ERLQ006~008BAV39

Outdoor unit for air to water heat pump

4PW63277-1 – 07.2010

Installation manual

3

M

ODEL

ERLQ units include special equipment (insulation, bottom plate
heater,...) to ensure good operation in areas where low ambient
temperature can occur together with high humidity conditions.

A

CCESSORIES

Accessories supplied with the outdoor unit:

Possible options

I

NSTALLATION

 

GUIDELINES

Precautions for selecting the location

The equipment is not intended for use in a potentially explosive
atmosphere.

Choose a place solid enough to bear the weight and vibration of
the unit, where the operation noise will not be amplified.

Choose a location where the hot air discharged from the unit or
the operation noise will not cause a nuisance to the neighbours
of the user.

Avoid places near a bedroom and the like, so that the operation
noise will cause no trouble.

There must be sufficient space for carrying the unit into and out
of the site.

There must be sufficient space for air passage and no
obstructions around the air inlet and the air outlet.

The site must be free from the possibility of flammable gas
leakage in a nearby place.

Locate the unit so that the noise and the discharged hot air will
not annoy the neighbours.

Install units, power cords and inter-unit cables at least 3 m away
from television and radio sets. This is to prevent interference to
images and sounds.

Depending on radio wave conditions, electromagnetic
interference may still occur even if installed more than 3 m away.

In coastal areas or other places with salty atmosphere of sulfate
gas, corrosion may shorten the life of the outdoor unit.

Since drain flows out of the outdoor unit, do not place anything
under the unit which must be kept away from moisture.

1

Select an installation site where the following conditions are
satisfied and that meets with your customer's approval.

-

Places which are well-ventilated.

-

Places where the unit does not bother next-door neighbours.

-

Safe places which can withstand the unit's weight and 
vibration and where the unit can be installed level.

-

Places where there is no possibility of flammable gas or 
product leak.

-

The equipment is not intended for use in a potentially 
explosive atmosphere.

-

Places where servicing space can be well ensured.

-

Places where the indoor and outdoor units' piping and wiring 
lengths come within the allowable ranges.

-

Places where water leaking from the unit cannot cause 
damage to the location (e.g. in case of a blocked drain pipe).

-

Places where the rain can be avoided as much as possible.

-

Do not install the unit in places often used as work place.
In case of construction works (e.g. grinding works) where a
lot of dust is created, the unit must be covered.

-

Do not place any objects or equipment on top of the unit (top 
plate).

-

Do not climb, sit or stand on top of the unit,

-

Be sure that sufficient precautions are taken, in accordance 
with relevant local and national regulations, in case of 
refrigerant leakage.

2

When installing the unit in a place exposed to strong wind, pay
special attention to the following.

Strong winds of 5 m/sec or more blowing against the outdoor
unit's air outlet causes short circuit (suction of discharge air),
and this may have the following consequences:
-

Deterioration of the operational capacity.

-

Frequent frost acceleration in heating operation.

-

Disruption of operation due to rise of high pressure.

-

When a strong wind blows continuously on the face of the 
unit, the fan can start rotating very fast until it breaks.

Refer to the figures for installation of this unit in a place where
the wind direction can be foreseen.

3

Prepare a water drainage channel around the foundation, to
drain waste water from around the unit.

4

If the water drainage of the unit is not easy, please build up the
unit on a foundation of concrete blocks, etc. (the height of the
foundation should be maximum 150 mm).

5

If you install the unit on a frame, please install a waterproof plate
within 150 mm of the underside of the unit in order to prevent the
invasion of water from the lower direction.

6

When installing the unit in a place frequently exposed to snow,
pay special attention to elevate the foundation as high as
possible.

7

If you install the unit on a building frame,
please install a waterproof plate (field
supply) (within 150 mm of the underside of
the unit) in order to avoid the drainwater
dripping. (See figure).

NOTE

An ERLQ0*

BA

 outdoor unit can only be connected to

an EKHBH/X008

B*

 indoor unit (bottom plate heater at

outdoor unit has to be controlled by indoor unit).

Installation manual

1x

Fluorinated greenhouse gases label

1x

Multilingual fluorinated greenhouse 
gases label

1x

Bottom plate heater

ERLQ_V3

Standard (125 W)

WARNING

Make sure to provide for adequate measures in order
to prevent that the outdoor unit be used as a shelter
by small animals.

Small animals making contact with electrical parts can
cause malfunctions, smoke or fire. Please instruct the
customer to keep the area around the unit clean.

NOTE

Units cannot be installed hanging from ceiling or
stacked.

Содержание ERLQ006BAV39

Страница 1: ...INSTALLATION MANUAL ERLQ006BAV39 ERLQ007BAV39 ERLQ008BAV39 Outdoor unit for air to water heat pump...

Страница 2: ...stig de bepalingen van 05 siguiendo las disposiciones de 06 secondo le prescrizioni per 07 v v v 08 de acordo com o previsto em 09 10 under iagttagelse af bestemmelserne i 11 enligt villkoren i 12 git...

Страница 3: ...esult in water leakage electric shocks or re Perform installation work in accordance with this installation manual Improper installation may lead to water leakage electric shocks or re Consult your lo...

Страница 4: ...dedicated power circuit Failure to do so may cause abnormal heat electric shock or re During pump down operation stop the compressor before removing the refrigerant piping If the compressor is still...

Страница 5: ...amage to the location e g in case of a blocked drain pipe Places where the rain can be avoided as much as possible Do not install the unit in places often used as work place In case of construction wo...

Страница 6: ...structions described below Construct a large canopy Construct a pedestal Install the unit high enough off the ground to prevent burying in snow CAUTION Piping and other pressure containing parts shall...

Страница 7: ...ot freeze causing blockage by ice accumulation Avoid drain water owing over the footpath so that in case of ambient freezing temperatures the footpath does not become slippery Flaring the pipe end To...

Страница 8: ...um pump then charge additional refrigerant Use a hexagonal wrench 4 mm to operate the stop valve rod All eld piping must be installed by a licensed refrigeration technician and must comply with releva...

Страница 9: ...e Kyoto Protocol Do not vent gases into the atmosphere Refrigerant type R410A GWP 1 value 1975 1 GWP global warming potential Please ll in with indelible ink the factory refrigerant charge of the prod...

Страница 10: ...nning it before the piping is ready will break the compressor WARNING All components procured on the site and all electric construction shall comply with the applicable local and national regulations...

Страница 11: ...indoor unit and outdoor unit when wire length exceeds 10 m use 2 5 mm wires instead of 1 5 mm wires 2 Power supply cable refer to the unit nameplate for maximum running current 3 Earth 4 Safety break...

Страница 12: ...m the compressor that needs elapse of a 50 hours run in period before reaching smooth operation and stable power consumption NOTE The unit requires a small amount of power in its standby mode If the s...

Страница 13: ...y out any service mode operation DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legisl...

Страница 14: ...NOTES...

Страница 15: ...NOTES...

Страница 16: ...4PW63277 1 07 2010 Copyright 2010 Daikin...

Отзывы: