Installation manual

1

4PW17562-1A

E EPIB6

Master/Slave int Power interface

The 

Master/Slave interface 

or 

Power interface 

must 

be installed to use microprocessor-based control panels 

on the whole range of units for models with a current 

consumption greater than 5 A.

The EPIMSA6 

Master/Slave interface 

is used for 

connecting up to 4 units in parallel to 1 controller 

FWEC(1,2,3)A. Up to 3 EPIMSA6 interfaces can be 

connected in parallel to 1 controller. The capacity of the 

EPIMSA6 contacts is 4 x 3 A.

The EPIB6  

Power interface 

permits to use the electronic 

remote controller FWEC(1,2,3)A on the whole range of 

units with a current consumption greater than 5 A. The 

capacity of the EPIB6  contacts is 16 A.

Neglecting the absolute requirement to install 

an additional interface (EPIB6  or EPIMSA6) to 

units with a current consumption greater than 

5  A  may  cause  fire  or  other  damage  to  the 

equipment.

Table below lists the maximum current of the whole 

range of units.

FWL/FWM/FWV

FWB

FWD

01

0.16 A

-

-

02

0.21 A

0.56 A

-

03

0.27 A

0.56 A

-

04

0.39 A

0.56 A

0.95 A

05

-

1.10 A

-

06

0.38 A

1.10 A

1.58 A

07

-

1.10 A

-

08

0.80 A

1.40 A

1.97 A

09

-

1.40 A

-

10

1.12 A

1.40 A

1.97 A

12

-

-

3.21 A

16

-

-

5.37 A

18

-

-

5.37 A

<=3 A

Master/Slave function is possible by installing the EPIMSA6.

>3 A

Installing EPIMSA6 you must install EPIB6.

>5 A

EPIB6  must be installed.

T

EchNical

 S

pEcificaTiONS

EPIMSA6

EPIB6 

Power supply

230 V

–15% +10% 50 Hz

Contacts at output

4x3A 250 V

1x16A 250 V

Operating temperature

0~40°C

Humidity limits (RH)

20~80% non-condensing

Protection rating

IP30

Container

105 x 90 x 70 mm

Weight

265 g

i

NSTallaTiON

 

n

All  field  wiring  and  components  must  be 

installed by a licensed electrician and must 

comply with relevant local and national 

regulations.

 

n

Before obtaining access to terminals, all 

power supply circuits must be interrupted.

 

n

The EPIMSA6 or EPIB6  interfaces are to be installed 

on a DIN guide, usually housed in the electric boards 

cabinet.

 

n

The overall dimensions of the EPIMSA6 and EPIB6  

interface are shown in figure 3.

 

n

Make the electrical connections with POWER OFF as 

indicated in the diagrams of figure 1+2 that show the 

following:

Figure 1:

 microprocessor-based cont 2x 

EPIMSA6 connected to 8 units.

Figure 2:

 connections of EPIB6 

Each unit requires a switch (IL) on the power supply line 

with a distance of at least 3 mm between the opening 

contacts, and a suitable safety fuse (F).

NOTE

Connect only one unit per EPIMSA6 or 

EPIB6  output.

EPIMSA6

EPIB6 

Master/Slave interface

Power interface

Installation manual

Содержание EPIB6

Страница 1: ...ve Interface d alimentation Français Manual de instalación Interfaz Unidad principal Unidad esclava Interfaz de alimentación Español Manuale d installazione Interfaccia master slave Interfaccia di alimentazione Italiano Installation manual English language Original Instructions All other language Translation of the Original Instruction Master Slave interface Power interface EPIMSA6 EPIB6 ...

Страница 2: ...7 28 30 29 1 31 32 34 33 3 4 2 1 3 23 24 26 25 20 19 21 22 27 28 30 29 31 32 34 33 23 24 26 25 M 1 RD BN GN BU YE GY BK WH 4 5 6 7 VC L N 1 2 3 VH 3 7 3 7 M 1 WH BK BU or GY RD 4 N L 7 6 5 M 1 WH BK BU RD 4 N L 7 6 5 M 1 M 1 M 1 M 1 M 1 WH BK BU RD RD BN GN BU YE GY BK WH WH BK BU RD WH BK BU RD WH BK BU or GY RD 4 N L 7 6 5 4 5 6 7 VC L N 1 2 3 VH 4 N L 7 6 5 4 N L 7 6 5 4 N L 7 6 5 14 L 15 L 16 ...

Страница 3: ...NOTES ...

Страница 4: ...97 A 12 3 21 A 16 5 37 A 18 5 37 A 3 A Master Slave function is possible by installing the EPIMSA6 3 A Installing EPIMSA6 you must install EPIB6 5 A EPIB6 must be installed Technical Specifications EPIMSA6 EPIB6 Power supply 230 V 15 10 50 Hz Contacts at output 4x3A 250 V 1x16A 250 V Operating temperature 0 40 C Humidity limits RH 20 80 non condensing Protection rating IP30 Container 105 x 90 x 70...

Страница 5: ...tor RD Red minimum speed VC Cold water valve VH Hot water valve WH White Common YE Yellow 3 7 3 out of 7 speeds Electrical connections to be made by the installer Figure 2 connections of EPIB6 A Power supply 230 V 1 50 Hz 14 15 phase 16 17 neutral B Connection line to control panel 1 fan motor common wire 2 minimum motor speed 3 medium motor speed 4 maximum motor speed C Connection line to motor 2...

Страница 6: ...r Slave Funktion ist möglich bei Installation von EPIMSA6 3 A Installieren EPIMSA6 müssen Sie EPIB6 installieren 5 A EPIB6 muss installiert werden Technische Spezifikationen EPIMSA6 EPIB6 Netzanschluss 230 V 15 10 50 Hz Kontakte am Ausgang 4x3A 250 V 1x16A 250 V Betriebstemperatur 0 40 C Feuchtigkeits begrenzungen RH 20 80 nicht kondensierend Schutznennleistung IP30 Behälter 105 x 90 x 70 mm Gewic...

Страница 7: ... VC Kaltwasserventil VH Heißwasserventil WH Weiß gemeinsam YE Gelb 3 7 3 von 7 Stufen Elektrische Anschlüsse müssen durch den Installateur erfolgen Abbildung 2 Anschlüsse von EPIB6 A Stromversorgung 230 V 1 50 Hz 14 15 Phase 16 17 neutral B Verbindungsleitung an das Bedienpult 1 Gemeinsames Kabel des Lüftermotors 2 Mindestdrehzahl des Motors 3 Mittlere Drehzahl des Motors 4 Maximale Drehzahl des M...

Страница 8: ...5 37 A 18 5 37 A 3 A La fonction maître esclave est possible en installant l EPIMSA6 3 A Installation EPIMSA6 vous devez installer EPIB6 5 A L EPIB6 doit être installé Spécifications Techniques EPIMSA6 EPIB6 Alimentation 230 V 15 10 50 Hz Contacts à la sortie 4x3A 250 V 1x16A 250 V Température de service 0 40 C Limites d humidité RH 20 80 nicht kondensierend Degré de protection IP30 Conteneur 105 ...

Страница 9: ...Vanne d eau froide VH Vanne d eau chaude WH Blanc Masse YE Jaune 3 7 3 vitesses sur 7 Connexions électriques à effectuer par l installateur Figure 2 connexions du EPIB6 A Alimentation électrique 230 V 1 50 Hz 14 15 phase 16 17 neutre B Fil de raccordement au panneau de commande 1 fil commun au moteur de ventilateur 2 vitesse minimale du moteur 3 vitesse moyenne du moteur 4 vitesse maximale du mote...

Страница 10: ...d principal Unidad esclava es posible instalando la EPIMSA6 3 A Instalación EPIMSA6 debe instalar EPIB6 5 A Debe instalarse EPIB6 Especificaciones Técnicas EPIMSA6 EPIB6 Alimentación eléctrica 230 V 15 10 50 Hz Contactos de salida 4x3A 250 V 1x16A 250 V Temperatura de funcionamiento 0 40 C Límites de humedad RH 20 80 sin condensación Grado de protección IP30 Contenedor 105 x 90 x 70 mm Peso 265 g ...

Страница 11: ... del ventilador RD Rojo velocidad mínima VC Válvula de agua fría VH Válvula de agua caliente WH Blanco común YE Amarillo 3 7 3 de 7 velocidades Conexiones eléctricas a realizar por el instalador Figura 2 conexiones de la EPIB6 A Alimentación 230 V 1 50 Hz 14 15 fase 16 17 neutro B Línea de conexión al panel de control 1 hilo común del motor de ventilador 2 mínima velocidad del motor 3 velocidad me...

Страница 12: ...IMSA6 è possibile disporre della funzione master slave 3 A Installando EPIMSA6 è necessario installare EPIB6 5 A È necessario installare EPIB6 Spacifiche tecniche EPIMSA6 EPIB6 Alimentazione 230 V 15 10 50 Hz Contatti in uscita 4x3A 250 V 1x16A 250 V Temperatura di funzionamento 0 40 C Limiti dell umidità RH 20 80 senza condensa Livello di protezione IP30 Contenitore 105 x 90 x 70 mm Peso 265 g In...

Страница 13: ... VC Valvola dell acqua fredda VH Valvola dell acqua calda WH Bianco comune YE Giallo 3 7 3 delle 7 velocità Collegamenti elettrici che devono essere eseguiti dall installatore Figura 2 collegamenti di EPIB6 A Alimentazione 230 V 1 50 Hz 14 15 fase 16 17 neutro B Linea di collegamento al pannello di controllo 1 filo comune del motore della ventola 2 velocità del motore minima 3 velocità del motore ...

Страница 14: ...NOTES ...

Страница 15: ...NOTES ...

Страница 16: ...4PW17562 1A Zandvoordestraat 300 B 8400 Oostende Belgium ...

Отзывы: