Daikin ERLQ006BAV39 Скачать руководство пользователя страница 8

Installation manual

6

ERLQ006~008BAV39

Outdoor unit for air to water heat pump

4PW63277-1 – 07.2010

5

Check that the flaring is properly made.

Connecting the refrigerant piping to the outdoor unit

1

When connecting the flare nut, coat the flare inner surface with
ether oil or with ester oil and initially tighten 3 or 4 turns by hand
before tightening firmly.

2

When loosening a flare nut, always use two wrenches together.

When connecting the piping, always use a spanner and torque
wrench together to tighten the flare nut to prevent nut cracking
and leaks.

Refrigerant piping work

Pipe handling guidelines

Protect the open end of the pipe against dust and moisture.

All pipe bends should be as gentle as possible. Use a pipe
bender for bending.
Bending radius should be 30 to 40 mm or larger.

Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the
following:

Insulation material: polyethylene foam
Heat transfer rate: 0.041 to 0.052 W/mK (0.035 to 0.045
kcal/mh°C)
Refrigerant gas pipe's surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this
temperature.

Be sure to insulate both the gas and liquid piping and to provide
insulation dimensions as below.

Use separate thermal insulation pipes for gas and liquid
refrigerant pipes.

Purging air and checking gas leakage

When all piping work is completed and the outdoor unit is connected
to the indoor unit, it is necessary to purge the air and check for gas
leakage.

If using additional refrigerant, perform air purging from the
refrigerant pipes and indoor unit using a vacuum pump, then
charge additional refrigerant.

Use a hexagonal wrench (4 mm) to operate the stop valve rod.

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

CAUTION

Do not use mineral oil on flared part.
Mineral oil getting into the system would reduce the
lifetime of the units.

Never use piping which has been used for previous
installations. Only use parts which are delivered with
the unit.

Do never install a drier to this R410A unit in order to
guarantee its lifetime. The drying material may
dissolve and damage the system.

Incomplete flaring may cause refrigerant gas leakage.

Flare nut

Flare nut tightening torque

Ø6.4 mm (1/4")

15~17 N•m

Ø15.9 mm (5/8")

63~75 N•m

Valve cap tightening torque

Valve cap

Gas pipe

Ø6.4 mm (1/4")

21.6~27.4 N•m

Ø15.9 mm (5/8")

44.1~53.9 N•m

Service port cap tightening torque

10.8~14.7 N•m

1

2

3

1

Flare's inner surface must be flaw-free.

2

The pipe end must be evenly flared in a 
perfect circle.

3

Make sure that the flare nut is fitted.

1

2

3

4

1

Torque wrench

2

Spanner

3

Piping union

4

Flare nut

Pipe size

Pipe insulation

Outer 

diameter

Thickness

Inner diameter

Thickness

6.4 mm (1/4")

0.8 mm

8-10 mm

10 mm

15.9 mm (5/8")

1.0 mm

16-20 mm

13 mm

WARNING

Do not mix any substance other than the specified
refrigerant (R410A) into the refrigeration cycle.

When refrigerant gas leaks occur, ventilate the room
as soon and as much as possible.

R410A, as well as other refrigerants, should always
be recovered and never be released directly into the
environment.

CAUTION

Use a vacuum pump for R410A exclusively. Using the
same vacuum pump for different refrigerants may damage
the vacuum pump or the unit.

5

6

1

2

4

3

1

Gas pipe

2

Inter-unit wiring

3

Liquid pipe

4

Liquid pipe insulation

5

Finishing tape

6

Gas pipe insulation

Содержание ERLQ006BAV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BAV39 ERLQ007BAV39 ERLQ008BAV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...esult in water leakage electric shocks or re Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or re Consult your lo...

Страница 4: ...dedicated power circuit Failure to do so may cause abnormal heat electric shock or re During pump down operation stop the compressor before removing the refrigerant piping If the compressor is still...

Страница 5: ...amage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction wo...

Страница 6: ...structions described below Construct a large canopy Construct a pedestal Install the unit high enough off the ground to prevent burying in snow CAUTION Piping and other pressure containing parts shall...

Страница 7: ...ot freeze causing blockage by ice accumulation Avoid drain water owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery Flaring the pipe end To...

Страница 8: ...um pump then charge additional refrigerant Use a hexagonal wrench 4 mm to operate the stop valve rod All eld piping must be installed by a licensed refrigeration technician and must comply with releva...

Страница 9: ...e Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please ll in with indelible ink the factory refrigerant charge of the prod...

Страница 10: ...nning it before the piping is ready will break the compressor WARNING All components procured on the site and all electric construction shall comply with the applicable local and national regulations...

Страница 11: ...indoor unit and outdoor unit when wire length exceeds 10 m use 2 5 mm wires instead of 1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safety break...

Страница 12: ...m the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the s...

Страница 13: ...y out any service mode operation DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legisl...

Страница 14: ...NOTES...

Страница 15: ...NOTES...

Страница 16: ...4PW63277 1 07 2010 Copyright 2010 Daikin...