9
|
Electrical installation
Installer reference guide
126
ERLA11~16D + EBVH16SU23D
Daikin Altherma 3 R F
4P655196-1A – 2022.05
Connecting to the
frame
When cables are routed from the unit, a protection
sleeve for the conduits (PG insertions) can be
inserted at the knockout hole.
When you do not use a wire conduit, protect the
wires with vinyl tubes to prevent the edge of the
knockout hole from cutting the wires.
a
b
A
B
c d
e
A
Inside of the outdoor unit
B
Outside of the outdoor unit
a
Wire
b
Bush
c
Nut
d
Frame
e
Hose
NOTICE
Precautions when making knockout holes:
▪
Avoid damaging the casing and underlying piping.
▪
After making the knockout holes, we recommend to remove the burrs and paint
the edges and areas around the edges using repair paint to prevent rusting.
▪
When passing electrical wiring through the knockout holes, wrap the wiring with
protective tape to prevent damage.
7
Reattach the service cover. See
"7.2.3 To close the outdoor unit"
79].
8
Connect an earth leakage circuit breaker and fuse to the power supply line.
9.3 Connections to the indoor unit
Item
Description
Power supply (main)
"9.3.1 To connect the main power
129].
Power supply (backup
heater)
"9.3.2 To connect the backup heater power
131].
Shut-off valve
"9.3.3 To connect the shut-off valve"
Electricity meters
"9.3.4 To connect the electricity meters"
Domestic hot water pump
"9.3.5 To connect the domestic hot water
135].
Alarm output
"9.3.6 To connect the alarm output"
136].
Space cooling/heating
operation control
"9.3.7 To connect the space cooling/heating ON/
137].