15 Unit installation
WARNING
In case of R32 refrigerant, the installation MUST comply with the requirements that
apply to this R32 equipment. For more information, see
equipment using R32 refrigerant"
In this chapter
15.1 Preparing the installation site
Choose an installation location with sufficient space for carrying the unit in and out
of the site.
Avoid installation in an environment with a lot of organic solvents such as ink and
siloxane.
Do NOT install the unit in places often used as work place. In case of construction
works (e.g. grinding works) where a lot of dust is created, the unit MUST be
covered.
Avoid direct sunlight on the unit (e.g. false ceiling exposed to natural light).
15.1.1 Installation site requirements of the indoor unit
INFORMATION
Also read the general installation site requirements. See the "
INFORMATION
The sound pressure level is less than 70 dBA.
NOTICE
The equipment described in this manual may cause electronic noise generated from
radio-frequency energy. The equipment complies to specifications that are designed
to provide reasonable protection against such interference. However, there is no
guarantee that interference will NOT occur in a particular installation.
It is therefore recommended to install the equipment and electric wires in such a
way that they keep a proper distance from stereo equipment, personal computers,
etc.
In places with weak reception, keep distances of 3 m or more to avoid
electromagnetic interference of other equipment and use conduit tubes for power
and transmission lines.
Do NOT install the unit in the following places: