Installation manual
1
4PW17562-1A
E EPIB6
Master/Slave int Power interface
The
Master/Slave interface
or
Power interface
must
be installed to use microprocessor-based control panels
on the whole range of units for models with a current
consumption greater than 5 A.
The EPIMSA6
Master/Slave interface
is used for
connecting up to 4 units in parallel to 1 controller
FWEC(1,2,3)A. Up to 3 EPIMSA6 interfaces can be
connected in parallel to 1 controller. The capacity of the
EPIMSA6 contacts is 4 x 3 A.
The EPIB6
Power interface
permits to use the electronic
remote controller FWEC(1,2,3)A on the whole range of
units with a current consumption greater than 5 A. The
capacity of the EPIB6 contacts is 16 A.
Neglecting the absolute requirement to install
an additional interface (EPIB6 or EPIMSA6) to
units with a current consumption greater than
5 A may cause fire or other damage to the
equipment.
Table below lists the maximum current of the whole
range of units.
FWL/FWM/FWV
FWB
FWD
01
0.16 A
-
-
02
0.21 A
0.56 A
-
03
0.27 A
0.56 A
-
04
0.39 A
0.56 A
0.95 A
05
-
1.10 A
-
06
0.38 A
1.10 A
1.58 A
07
-
1.10 A
-
08
0.80 A
1.40 A
1.97 A
09
-
1.40 A
-
10
1.12 A
1.40 A
1.97 A
12
-
-
3.21 A
16
-
-
5.37 A
18
-
-
5.37 A
<=3 A
Master/Slave function is possible by installing the EPIMSA6.
>3 A
Installing EPIMSA6 you must install EPIB6.
>5 A
EPIB6 must be installed.
T
EchNical
S
pEcificaTiONS
EPIMSA6
EPIB6
Power supply
230 V
–15% +10% 50 Hz
Contacts at output
4x3A 250 V
1x16A 250 V
Operating temperature
0~40°C
Humidity limits (RH)
20~80% non-condensing
Protection rating
IP30
Container
105 x 90 x 70 mm
Weight
265 g
i
NSTallaTiON
n
All field wiring and components must be
installed by a licensed electrician and must
comply with relevant local and national
regulations.
n
Before obtaining access to terminals, all
power supply circuits must be interrupted.
n
The EPIMSA6 or EPIB6 interfaces are to be installed
on a DIN guide, usually housed in the electric boards
cabinet.
n
The overall dimensions of the EPIMSA6 and EPIB6
interface are shown in figure 3.
n
Make the electrical connections with POWER OFF as
indicated in the diagrams of figure 1+2 that show the
following:
Figure 1:
microprocessor-based cont 2x
EPIMSA6 connected to 8 units.
Figure 2:
connections of EPIB6
Each unit requires a switch (IL) on the power supply line
with a distance of at least 3 mm between the opening
contacts, and a suitable safety fuse (F).
NOTE
Connect only one unit per EPIMSA6 or
EPIB6 output.
EPIMSA6
EPIB6
Master/Slave interface
Power interface
Installation manual