8 Troubleshooting

Operation manual

19

ETVH/X16S(U)18+9W + ETBH/9W
Daikin Altherma 3 H HT F+W
4P644732-1 – 2021.02

8.3

Symptom: You are feeling too cold
(hot) in your living room

Possible cause

Corrective action

The desired room temperature is
too low (high).

Increase (decrease) the desired
room temperature. See 

"5.6.2 To

change the desired room
temperature"

 [

4

 12].

If the problem recurs daily, do
one of the following:

▪ Increase  (decrease)  the  room

temperature  preset  value.  See
the user reference guide.

▪ Adjust  the  room  temperature

schedule.  See 

"5.8  Schedule

screen: Example"

 [

4

 14].

The desired room temperature
cannot be reached.

Increase the desired leaving
water temperature in accordance
with the heat emitter type. See

"5.6.3 To change the desired
leaving water temperature"

 [

4

 12].

The weather-dependent curve is
set incorrectly.

Adjust the weather-dependent
curve. See 

"5.9 Weather-

dependent curve"

 [

4

 15].

8.4

Symptom: The water at the tap is
too cold

Possible cause

Corrective action

You ran out of domestic hot
water because of unusual high
consumption.

If you immediately need domestic
hot water, activate the DHW tank

Powerful operation

. However,

this consumes extra energy. See

"5.7.4 Using DHW powerful
operation"

 [

4

 13].

If the problems recurs daily, do
one of the following:

▪ Increase 

the 

DHW 

tank

temperature  preset  value.  See
the user reference guide.

▪ Adjust 

the 

DHW 

tank

temperature 

schedule.

Example: 

Program 

to

additionally 

heat 

up 

the

DHW  tank  to  a  preset  value
(

Eco  setpoint

  =  lower  tank

temperature)  during  the  day.
See 

"5.8  Schedule  screen:

Example"

 [

4

 14].

The desired DHW tank
temperature is too low.

8.5

Symptom: Heat pump failure

When  the  heat  pump  fails  to  operate,  the  backup  heater  and/or
booster heater can serve as an emergency heater. It then takes over
the heat load either automatically or by manual interaction.

▪ When 

Emergency

  is  set  to 

Automatic

  and  a  heat  pump  failure

occurs:

▪ For  ETVH/X:  The  backup  heater  automatically  takes  over  the

domestic hot water production and space heating.

▪ For  ETBH/X:  The  backup  heater  automatically  takes  over  the

heat load, and the booster heater in the optional tank takes over
the domestic hot water production.

▪ When 

Emergency

  is  set  to 

Manual

  and  a  heat  pump  failure

occurs, the domestic hot water heating and space heating stops.

To  manually  recover  it  via  the  user  interface,  go  to  the

Malfunctioning

  main  menu  screen  and  confirm  whether  the

backup heater and/or booster heater can take over the heat load
or not.

▪ Alternatively, when 

Emergency

 is set to:

auto  SH  reduced/DHW  on

,  space  heating  is  reduced  but

domestic hot water is still available.

auto  SH  reduced/DHW  off

,  space  heating  is  reduced  and

domestic hot water is NOT available.

auto  SH  normal/DHW  off

,  space  heating  operates  as

normally but domestic hot water is NOT available.

Similarly  as  in 

Manual

  mode,  the  unit  can  take  the  full  load  with

the backup heater and/or booster heater if the user activates this
via the 

Malfunctioning

 main menu screen.

When  the  heat  pump  fails, 

  or 

  will  appear  on  the  user

interface.

Possible cause

Corrective action

Heat pump is damaged.

See 

"8.1 To display the help text

in case of a malfunction"

 [

4

 18].

INFORMATION

When  the  backup  heater  or  booster  heater  takes  over  the
heat  load,  electricity  consumption  will  be  considerably
higher.

8.6

Symptom: The system is making
gurgling noises after
commissioning

Possible cause

Corrective action

There is air in the system.

Purge air from the system.

(a)

Incorrect hydraulic balance.

1

Perform  hydraulic  balancing
to  assure  that  the  flow  is
correctly 

distributed

between the emitters.

2

If  hydraulic  balancing  is  not
sufficient,  change  the  pump
limitation  settings  ([9-0D]
and [9-0E] if applicable).

Various malfunctions.

Check if 

 or 

 is displayed

on the home screen of the user
interface. See 

"8.1 To display the

help text in case of a
malfunction"

 [

4

 18] for more

information about the
malfunction.

(a)

We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:

WARNING

Air  purging  heat  emitters  or  collectors.

  Before  you

purge  air  from  heat  emitters  or  collectors,  check  if 

  or

 is displayed on the home screen of the user interface.

▪ If not, you can purge air immediately.

▪ If  yes,  make  sure  that  the  room  where  you  want  to

purge air is sufficiently ventilated. 

Reason:

 Refrigerant

might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.

Содержание ETVH16S23EA6V

Страница 1: ...rma 3 H HT F W English Operation manual Daikin Altherma 3 H HT F W ETVH16S U 18EA6V ETVH16S U 23EA6V ETVH16S18EA9W ETVH16S23EA9W ETVX16S18EA6V ETVX16S23EA6V ETVX16S18EA9W ETVX16S23EA9W ETBH16EF6V ETBH...

Страница 2: ...onfiguration wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user interface to ensure the best...

Страница 3: ...appliance Cleaning and user maintenance SHALL NOT be made by children without supervision WARNING To prevent electrical shocks or fire Do NOT rinse the unit Do NOT operate the unit with wet hands Do...

Страница 4: ...or collectors Before you purge air from heat emitters or collectors check if or is displayed on the home screen of the user interface If not you can purge air immediately If yes make sure that the ro...

Страница 5: ...control the protection is NOT guaranteed NOTICE Water pipe freeze prevention Even if you turn OFF space heating cooling operation C 2 Operation Space heating cooling water pipe freeze prevention if e...

Страница 6: ...ing water temperature Possible actions on this screen Go through the temperatures Change the temperature Go to the next temperature Confirm changes and proceed More information For more information se...

Страница 7: ...user interface MMI This requires a correct config file on the USB memory stick Export the current settings i e field settings MMI EEPROM settings schedule timers from the user interface MMI to the USB...

Страница 8: ...5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 7 2 Time date Hours Minutes Year Month Day Daylight savings time Format 7 3 Holiday Activation From Till 7 4 Quiet Acti...

Страница 9: ...y Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available via solar panels or smart grid e2 Smart energy...

Страница 10: ...erature 2 Main zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leavin...

Страница 11: ...ating cooling operation ON b Space heating cooling operation OFF Tank heating operation 1 6 bar 55 21 35 45 c 1 6 bar 55 21 35 45 d c Tank heating operation ON d Tank heating operation OFF 5 4 2 To tu...

Страница 12: ...one of the following options Heating Only heating mode Cooling Only cooling mode Automatic The operation mode changes automatically between heating and cooling based on the outdoor temperature Restric...

Страница 13: ...to produce hot water is at night because the space heating demand is lower Example t 60 C 00 00 07 00 50 C 15 C 40 C 14 00 21 00 1 2 3 4 5 Tt Tt DHW tank temperature t Time Initially the DHW tank temp...

Страница 14: ...temperature control is active you can program the main zone schedule instead 1 Go to the schedule 2 optional Clear the content of the whole week schedule or the content of a selected day schedule 3 Pr...

Страница 15: ...each character of the schedule name 4 To name the current schedule browse through the character list and confirm the selected character The schedule name can contain up to 15 characters 5 Confirm the...

Страница 16: ...erature Go to the next temperature Confirm changes and proceed 5 9 3 Slope offset curve Slope and offset Define the weather dependent curve by its slope and offset Change the slope to differently incr...

Страница 17: ...g 2 6 Main zone Cooling WD curve Additional zone Heating 3 5 Additional zone Heating WD curve Additional zone Cooling 3 6 Additional zone Cooling WD curve Zone Go to Tank Restriction Only available to...

Страница 18: ...on on fluorinated greenhouse gases requires that the refrigerant charge of the unit is indicated both in weight and CO2 equivalent Formula to calculate the quantity in CO2 equivalent tonnes GWP value...

Страница 19: ...er production When Emergency is set to Manual and a heat pump failure occurs the domestic hot water heating and space heating stops To manually recover it via the user interface go to the Malfunctioni...

Страница 20: ...em Indoor unit type read only Backup heater type 9 3 1 read only Domestic hot water 9 2 1 Emergency 9 5 Number of zones 4 4 Glycol Filled system overview field setting E 0D Booster heater capacity 9 4...

Страница 21: ......

Страница 22: ......

Страница 23: ......

Страница 24: ...4P644732 1 2021 02 Copyright 2021 Daikin 4P644732 1 0000000O Verantwortung f r Energie und Umwelt...

Отзывы: