11
|
Configuration
Installer reference guide
208
ERGA04~V3A+V37 + EHSH/X(B)04+08P30+50EF
Daikin Altherma 3 R ECH₂O
4P678716-1A – 2022.07
INFORMATION
This does not reset the configuration settings and field settings of the indoor unit.
#
Code
Description
[8.A]
N/A
Reset the MMI EEPROM
to factory default
Piping diagram
The piping diagram screen visualizes various real-time sensor and actuator
information within the piping layout. This allows a check of the system at one
glance.
R3T = 3
R4T = 3
3
3
P = 3
V = 3
R1T = 3
R2T = 3
R7T = 3
R5T = 3
R6T = 3
a1
a3
a4
b1
2
a
3
b
b5
b4
c1
c2
c3
c4
b2
C5
c7
C6
c8 c9
Item
Description
a
Energy sources
a1
Heat pump compressor is operating.
a2
Solar energy is available.
a3
Backup heater is activated.
a4
Boiler is activated
b
Actuator status
b1
Pump is running.
b2
Heat pump is operating.
b3
Backup heater is activated.
b4
Tank valve is turning. Valve position [%].
b5
Bypass valve is turning. Valve position [%].