Installation manual

4

ERLQ006~008BAV39

Outdoor unit for air to water heat pump

4PW63277-1 – 07.2010

Selecting a location in cold climates

To  prevent exposure to wind, install the outdoor unit with its
suction side facing the wall.

Never install the outdoor unit at a site where the suction side
may be exposed directly to wind.

To  prevent exposure to wind, install a baffle plate on the air
discharge side of the outdoor unit.

In heavy snowfall areas it is very important to select an
installation site where the snow will not affect the unit. If lateral
snowfall is possible, make sure that the heat exchanger coil is
not affected by the snow (if necessary construct a lateral
canopy).

Refrigerant piping specifications

Installing near a wall or obstacle

Where a wall or other obstacle is in the path of the outdoor unit
air intake or exhaust airflow, follow the installation guidelines
below.

For any of the installation patterns below, the wall height on the
exhaust side should be 1200 mm or less.

Wall facing one side (unit: mm)

Walls facing two sides (unit: mm)

Walls facing three sides (unit: mm)

CAUTION

When operating the outdoor unit in a low outdoor ambient
temperature, be sure to follow the instructions described
below.

Construct a large canopy.

Construct a pedestal.

Install the unit high enough off the ground 
to prevent burying in snow.

CAUTION

Piping and other pressure containing parts shall
comply with the applicable national and international
regulations and shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for
refrigerant.

Installation shall be done by a licensed refrigerant
technician, the choice of materials and installation
shall comply with national and international
regulations. In Europe the EN378 is the application
standard that shall be used.

To persons in charge of piping work:

Be sure to open the stop valve after piping installing
and vacuming is complete. (Running the system with
the valve closed may break the compressor.)

It is forbidden to discharge refrigerant into the
atmosphere. Collect the refrigerant in accordance with
the freon collection and destruction law.

Refrigerant piping specifications

Maximum allowable piping length 
between outdoor unit and indoor unit

30 m

Minimum required piping length 
between outdoor unit and indoor unit

3 m

Maximum allowable height difference 
between outdoor unit and indoor unit

20 m

Additional refrigerant required for 
refrigerant pipe exceeding 10 m in 
length

20 g/m

Gas pipe - outer diameter

15.9 mm (5/8")

Liquid pipe - outer diameter

6.4 mm (1/4")

>100

>350

1200

>50

>50

>350

>100

>100

>350

>50

Содержание ERLQ006BAV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BAV39 ERLQ007BAV39 ERLQ008BAV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...esult in water leakage electric shocks or re Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or re Consult your lo...

Страница 4: ...dedicated power circuit Failure to do so may cause abnormal heat electric shock or re During pump down operation stop the compressor before removing the refrigerant piping If the compressor is still...

Страница 5: ...amage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction wo...

Страница 6: ...structions described below Construct a large canopy Construct a pedestal Install the unit high enough off the ground to prevent burying in snow CAUTION Piping and other pressure containing parts shall...

Страница 7: ...ot freeze causing blockage by ice accumulation Avoid drain water owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery Flaring the pipe end To...

Страница 8: ...um pump then charge additional refrigerant Use a hexagonal wrench 4 mm to operate the stop valve rod All eld piping must be installed by a licensed refrigeration technician and must comply with releva...

Страница 9: ...e Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please ll in with indelible ink the factory refrigerant charge of the prod...

Страница 10: ...nning it before the piping is ready will break the compressor WARNING All components procured on the site and all electric construction shall comply with the applicable local and national regulations...

Страница 11: ...indoor unit and outdoor unit when wire length exceeds 10 m use 2 5 mm wires instead of 1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safety break...

Страница 12: ...m the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the s...

Страница 13: ...y out any service mode operation DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legisl...

Страница 14: ...NOTES...

Страница 15: ...NOTES...

Страница 16: ...4PW63277 1 07 2010 Copyright 2010 Daikin...

Отзывы: