10
|
Configuration
Installer reference guide
193
EPRA14~W1 + ETVH/9W
Daikin Altherma 3 H HT F
4P644737-1 – 2021.02
INFORMATION
Only for systems with integrated domestic hot water tank: If backup heater
operation during space heating needs to be limited but can be allowed for domestic
hot water operation, then set [4‑00] to 2.
Emergency
Emergency
When the heat pump fails to operate, the backup heater can serve as an
emergency heater. It then takes over the heat load either automatically or by
manual interaction.
▪
When
Emergency
is set to
Automatic
and a heat pump failure occurs, the
backup heater automatically takes over the domestic hot water production and
space heating.
▪
When
Emergency
is set to
Manual
and a heat pump failure occurs, the
domestic hot water heating and space heating stops.
To manually recover it via the user interface, go to the
Malfunctioning
main
menu screen and confirm whether the backup heater can take over the heat load
or not.
▪
Alternatively, when
Emergency
is set to:
-
auto SH reduced/DHW on
, space heating is reduced but domestic hot
water is still available.
-
auto SH reduced/DHW off
, space heating is reduced and domestic hot
water is NOT available.
-
auto SH normal/DHW off
, space heating operates as normally but
domestic hot water is NOT available.
Similarly as in
Manual
mode, the unit can take the full load with the backup
heater if the user activates this via the
Malfunctioning
main menu screen.
To keep energy consumption low, we recommend to set
Emergency
to
auto SH
reduced/DHW off
if the house is unattended for longer periods.
#
Code
Description
[9.5.1]
[4-06]
▪
0:
Manual
▪
1:
Automatic
▪
2:
auto SH reduced/DHW on
▪
3:
auto SH reduced/DHW off
▪
4:
auto SH normal/DHW off
INFORMATION
The auto emergency setting can be set in the menu structure of the user interface
only.
INFORMATION
If a heat pump failure occurs and
Emergency
is set to
Manual
, the room frost
protection function, the underfloor heating screed dryout function, and the water
pipe antifreeze function will remain active even if the user does NOT confirm
emergency operation.