  the
temperature drops below a certain value.

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

Tt

T

t

DHW tank temperature

t

Time

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank

 > 

Heat up mode

 > 

Reheat only

.

INFORMATION

When  the  DHW  tank  mode  is  reheat,  the  risk  for  capacity
shortage  and  comfort  problem  is  significant.  In  case  of
frequent  reheat  operation,  space  heating/cooling  function
is regularly interrupted.

5.7.2

Scheduled mode

In scheduled mode the DHW tank produces hot water corresponding
to a schedule. The best time to allow the tank to produce hot water is
at night, because the space heating demand is lower.

Example: 

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

DHW tank temperature

t

Time

▪ Initially,  the  DHW  tank  temperature  is  the  same  as  the

temperature  of  the  domestic  water  entering  the  DHW  tank
(example: 

15°C

).

▪ At 00:00 the DHW tank is programmed to heat up the water to a

preset value (example: 

Comfort

 

= 60°C

).

▪ During  the  morning,  you  consume  hot  water  and  the  DHW  tank

temperature decreases.

▪ At 14:00 the DHW tank is programmed to heat up the water to a

preset value (example: 

Eco

 = 

50°C

). Hot water is available again.

▪ During  the  afternoon  and  evening,  you  consume  hot  water  again

and the DHW tank temperature decreases again.

▪ At 00:00 the next day, the cycle repeats.

5.7.3

Sch reheat mode

In  scheduled  +  reheat  mode,  the  domestic  hot  water  control  is  the
same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C

45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

Domestic hot water tank temperature

t

Time

5.7.4

Using DHW powerful operation

About powerful operation

Powerful operation

 allows the domestic hot water to be heated by

the  backup  heater  or  booster  heater.  Use  this  mode  on  days  when
there is more hot water usage than usual.

Содержание ETVH16S23EA6V

Страница 1: ...rma 3 H HT F W English Operation manual Daikin Altherma 3 H HT F W ETVH16S U 18EA6V ETVH16S U 23EA6V ETVH16S18EA9W ETVH16S23EA9W ETVX16S18EA6V ETVX16S23EA6V ETVX16S18EA9W ETVX16S23EA9W ETBH16EF6V ETBH...

Страница 2: ...onfiguration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user interface to ensure the best...

Страница 3: ...appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do...

Страница 4: ...or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the ro...

Страница 5: ...control the protection is NOT guaranteed NOTICE Water pipe freeze prevention Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling water pipe freeze prevention if e...

Страница 6: ...ing water temperature Possible actions on this screen Go through the temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information se...

Страница 7: ...user interface MMI This requires a correct config file on the USB memory stick Export the current settings i e field settings MMI EEPROM settings schedule timers from the user interface MMI to the USB...

Страница 8: ...5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Acti...

Страница 9: ...y Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy...

Страница 10: ...erature 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leavin...

Страница 11: ...ating cooling operation ON b Space heating cooling operation OFF Tank heating operation 1 6 bar 55 21 35 45 c 1 6 bar 55 21 35 45 d c Tank heating operation ON d Tank heating operation OFF 5 4 2 To tu...

Страница 12: ...one of the following options Heating Only heating mode Cooling Only cooling mode Automatic The operation mode changes automatically between heating and cooling based on the outdoor temperature Restric...

Страница 13: ...to produce hot water is at night because the space heating demand is lower Example t 60 C 00 00 07 00 50 C 15 C 40 C 14 00 21 00 1 2 3 4 5 Tt Tt DHW tank temperature t Time Initially the DHW tank temp...

Страница 14: ...temperature control is active you can program the main zone schedule instead 1 Go to the schedule 2 optional Clear the content of the whole week schedule or the content of a selected day schedule 3 Pr...

Страница 15: ...each character of the schedule name 4 To name the current schedule browse through the character list and confirm the selected character The schedule name can contain up to 15 characters 5 Confirm the...

Страница 16: ...erature Go to the next temperature Confirm changes and proceed 5 9 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently incr...

Страница 17: ...g 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional zone Cooling 3 6 Additional zone Cooling WD curve Zone Go to Tank Restriction Only available to...

Страница 18: ...on on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value...

Страница 19: ...er production When Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioni...

Страница 20: ...em Indoor unit type read only Backup heater type 9 3 1 read only Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 Glycol Filled system overview field setting E 0D Booster heater capacity 9 4...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...4P644732 1 2021 02 Copyright 2021 Daikin 4P644732 1 0000000O Verantwortung f r Energie und Umwelt...

Отзывы: