background image

C

ontrols

www.DaikinApplied.com 17 

IM 1049-9

Table 5: MicroTech III unit controller terminals locations 

and descriptions

H1 – 1

24

24 VAC Power Input

H1 – 2

C

24 VAC common

H2 – 1

SL1

Fan Low Speed Output – Switched L1

H2 – 2

Blank Terminal

H2 – 3

N

Fan Low Speed Output – Neutral

H3 – 1

HP1-1

Comp High Pressure Switch (HP1) Input Terminal 1

H3 – 2

HP1-2

Comp High Pressure Switch (HP1) Input Terminal 2

H4 – 1

1

Discharge Air Temp Sensor – Common

H4 – 2

Discharge Air Temp Sensor – Signal

H4 – 3

Leaving Water Temp Sensor – Common

H4 – 4

Leaving Water Temp Sensor – Signal

H5 – 1

1

I/O Expansion Module Common (Gnd)

H5 – 2

I/O Expansion Module Common (Gnd)

H5 – 3

I/O Expansion 5 VDC

H5 – 4

I/O Expansion Module SPI CE1

H5 – 5

I/O Expansion Module SPI CLK

H5 – 6

I/O Expansion Module SPI OUT

H5 – 7

I/O Expansion Module SPI IN

H5 – 8

I/O Expansion 12 VDC

H5 – 9

I/O Expansion Module 24 VAC

H5 – 10

I/O Expansion Module 24 VAC

H5 – 11

No Connection

H5 – 12

No Connection

H6 – 1

1

Condensate Overflow Signal Input

H6 – 2

Comp#1 Suction Temp Sensor (LT1) – Common

H6 – 3

Comp#1 Suction Temp Sensor (LT1) – Signal

H6 – 4

Comp#1 Low Pressure Switch (LP1) – Source Voltage

H6 – 5

Comp#1 Low Pressure Switch (LP1) – Signal

H6 – 6

Reversing Valve#1 – Common

H6 – 7

Reversing Valve#1 – Output

H7 – 1

1

No Connection

H7 – 2

No Connection

H7 – 3

Red LED Output

H7 – 4

Green LED Output

H7 – 5

Yellow LED Output

H7 – 6

Red-Green-Yellow LED Common

H8 – 1

1

Isolation Valve/Pump Request Relay N/O

H8 – 2

Isolation Valve/Pump Request Relay N/C

H8 – 3

24 VAC Common

H9 – 1

1

Room Temp Sensor & Tenant Override – Signal

H9 – 2

Room Temp Sensor & Tenant Override – Common

TB1 – 1

1

Room Sensor – Status LED Output

TB1 – 2

2

Room Sensor – Fan Mode & Unit Mode Switches

TB1 – 3

3

Room Sensor – Setpoint Adjust

TB1 – 4

4

Room Sensor – Room Temp Sensor & Tenant Override

TB1 – 5

5

Room Sensor – DC Signal Common

TB2 – 1

R

24 VAC 

TB2 – 2

A

Alarm Output

TB2 – 3

W2

Thermostat – Heat Stage #2 Input

TB2 – 4

W1

Thermostat – Heat Stage #1 Input

TB2 – 5

Y2

Thermostat – Cool Stage #2 Input

TB2 – 6

Y1

Thermostat – Cool Stage #1 Input

TB2 – 7

G

Thermostat – Fan Input

TB2 – 8

O

Thermostat – Tenant Override Input

TB2 – 9

C

24 VAC Common

TB3 – 1

E

Emergency Shutdown Input

TB3 – 2

U

Unoccupied/Occupied Input

L1 – 1

L1 - 1

Line Voltage Terminal 1

L1 – 2

L1 - 2

Line Voltage Terminal 2

L1 – 3

L1 - 3

Line Voltage Terminal 3

N1

N1

Neutral Terminal 1

N2

N2

Neutral Terminal 2

N3

N3

Neutral Terminal 3

COMP

 Relay

SWL1

Switch – L1 Voltage

L1

No Connection

Table 6: MicroTech III Controller Configuration Jumper Settings

Baseboard Description

Jumper(s)

Jumper Setting

Function

Normal / Test Mode

JP1

Open

Normal Operation

Shorted

Service / Test Mode

Fan Operation

JP2   

Open

Continuous Fan Operation (On), when not operating in the unccupied mode.

Shorted

Cycling Fan Operation (Auto)

Loop Fluid

JP3

(see warning)

Open

Water freeze protection (factory default setting)

Shorted

Systems with anti-freeze protection

Alarm "A" Terminal Output Polarity

JP4

Open

Fault de-energizes alarm output to 0VAC.

Shorted

Fault energizes alarm output to 24VAC.

Room Sensor Setpoint 

Potentiometer Range

JP5

Open

Short Range: -3 to +3 ºF (-1.67 to +1.67 ºC) 

Shorted

Long Range: 55 to 95 ºF (12.78 to 35 ºC)

Thermostat / Room Sensor

JP6

Open

Thermostat Control

Shorted

Room Sensor Control

Not Used

JP7

Open

Not Used

JP8

Open

 

WARNING

Proper antifreeze/water solution is required to minimize the potential of fluid freeze-up. Jumper JP3 is factory set for water freeze protection with the jumper open. Operation with anti-freeze 
protection requires JP3 to be field configured for the jumper closed. If unit is employing a fresh water system (no anti-freeze protection), it is extremely important that JP3 jumper setting 

remains in the open position (factory default setting) in order to shut down the unit at the appropriate water temperature to protect your heat pump from freezing. Failure to do so can result 

in unit damage and fluid leaks.”

Содержание Enfinity CCW

Страница 1: ...Installation and Maintenance Manual IM 1049 9 Group WSHP Part Number 910258820 Date December 2018 Daikin Enfinity Horizontal Water Source Heat Pumps R 410A Refrigerant Model CCH CCW Unit Sizes 007 070...

Страница 2: ......

Страница 3: ...rt up 23 Changing PSC Fan Motor Speed 23 Optional EC Motor 25 Start up 26 Typical Wiring Diagrams 27 Thermostats Wall Sensors 32 Typical Connections For Thermostats Temperature Sensors 32 Additional A...

Страница 4: ...ht Discharge Air 09 13 E End Discharge S Straight Discharge Blower Motor 10 14 15 01 Standard PSC 03 Low Static 04 ECM Construction Type 12 18 A Standard 1 2 inch FG insulation 1 filter rack B Standar...

Страница 5: ...spection by the carrier s agent within fifteen 15 days of the delivery date and file a claim with the carrier CAUTION The installer must determine and follow all applicable codes and regulations This...

Страница 6: ...ts 5 Each unit is furnished with a hanger kit The kit is shipped unassembled and includes hanger brackets rubber isolators washers bolts and lock washers Lay out the threaded rods per the dimension in...

Страница 7: ...personal injury or death CAUTION Sharp edges can cause personal injury Avoid contact with them Use care and wear protective clothing safety glasses and gloves when handling parts and servicing heat pu...

Страница 8: ...Fan Motor Reinstall Top Completed End Discharge Assembly IM 1049 9 8 www DaikinApplied com 6 Lift the fan assembly out rotating it 180 degrees and position it within the opening at the end of the unit...

Страница 9: ...ace a straight length of duct 5 to 10 times the duct width before the next fitting to smooth out airflow Diffusers that are located in the bottom of a trunk duct can also produce noise For this same r...

Страница 10: ...gure 9 Standard 1 25mm Filter rack return air duct collar Standard 2 51mm Figure 10 Optional 2 51mm Filter rack return air duct collar Tool less Filter Removal Ventilation Air Ventilation may require...

Страница 11: ...Volt Operation All 208 230 volt single phase and three phase units are factory wired for 208 volt operation For 230 phase operation the line voltage tap on the 24 volt transformer must be changed Dis...

Страница 12: ...tape to assure a tight seal Figure 11 Sizes 007 through 060 shown Ball Valves Supply Riser Return Riser Condensate Riser Supply Air Hanger Kits 4 Flex Hoses Electrical Access Panel Note Do not over t...

Страница 13: ...an drain water 3 Shut off supplemental heater and circulator pump and open all drains and vents to completely drain down the system Short circuited supply and return runouts should now be connected to...

Страница 14: ...selection Some conditioners have built in time delays which prevent the compressor from immediately starting With most control schemes the fan will start immediately After a few minutes of compressor...

Страница 15: ...not for continuous duty Operating Mode Entering Air F Entering Water F Minimum Maximum Standard Range Extended Range DB WB DB WB Minimum Maximum Minimum Maximum Cooling 50 40 105 87 45 120 30 120 Amb...

Страница 16: ...al output to indicate an alarm condition exists Remote Reset of Automatic Lockouts The Remote Reset feature provides the means to remotely reset some lockouts There are 3 means to reset an automatic l...

Страница 17: ...larm Output TB2 3 W2 Thermostat Heat Stage 2 Input TB2 4 W1 Thermostat Heat Stage 1 Input TB2 5 Y2 Thermostat Cool Stage 2 Input TB2 6 Y1 Thermostat Cool Stage 1 Input TB2 7 G Thermostat Fan Input TB2...

Страница 18: ...s Jumper Setting Model Compressor Options JP1 JP1 Open Single Compressor Model factory default setting JP1 Shorted Dual Compressor Model Hot Gas Water Reheat HGR Dehumidification JP2 JP2 Open None def...

Страница 19: ...rned on This signal is detected by a pump restart relay providing a N O or N C set of contacts for heat pump loop circulation pump or motorized valve control When used with a system control by others...

Страница 20: ...apability of substituting the wall sensor with a duct mounted return air sensor Each unit controller orchestrates the following unit operations Enable heating and cooling to maintain setpoint based on...

Страница 21: ...ed that the MAC address dip switches on the communication module be set prior to installing the unit in the ceiling Access to the dip switches may be limited when the unit is installed Reference IM 92...

Страница 22: ...IM 1049 9 22 www DaikinApplied com Controls Figure 18 LonWorks Communication Module Placement on MicroTech III Unit Controller...

Страница 23: ...GRN RD LOW BLK HIGH Factory Wired WHT CAPACITOR LINE BRN FAN MOTOR Unit Sizes 015 and 024 all available voltages Fan motors on unit sizes 015 and 024 in all available voltages have a four position ter...

Страница 24: ...0 60 1 and 208 230 60 3 factory wired for low speed 1 YEL 2 BRN 3 BLK 4 RED LOW FACTORY WIRED LINE HIGH GR YE CAPACITOR FAN MOTOR Unit Size 048 380 50 3 460 60 3 575 60 3 The fan motor on unit size 04...

Страница 25: ...NE HIGH FACTORY WIRED GR YE CAPACITOR FAN MOTOR Unit Size 070 460 60 3 575 60 3 The fan motor on unit size 070 for voltages 460 60 3 and 575 60 3 Figure 32 have a five position terminal block and are...

Страница 26: ...g After a few minutes of operation check the discharge grilles for cool air delivery Measure the temperature difference between entering and leaving water It should be approximately 1 1 2 times greate...

Страница 27: ...sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow Sensor...

Страница 28: ...EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow Sen...

Страница 29: ...itch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board RAT Return Air Temp Sensor RV Reversing Valve Solenoid X1 Transformer _____ Standard Unit Wiring _ _ _ _...

Страница 30: ...LED Annunciator Harness LP Low Pressure Switch SLTS Suction Line Temp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board R1 Relay Fan Motor RAT Return Air Temp Sensor RV Reversing Val...

Страница 31: ...mp Sensor LWT Leaving Water Temp Sensor MIII MicroTech III Main Board RAT Return Air Temp Sensor RV Reversing Valve Solenoid X1 Transformer _____ Standard Unit Wiring _ _ _ _ Optional Wiring by others...

Страница 32: ...Y2 G C RH RC W2 A I O Expansion Module TB1 MicroTech III Controller Terminal TB2 Programmable Touch Screen Y1 1 Notes Includes thermostat and wall plate Refer to IO manual 910193127 Figure 41 Program...

Страница 33: ...132 910193133 910193134 P N 667720401 Sensors used with MicroTech III control Building Automated System Operation Figure 46 Digitally Adjustable Display Sensor 6 button P N 910121754 1 R 2 4 E U 6 5 3...

Страница 34: ...10121753 3 2 5 1 4 Figure 51 Adjustable Cool Warm with Occupancy Switch P N 910121753 NOTICE For 50Hz units it may be necessary to install a Ferrite Core Noise Suppresor on the thermostat cord cable w...

Страница 35: ...ssory used when up to 3 units are controlled from a single thermostat Typically the control panel and board is centrally mounted between the units and thermostat A maximum of 2 boards may be used toge...

Страница 36: ...a water source heat pump operates under a wide range of water and air temperatures the values printed below are to be taken as suggested pressure and temperatures All Daikin water source heat pumps a...

Страница 37: ...sure switch Unit is low on charge Table 14 Compressor Suction Temp Fail Room Temp Sensor Fail Leaving Water Temp Sensor Fail Description Type Yellow Green Red Compressor Suction Temp Sensor Fail Fault...

Страница 38: ...have a control signal or ready to operate when a control signal is active I O Expansion Module LED Faults For units with optional boilerless electric heat Table 22 Invalid Jumper Configuration Descrip...

Страница 39: ...Pressure Circuit 2 Description Type Yellow Green Red Low Pressure Circuit 2 Fault OFF OFF ON Loose wire connection on low pressure circuit Failed low pressure switch Unit is low on charge Table 28 Low...

Страница 40: ...Pressure Low Low Air Flow Heating High High High High Low High Low High Pressure Normal Low Air Flow Cooling Low Low Low Low High High Low Low Temp Normal Low Water Flow Heating Low Low Low Low High...

Страница 41: ...defective wiring or loose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal windings with ohm meter...

Страница 42: ...n flows as a low pressure gas through the reversing valve and back to the suction side of the compressor to complete the cycle Figure 59 Heating Mode Single Circuit Only Shown Return Air Thermal Expan...

Страница 43: ...roTech III unit controller s control or thermostat inputs However only one drive terminal R or C can be connected to any individual input terminal or damage may result Some control inputs are not acce...

Страница 44: ...of Air ____________________________________________________________________ Filters Clean _____________________________________________________________________________ Condensate Traps Installed _____...

Страница 45: ...be converted to GPM by looking in the equipment specificaton catalog Caution P GPM Note A conversion table must be used to find GPM from Delta P measurements Loop Fluid Temperature Rise Drop through...

Страница 46: ...page Model Serial H P EWT 3 LWT 4 EWP 1 LWP 2 EAT 5 LAT 6 Volts Amps Cool ing Check Air Filter and Coil Comments more comments on next sheet 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23...

Страница 47: ...Notes Comments Form WS CTS 00 01 Rev 4 14 www DaikinApplied com 47 IM 1049 9...

Страница 48: ...ndard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied representative for warranty details Refer to Form 933 430285Y To find your local Daikin Applied...

Отзывы: