9/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[3-00]
R/W
0: No
1: Yes
9.I
[3-01]
0
9.I
[3-02]
1
9.I
[3-03]
4
9.I
[3-04]
2
9.I
[3-05]
1
9.I
[3-06]
R/W
18~30°C, step: 1°C
30°C
9.I
[3-07]
R/W
12~18°C, step: 1°C
12°C
9.I
[3-08]
R/W
25~35°C, step: 1°C
35°C
9.I
[3-09]
R/W
15~25°C, step: 0,5 1°C
15°C
9.I
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
9.I
[4-01]
R/W
0: None
1: BSH
2: BUH
9.I
[4-02]
R/W
14~35°C, step: 1°C
35°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
R/W
0: Intermittent
1: Continuous
2: Off
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.I
[4-07]
6
9.I
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
9.I
[4-09]
R/W
0: Current
1: Power
9.I
[4-0A]
R/W
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: No
1: Yes
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
9.I
[5-0E]
1
9.I
[6-00]
R/W
2~40°C, step: 1°C
8°C
9.I
[6-01]
R/W
0~10°C, step: 1°C
2°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
3kW (*3)
0kW (*4)
9.I
[6-03]
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
9.I
[6-04]
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
9.I
[6-05]
0
9.I
[6-06]
0
9.I
[6-07]
0
9.I
[6-08]
R/W
2~20°C, step: 1°C
10°C
--
--
What is the hysteresis to be used in reheat mode?
The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
--
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Backup heater voltage
--
Space heating priority temperature.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
--
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
What is the equilibrium temperature for the building?
Space heating priority.
--
Emergency
--
Which power limitation mode is required on the system?
Which power limitation type is required?
Backup heater configuration
What is the minimum desired room temperature in cooling?
What is the BUH operation mode?
Which electric heater has priority?
Below which outdoor temperature is heating allowed?
Operation permission of the booster heater.
Water pipe freeze prevention
--
--
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
Is auto restart of the unit allowed?
--
--
(*1) *6V_(*2) *9W_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*
(#) Only applicable in Swedish language.
4P644734-1 - 2021.02