Typical water source heat pump common design temperatures
Table 2: Typical water source heat pump common design temperatures
Operating
Mode
Entering Air °F
Entering Water °F
Minimum
Maximum
Standard Range
Extended Range
DB
WB
DB
WB
Minimum
Maximum
Minimum
Maximum
Cooling
75
63
80
67
85
100
85
100
Heating
60
–
70
–
60
70
40
70
Water source heat pump operating temperature limits (for continuous duty)
Table 3: Water source heat pump operating temperature limits (for continuous duty)
Operating
Mode
Entering Air °F
Entering Water °F
Minimum
Maximum
Standard Range
Extended Range
DB
WB
DB
WB
Minimum
Maximum
Minimum
Maximum
Cooling
65
55
85
71
55
110
50
110
Ambient
50
–
100
–
–
–
–
–
Heating
50
–
80
–
55
90
20
90
Ambient
50
–
85
–
–
–
–
–
Notes:
In the heating mode, the sum of the entering air + entering water must be ≥ 100°F. MINIMUM WATER FLOW =
1.5 GPM/Ton. Maximum and minimum values may not be combined. If one value is at maximum or minimum, the
other two conditions may not exceed the normal condition for standard units. Extended range units may combine
any two maximum conditions, but not more than two, with all other conditions being normal conditions.
Water source heat pump operating temperature limits at start-up (not for continuous duty)
Table 4: Water source heat pump operating temperature limits at start-up (not for continuous duty)
Operating
Mode
Entering Air °F
Entering Water °F
Minimum
Maximum
Standard Range
Extended Range
DB
WB
DB
WB
Minimum
Maximum
Minimum
Maximum
Cooling
50
40
105
87
45
120
30
120
Ambient
45
–
110
–
–
–
–
–
Heating
40
–
85
–
40
95
20
100
Ambient
40
–
85
–
–
–
–
–
www.DaikinApplied.com 15
IM 1049-9
Standard Range Units:
Units are designed to start in an ambient of 50°F (10°C)
with entering air at 50°F (10°C), with entering water at
50°F (10°C), with nominal air flow and water flow (3.0
GPM/Ton), for initial start-up in heating.
Note:
This is not a normal or continuous operating
condition. It is assumed that such start-up is for
the purpose of bringing the building space up to
occupancy temperature.
Geothermal Range Units:
Units are designed to start in an ambient of 40°F (5°C)
with entering air at 40°F (5°C), with entering water at
20°F (-7°C), with nominal air flow and water flow (3.0
GPM/Ton), for initial start-up in heating.
Note:
This is not a normal or continuous operating
condition. It is assumed that such start-up is for
the purpose of bringing the building space up to
occupancy temperature.
Environment
This equipment is designed for indoor installation
only. Sheltered locations such as attics, garages, etc.,
generally will not provide sufficient protection against
extremes in temperature and/or humidity, and equipment
performance, reliability, and service life may be
adversely affected.
Power supply
A voltage variation of +/-10% of nameplate voltage is
acceptable. Three-phase system imbalance shall not
exceed 2%.